510667-YTG-B-0509

HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJF42S41S1

 

 

 

 

 

 

 

EVAPORATOR COIL MODEL NO

AHX60

 

 

 

 

 

 

 

 

AIR TEMP.

AIR TEMP.

 

 

 

 

ID CFM

 

 

 

 

ENTERING

ENTERING

 

1200

 

 

1400

 

 

1600

 

OUTDOOR UNIT

INDOOR COIL

 

 

 

 

 

 

 

 

 

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

 

 

 

 

 

 

 

 

 

 

 

 

60

45.3

4.1

2.8

45.0

4.1

2.7

44.6

4.2

2.6

60

 

 

 

 

 

 

 

 

 

 

70

45.1

3.8

3.0

44.9

3.8

2.9

44.6

3.9

2.8

 

 

 

 

 

 

 

 

 

 

 

 

80

44.9

3.5

3.3

44.8

3.6

3.1

44.7

3.6

3.0

 

 

 

 

 

 

 

 

 

 

 

 

60

41.3

4.1

2.5

41.2

4.1

2.5

41.1

4.1

2.4

47

 

 

 

 

 

 

 

 

 

 

70

40.7

3.6

2.8

40.7

3.7

2.7

40.7

3.7

2.6

 

 

 

 

 

 

 

 

 

 

 

 

80

40.0

3.3

3.1

40.2

3.3

3.0

40.3

3.4

2.9

 

 

 

 

 

 

 

 

 

 

 

 

60

38.2

3.8

2.5

38.4

3.9

2.4

38.5

3.9

2.3

40

 

 

 

 

 

 

 

 

 

 

70

37.4

3.4

2.8

37.7

3.5

2.7

38.1

3.5

2.6

 

 

 

 

 

 

 

 

 

 

 

 

80

36.6

3.1

3.0

37.1

3.1

3.0

37.7

3.2

2.9

 

 

 

 

 

 

 

 

 

 

 

 

60

33.3

3.4

2.4

33.4

3.4

2.4

33.5

3.4

2.3

30

 

 

 

 

 

 

 

 

 

 

70

32.7

3.0

2.7

32.8

3.1

2.6

32.9

3.1

2.5

 

 

 

 

 

 

 

 

 

 

 

 

80

32.0

2.7

3.0

32.2

2.8

2.9

32.3

2.8

2.8

 

 

 

 

 

 

 

 

 

 

 

 

60

26.7

2.9

2.2

26.9

2.9

2.2

27.2

2.8

2.2

17

 

 

 

 

 

 

 

 

 

 

70

25.2

2.5

2.5

20.9

2.5

2.4

26.7

2.5

2.5

 

 

 

 

 

 

 

 

 

 

 

 

80

23.6

2.1

2.8

14.9

2.2

2.7

26.3

2.3

2.7

 

 

 

 

 

 

 

 

 

 

 

 

60

22.8

2.5

2.3

23.3

2.5

2.2

23.8

2.5

2.2

10

 

 

 

 

 

 

 

 

 

 

70

22.9

2.2

2.6

23.2

2.3

2.5

23.6

2.3

2.4

 

 

 

 

 

 

 

 

 

 

 

 

80

22.9

2.1

2.8

23.1

2.1

2.8

23.3

2.1

2.7

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

MBH

KW

COP

F6FP060

1.01

1.01

1.00

MV20D

FC/MC62D

1.00

1.01

1.00

Furnace

Coil

MBH

KW

COP

T*(8,L)X*C16

FC/MC62D

1.00

1.02

0.99

T*(8,L)X*C20

FC/MC62D

1.01

1.02

0.99

T*9X*C16

FC/MC62D

1.01

1.00

1.02

T*9X*C20

FC/MC62D

1.00

1.01

1.00

T*9X*D20

FC/MC62D

1.00

1.01

1.00

Y*(8,L)C*C20

FC/MC62D

1.01

1.00

1.01

(Y*9C/T*9V)*C16

FC/MC62D

1.02

0.97

1.06

(Y*9C/T*9V)*C20

FC/MC62D

1.01

0.98

1.04

(Y*9C/T*9V)*D20

FC/MC62D

1.01

0.99

1.03

24

Johnson Controls Unitary Products

Page 24
Image 24