Pentair NT Series installation manual Indoor Venting General Requirements

Page 14

Section III. Installation

14

 

 

INDOOR VENTING — General Requirements

The vent pipe must be the same size or larger. The MiniMax NT heaters are capable of a 360-degree discharge rotation and operate with a positive vent static pressure and with a vent gas temperature less than 400° F. The total length of the horizontal run must not exceed the length that is listed below in the tables.

NOTE

The allowable vent runs for each vent pipe diameter are different and can not be exceeded.

Each 90-degree elbow reduces the maximum horizontal vent run by 8 feet and each 45-degree elbow in the vent run reduces the maximum vent run by 4 feet. See the tables below for the maximum vent lengths using 90-degree and 45-degree elbows.

The MiniMax NT is a “Category III” appliance and is an induced-draft pool and spa heater which uses positive pressure to push flue gases through the vent pipe to the outside. This requires a completely sealed vent system—single wall vent pipe with sealed-seams and joints. Flue gases under positive pressure may escape into the dwelling with any cracks or loose joints in the vent pipe, or improper vent installation. The vent pipe must be of a sealed-seam construction, such as those listed for use with “Category III Appliances”, and for operating temperatures less than 400° F. The use of listed thimbles, roof jacks and/or side vent terminals are required; and the proper clearances to combustible materials must be maintained in accordance with type of vent pipe employed—in the absence of a clearance recommendation by the vent pipe manufacturer, the requirements of the Uniform Mechanical Code should be met. The ventilation air requirements for the MiniMax NT heater can be

4 inch Vent Pipe

Number of

Maximum

Elbows

Vent Run

 

 

90°

45°

(Feet)

 

 

 

1

22

 

 

 

1

1

18

 

 

 

1

2

14

 

 

 

2

14

 

 

 

found on page 16. It is recommended that vent runs over 18 feet be insulated to reduce condensation related problems and/or the use of a condensate trap in the vent run close to the heater may be necessary in certain installations such as cold climates. The MiniMax NT heater is suitable for through-the- wall venting, see table and dimensions below.

Recommended sources for Side-wall vent hood terminals include: The Field Controls Co. (2308 Airport Road, Kingston, NC 28501, (800)742-8368) and Tjernlund Products Inc. (1601 Ninth Street, White Bear Lake, MN 55110, (800) 255-4208)— consult manufacturer for model information and availability.

CAUTION

Do NOT combine exhaust vent pipes to a common exhaust vent in multiple unit installations. Run separate vent pipes.

 

 

 

 

 

Table 8.

 

 

 

 

 

 

5 inch Vent Pipe

5 inch Vent Pipe

 

 

 

 

 

 

Number of

Maximum

Number of

Maximum

Elbows

Elbows

Vent Run

Vent Run

 

 

 

 

90°

45°

(Feet)

90°

45°

(Feet)

 

 

 

 

 

 

0

2

45

2

2

29

 

 

 

 

 

 

1

45

2

3

25

 

 

 

 

 

 

1

1

41

2

4

21

 

 

 

 

 

 

1

2

37

3

29

 

 

 

 

 

 

1

3

33

3

1

25

 

 

 

 

 

 

2

37

3

2

21

 

 

 

 

 

 

2

1

33

4

21

 

 

 

 

 

 

 

 

 

 

 

Table 9.

THROUGH WALL VENT KITS FOR HEATERS

Part

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

471532

4

in. Dia.

6

in. Dia.

8½ in.

6 5/16 in.

12

5/8 in.

10

5/8 in.

 

 

 

 

 

 

 

 

 

 

 

471543

5

in. Dia.

8

in. Dia.

8½ in.

8 in.

12

5/8 in.

10

5/8 in.

 

 

 

 

 

 

 

 

 

 

 

Table 10.

C F

B AE

D

Figure 5.

P/N 472235

Rev. E 4-15-05

Image 14
Contents MiniMax NT Series Customer Service Table of Contents Heater Identification Information Heater Identification Information HINWarranty Information Important NoticesConsumer Information and Safety Code RequirementsInstallation Instructions SpecificationsPlumbing Connections Below Pool InstallationBelow or Above Pool Installation ValvesWater Connections Reversing HeadersReversible Inlet/Outlet Connection, cont’d Sediment Traps GAS Line InstallationsGAS Connections GAS Pipe Sizing Pipe Sizing for GAS Line ConnectionsTesting GAS Pressure GAS Pressure RequirementsIndoor Venting General Requirements Indoor Installation USA only Outdoor Shelter Installation CanadaFits ALL Models Combustion AIR SupplyVent Adaptors Indoor Installations Minimax NT Venting Guidelines Outdoor Installation Venting Guidelines Side View Outdoor Vent KITElectrical Rating 60 Hz 120 / 240 Volts AC, single phase Electrical ConnectionsWiring DIAGRAM-NT STD & TSI with Ddtc MiniMax NT TSI & STD W/DDTC Wiring DiagramBasic System Operation Minimax NT HSI Electronic Ignition LIGHTING/OPERATIONWater Pressure Switch Safety ControlsVacuum AIR Pressure FAN Switch Thermal FuseOperation of Ignition Module Heat ModeHigh Limits Failure to Light the BURNER-LOCK OUTDigital Display Temperature Controller Ddtc System Indicator LightsSection IV. Operation SET UP Temperature Setting Troubleshooting Instruction Troubleshooting DdtcTroubleshooting General Service CHECKS-IGNITION ModuleMaintenance Instruction Energy Saving TipsSpring and Fall Operation Winter OperationChemical Balance Pool and SPA WaterReplacement Parts For Stdonly onlyRev. E Rev. E NT TSI w/DDTC 400 Model Starting w/Serial No Rev. E Rev. E Rev. E Pentair Water Pool and Spa, Inc Guide Dinstallation ET DE Fonctionnement Chauffe-eau pour piscine et spa MiniMax NTService Clients Table des matières Information Pour Lidentification DU CHAUFFE-EAU Information Pour Lidentification DU CHAUFFE-EAUConsignes Importantes GarantieInformation ET Recommandations À Lintention DU Consommateur Conformité AUX CodesConsignes dinstallations SpécificationsDérivation Manuelle Raccords DE PlomberieSoupapes Raccordements DES Conduites Deau Collecteurs réversiblesRaccords dentrée et de sortie réversibles, suite Collecteurs DE Sédiment Installations DE LA Conduite DE GAZRaccordement DES Conduites DE GAZ Dimension DES Tuyaux DE GAZ Mesure DES Tuyaux Pour Raccords D’ARRIVÉE DE GAZVérification DE LA Pression DE GAZ Le côté admission de la soupape de gazVentilation Intérieur Exigences Générales Installation Intérieure États-Unis Uniquement Convient À Tous LES Modèles Admission Dair DE CombustionAdaptateurs Daération Conseils Pour Linstallation Intérieur DU Minimax NT Ensemble DE Ventilation Pour Lextérieur Terminaison de la ventilationRaccordements Électriques Classement électrique 60 Hz 120/240 Volts c.a. monophaséWire Color Couleur DU Cable Consignes de Fonctionnement Fonctionnement Générale DU SystèmeCommutateur DE Pression Deau Contrôles DE SécuritéCommutateur Ventilateur DE Pression DU Vide Dair Fusible ThermiqueVerrouillage EN CAS Déchec Dallumage Mode ChaleurHautes Limites Échec DE LA Flamme RallumageThermostat À Affichage Numérique Témoins Indicateurs DU SystèmeSection IV. Fonctionnement Réglage DU Thermostat Réglage DE LA Temperature Consignes DE Dépannage Dépannage Thermostat a Affichage NumeriqueConsignes DE Dépannage Verifications Dentretien Module DallumageConseils Pour Économies Dénergie Soupape DE SurpressionFonctionnement AU Printemps ET EN Automne Fonctionnement EN HiverÉquilibre Chimique DE Leau EAU DE Piscine ET DE SPAPièces DE Remplacement OnlyRev. E Pièces de Rechange pour La Série de Pièces DE Remplacement Rev. E Annote Annote Veuillez Concerver CE Guide Dinstruction

NT Series specifications

Pentair is a renowned name in the realm of water filtration and fluid management solutions, and the NT Series stands out as a key player in their extensive product lineup. Engineered for optimal performance and reliability, the NT Series showcases innovative features and technologies that cater to various water treatment needs.

One of the defining characteristics of the Pentair NT Series is its exceptional filtration capabilities. These filters are designed to effectively remove sediments, chlorine taste and odor, and other contaminants, ensuring clean and safe drinking water. With a multi-stage filtration process, the NT Series utilizes advanced materials and technologies that enhance filtration efficiency and longevity.

The NT Series is equipped with advanced filter media that can capture particles as small as 0.5 microns. This level of filtration is essential for households and commercial applications, where water quality is paramount. The filters are also designed for easy replacement, ensuring minimal downtime and ease of maintenance for users.

Another prominent feature of the NT Series is its compact design, making it suitable for various installation spaces. The filters are engineered to maximize flow rate while maintaining high filtration efficiency, ensuring that users do not experience reduced water pressure. This balance of performance and design is integral, especially in demanding applications.

Moreover, the NT Series incorporates innovative technology to monitor filter life and performance. Several models come with built-in sensors that provide real-time data on filter conditions, allowing users to know when it's time for a replacement. This proactive approach to maintenance enhances user experience and ensures continued access to high-quality water.

The materials used in the NT Series are also noteworthy. Constructed from durable, corrosion-resistant components, these filters are designed to withstand harsh operating conditions while maintaining peak performance over time. This enhances the overall lifespan of the product, providing users with a reliable and long-lasting solution for their water filtration needs.

In summary, the Pentair NT Series represents a blend of advanced filtration technology, user-friendly design, and durable construction. With its ability to remove various contaminants, easy maintenance features, and compact design, the NT Series caters to residential and commercial users alike. Investing in the NT Series ensures access to clean, great-tasting water while enjoying the benefits of reliable and efficient filtration technology.