COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

EABD-F036S, EABD-(T,W)036S**

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC/PC/UC48

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

 

1000

 

 

 

 

1200

 

 

 

 

1400

 

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

 

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

 

T.C.

35.0

37.8

37.5

41.8

46.7

37.1

39.1

38.7

43.0

47.4

39.1

40.4

39.9

44.2

48.1

 

65

S.C.

33.9

31.5

26.9

26.8

22.0

36.0

34.7

29.4

29.0

23.8

38.1

37.9

31.8

31.3

25.5

 

 

K.W.

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

 

 

T.C.

33.5

35.8

35.6

39.6

44.3

35.4

37.0

36.8

40.7

45.2

37.4

38.2

37.9

41.8

46.0

 

75

S.C.

32.4

30.5

26.0

26.0

21.2

34.4

33.5

28.4

28.2

22.9

36.4

36.5

30.8

30.5

24.6

 

 

K.W.

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.2

 

 

T.C.

32.0

33.8

33.8

37.4

41.9

33.8

34.9

34.9

38.4

42.9

35.6

36.0

36.0

39.4

43.8

 

85

S.C.

31.0

29.5

25.1

25.1

20.3

32.8

32.3

27.5

27.4

22.0

34.7

35.1

29.8

29.8

23.7

 

 

K.W.

2.3

2.3

2.3

2.3

2.4

2.3

2.3

2.3

2.3

2.4

2.3

2.3

2.3

2.3

2.4

 

 

T.C.

30.5

31.8

31.9

35.1

39.6

32.1

32.8

33.0

36.1

40.6

33.8

33.8

34.1

37.0

41.7

 

95

S.C.

29.5

28.4

24.3

24.2

19.5

31.2

31.1

26.6

26.6

21.2

33.0

33.7

28.8

29.0

22.8

 

 

K.W.

2.4

2.5

2.5

2.5

2.6

2.5

2.5

2.5

2.5

2.6

2.5

2.5

2.5

2.5

2.6

 

 

T.C.

29.0

29.9

29.8

32.9

36.9

30.5

30.8

30.8

33.7

37.8

31.9

31.7

31.7

34.5

38.7

 

105

S.C.

28.1

27.5

23.4

23.3

18.6

29.6

29.7

25.7

25.7

20.2

31.2

31.9

28.0

28.0

21.8

 

 

K.W.

2.7

2.7

2.7

2.7

2.8

2.7

2.7

2.7

2.7

2.8

2.7

2.7

2.7

2.8

2.8

 

 

T.C.

27.7

28.0

27.9

30.7

34.2

28.9

28.9

28.6

31.3

35.0

30.1

29.8

29.3

32.0

35.8

 

115

S.C.

26.8

26.6

22.6

22.4

17.7

28.1

28.4

24.9

24.7

19.2

29.4

30.2

27.1

27.0

20.8

 

 

K.W.

2.9

2.9

2.8

2.9

3.0

2.9

2.9

2.9

3.0

3.0

3.0

2.9

2.9

3.0

3.1

 

 

T.C.

26.3

26.1

25.9

28.5

31.6

27.3

27.0

26.4

29.0

32.3

28.3

27.8

27.0

29.5

32.9

 

125

S.C.

25.5

25.7

21.8

21.5

16.8

26.6

27.1

24.0

23.8

18.3

27.6

28.4

26.3

26.0

19.8

 

 

K.W.

3.1

3.1

3.0

3.1

3.2

3.1

3.1

3.1

3.2

3.3

3.2

3.2

3.1

3.2

3.3

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

 

 

 

 

**

For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.

 

 

 

 

 

 

 

 

 

 

 

 

Multipliers for determining the performance with other indoor sections

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

MA12B

FC/MC35B

0.99

0.99

0.99

MA12B

FC/MC42B

0.99

0.99

0.99

MA16C

FC/MC35C

0.99

0.99

0.99

MA16C

FC/MC42C

0.99

0.99

0.99

MA14D

FC/MC48D

1.00

1.00

1.00

AHP36

0.98

0.99

0.98

F*FP040

0.99

0.99

0.99

F*FP042

0.99

0.99

0.99

MV16C*

FC/MC35C

1.01

0.98

0.97

MV16C*

FC/MC42C

1.01

0.98

0.97

MV16C*

FC/MC48C

1.01

0.98

0.97

MV20D*

FC/MC48D

1.01

0.98

0.97

AV36*

1.01

0.98

0.97

FC/MC/PC/35

0.99

0.99

0.99

FC/MC/PC/UC42

0.99

0.99

0.99

HC42

0.98

0.96

0.98

HD36

0.98

0.98

0.98

*= Single-phase outdoor units only.

Variable Speed

Coil

T.C.

S.C.

KW

Furnace *

 

 

 

 

(F,L)L8VB16

FC/MC/PC35B

1.01

1.00

0.96

FL9(C,V)B12

FC/MC/PC35B

1.01

1.00

0.96

(F,L)L8VC16

FC/MC/PC35C

1.01

1.00

0.96

(F,L)L8VC20

FC/MC/PC35C

1.01

1.00

0.96

FL9(C,V)C16

FC/MC/PC35C

1.00

1.00

1.00

FL9(C,V)C20

FC/MC/PC35C

1.00

0.99

0.96

(F,L)L8VB16

FC/MC/PC42B

1.01

1.00

0.96

FL9(C,V)B12

FC/MC/PC42B

1.01

1.00

0.96

(F,L)L8VC16

FC/MC/PC42C

1.01

1.00

0.96

(F,L)L8VC20

FC/MC/PC42C

1.01

1.00

0.96

FL9(C,V)C16

FC/MC/PC42C

1.00

1.00

1.00

FL9(C,V)C20

FC/MC/PC42C

1.00

0.99

0.96

(F,L)L8VC20

FC/MC/PC48C

1.01

1.00

0.97

FL9(C,V)C16

FC/MC/PC48C

1.01

1.00

0.97

FL9(C,V)C20

FC/MC/PC48C

1.01

0.99

0.97

FL9(C,V)D20

FC/MC/PC48D

1.01

1.00

0.97

(F,L)L8VC20

HC42

1.01

0.99

0.96

FL9(C,V)C16

HC42

1.00

1.00

1.00

FL9(C,V)C20

HC42

1.00

1.00

0.96

(F,L)L8VC20

HD36

1.01

1.01

0.96

FL9(C,V)C16

HD36

1.00

1.00

1.00

FL9(C,V)C20

HD36

1.00

1.00

0.96

*= Single-phase outdoor units only.