HEATING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

YZB06012

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC62D

 

 

 

 

 

 

 

 

AIR TEMP.

AIR TEMP.

 

 

 

 

 

ID CFM

 

 

 

 

ENTERING

ENTERING

 

 

1650

 

 

1900

 

 

2150

 

OUTDOOR UNIT

INDOOR COIL

 

 

 

 

 

 

 

 

 

 

MBTUH

 

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

 

60

71.5

 

4.9

4.3

72.1

4.8

4.4

72.7

4.6

4.6

60

 

 

 

 

 

 

 

 

 

 

 

70

70.3

 

5.4

3.8

70.9

5.3

3.9

71.5

5.1

4.1

 

 

 

 

 

 

 

 

 

 

 

 

 

80

69.2

 

5.9

3.4

69.8

5.8

3.5

70.3

5.6

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

60

61.1

 

4.8

3.8

61.2

4.7

3.8

61.4

4.6

3.9

47

 

 

 

 

 

 

 

 

 

 

 

70

60.3

 

5.3

3.4

60.6

5.2

3.4

60.8

5.1

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

80

59.6

 

5.8

3.0

59.9

5.7

3.1

60.2

5.6

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

60

53.5

 

4.7

3.3

50.2

4.6

3.2

47.0

4.6

3.0

40

 

 

 

 

 

 

 

 

 

 

 

70

53.7

 

5.3

3.0

52.0

5.1

3.0

50.4

5.0

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

80

53.9

 

5.9

2.7

53.8

5.6

2.8

53.8

5.4

2.9

 

 

 

 

 

 

 

 

 

 

 

 

 

60

43.9

 

4.6

2.8

42.5

4.5

2.8

41.1

4.5

2.7

30

 

 

 

 

 

 

 

 

 

 

 

70

44.0

 

5.2

2.5

42.6

5.1

2.4

41.1

5.1

2.4

 

 

 

 

 

 

 

 

 

 

 

 

 

80

44.2

 

5.8

2.2

42.7

5.7

2.2

41.2

5.6

2.1

 

 

 

 

 

 

 

 

 

 

 

 

 

60

35.4

 

4.4

2.4

35.0

4.3

2.4

34.6

4.3

2.4

17

 

 

 

 

 

 

 

 

 

 

 

70

35.0

 

4.9

2.1

35.3

4.9

2.1

35.7

4.8

2.2

 

 

 

 

 

 

 

 

 

 

 

 

 

80

34.5

 

5.4

1.9

35.7

5.4

1.9

36.8

5.4

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

60

30.7

 

4.4

2.1

28.9

4.3

2.0

27.2

4.3

1.9

10

 

 

 

 

 

 

 

 

 

 

 

70

30.9

 

4.9

1.8

30.0

4.9

1.8

29.1

4.9

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

80

31.1

 

5.5

1.7

31.0

5.4

1.7

31.0

5.4

1.7

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

 

MBH

KW

COP

MV20D

 

FC/MC62D

1.00

1.01

0.99

MA20D

 

FC/MC62D

1.00

1.00

1.00

Variable Speed

Coil

MBH

KW

COP

Furnace

 

 

 

 

P(C,V)9*D20

FC/MC62D

0.96

1.01

0.99

Y*(8,L)C*C20

FC/MC62D

0.98

1.00

0.98

Y*9C*C20

FC/MC62D

0.99

0.99

1.00

Y*9C*D20

FC/MC62D

0.99

0.99

1.00

G*9V*C20

FC/MC62D

0.99

0.99

1.00

G*9V*D20

FC/MC62D

0.99

0.99

1.00

Subject to change without notice. Printed in U.S.A.

271457-YTG-B-0908

Copyright © 2008 by Johnson Controls, Inc. All rights reserved.

Supersedes: 271457-YTG-A-0907

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 73069

Page 40
Image 40
York YZB018 THRU 060 warranty Outdoor Unit Model No, YZB06012, Indoor Coil Model No, FC/MC62D, Norman, OK