510667-YTG-B-0509

HEATING CAPACITY - With High Efficiency Motor Furnaces (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

FURNACE

COIL1

 

 

 

ARI HEATING2

 

 

 

MODEL

MODEL

 

47°F

 

 

 

 

17°F

 

HSPF

 

 

 

MBH

COP

KW

 

MBH

 

COP

KW

STD

 

T*(8,L)X*A12

FC/MC/PC37A

36.0

3.80

2.78

 

24.6

 

2.54

2.84

8.50

 

T*(8,L)X*B12

FC/MC/PC43B

36.0

3.80

2.78

 

24.6

 

2.54

2.84

8.50

 

T*(8,L)X*C16

FC/MC/PC43C

36.0

3.78

2.79

 

24.0

 

2.56

2.75

9.00

 

T*(8,L)X*C20

FC/MC/PC43C

36.0

3.88

2.72

 

24.4

 

2.60

2.75

9.00

 

T*9X*B12

FC/MC/PC43B

36.0

3.80

2.78

 

24.6

 

2.54

2.84

8.50

YHJF36S41S1

T*9X*C16

FC/MC/PC43C

36.0

3.82

2.76

 

24.4

 

2.56

2.79

8.50

 

T*9X*C20

FC/MC/PC43C

36.0

3.74

2.82

 

24.2

 

2.52

2.81

8.50

 

Y*(8,L)C*C16

FC/MC/PC43C

36.0

3.72

2.84

 

24.4

 

2.50

2.86

8.50

 

Y*(8,L)C*C20

FC/MC/PC43C

36.0

3.74

2.82

 

24.2

 

2.52

2.81

8.50

 

(Y*9C/T*9V)*C16

FC/MC/PC43C

36.0

3.76

2.81

 

24.6

 

2.52

2.86

8.50

 

(Y*9C/T*9V)*C20

FC/MC/PC43C

36.0

3.70

2.85

 

24.4

 

2.50

2.86

8.50

 

T*(8,L)X*C16

FC/MC62D

40.5

4.06

2.92

 

26.0

 

2.78

2.74

9.00

 

T*(8,L)X*C20

FC/MC62D

41.0

4.08

2.94

 

26.2

 

2.78

2.76

9.00

 

T*9X*C16

FC/MC62D

41.0

3.98

3.02

 

26.2

 

2.72

2.82

9.00

 

T*9X*C20

FC/MC62D

40.5

4.02

2.95

 

26.2

 

2.74

2.80

9.00

YHJF42S41S1

T*9X*D20

FC/MC62D

40.5

4.02

2.95

 

26.0

 

2.76

2.76

9.00

Y*(8,L)C*C16

FC/MC62D

41.0

3.96

3.03

 

26.4

 

2.70

2.86

9.00

 

 

 

 

Y*(8,L)C*C20

FC/MC62D

41.0

4.00

3.00

 

26.2

 

2.74

2.80

9.00

 

(Y*9C/T*9V)*C16

FC/MC62D

41.5

3.86

3.15

 

26.6

 

2.64

2.95

9.00

 

(Y*9C/T*9V)*C20

FC/MC62D

41.0

3.90

3.08

 

26.4

 

2.68

2.89

9.00

 

(Y*9C/T*9V)*D20

FC/MC62D

41.0

3.94

3.05

 

26.4

 

2.70

2.86

9.00

 

T*(8,L)X*C16

FC/MC62D

48.0

3.78

3.72

 

32.0

 

2.56

3.66

9.00

 

T*(8,L)X*C20

FC/MC62D

48.0

3.80

3.70

 

31.8

 

2.58

3.61

9.00

 

T*9X*C16

FC/MC62D

48.0

3.76

3.74

 

32.0

 

2.56

3.66

9.00

 

T*9X*C20

FC/MC62D

48.0

3.80

3.70

 

32.0

 

2.58

3.63

9.00

YHJF48S41S1

T*9X*D20

FC/MC62D

48.0

3.76

3.74

 

32.0

 

2.56

3.66

9.00

 

Y*(8,L)C*C20

FC/MC62D

48.0

3.76

3.74

 

32.0

 

2.56

3.66

9.00

 

(Y*9C/T*9V)*C16

FC/MC62D

48.0

3.72

3.78

 

32.2

 

2.54

3.71

9.00

 

(Y*9C/T*9V)*C20

FC/MC62D

48.0

3.68

3.82

 

32.4

 

2.50

3.80

9.00

 

(Y*9C/T*9V)*D20

FC/MC62D

48.0

3.72

3.78

 

32.2

 

2.52

3.74

9.00

1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

2.Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.

3.Variable speed furnaces have B.O.D (Blower on Delay) standard.

CP equals MBH output divided by (total KW input x 3.412).

HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.