HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJF60S41S1

 

 

 

 

 

 

 

EVAPORATOR COIL MODEL NO

AHX60

 

 

 

 

 

 

 

 

AIR TEMP.

AIR TEMP.

 

 

 

 

ID CFM

 

 

 

 

ENTERING

ENTERING

 

1600

 

 

1800

 

 

2000

 

OUTDOOR UNIT

INDOOR COIL

 

 

 

 

 

 

 

 

 

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

 

60

70.70

4.28

4.25

71.76

4.41

4.11

72.83

4.54

3.97

60

70

69.78

3.85

4.72

70.63

3.95

4.57

71.49

4.07

4.41

 

80

68.86

3.48

5.19

69.51

3.58

5.03

70.15

3.67

4.86

 

60

61.77

3.89

4.05

62.15

3.97

3.92

62.54

4.05

3.78

47

70

60.84

3.47

4.53

61.18

3.55

4.39

61.52

3.62

4.23

 

80

59.90

3.13

5.01

60.20

3.19

4.86

60.50

3.27

4.69

 

60

56.20

3.64

3.93

56.47

3.70

3.80

56.74

3.76

3.69

40

70

55.47

3.24

4.42

55.62

3.30

4.27

55.76

3.35

4.13

 

80

54.75

2.92

4.90

54.77

2.96

4.75

54.79

3.02

4.57

 

60

49.33

3.30

3.78

49.52

3.33

3.70

49.72

3.34

3.61

30

70

47.84

2.83

4.36

47.68

2.87

4.21

47.52

2.90

4.06

 

80

46.36

2.45

4.94

45.84

2.49

4.71

45.31

2.53

4.51

 

60

40.18

2.78

3.64

37.45

2.80

3.50

34.72

2.80

3.40

17

70

40.02

2.47

4.14

38.68

2.60

4.00

37.36

2.50

3.91

 

80

39.86

2.23

4.65

39.91

2.25

4.53

39.99

2.27

4.42

 

60

35.02

2.49

3.52

35.29

2.51

3.45

35.54

2.53

3.38

10

70

33.76

2.16

3.98

34.56

2.22

3.90

35.35

2.27

3.82

 

80

32.50

1.89

4.44

33.83

1.97

4.34

35.15

2.06

4.26

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

MBH

KW

COP

MV20D

FC/MC62D

0.99

1.00

0.99

Furnace

Coil

MBH

KW

COP

T*(8,L)X*C20

FC/MC62D

0.97

0.89

1.10

T*9X*C20

FC/MC62D

1.00

1.01

1.00

T*9X*D20

FC/MC62D

1.00

1.02

0.99

Y*(8,L)C*C20

FC/MC62D

0.99

0.95

1.04

(Y*9C/T*9V)*C20

FC/MC62D

0.99

0.96

1.04

(Y*9C/T*9V)*D20

FC/MC62D

1.00

0.97

1.03

Subject to change without notice. Published in U.S.A.

510667-YTG-B-0509

Copyright © 2009 by Johnson Controls, Inc. All rights reserved.

Supersedes: 510667-YTG-A-0409

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 73069

Page 26
Image 26