Lennox International Inc G61MP Series Units, Gas Units installation instructions Electrical

Models: G61MP Series Units Gas Units

1 64
Download 64 pages 11.85 Kb
Page 35
Image 35
Electrical

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

Manual backgroundCAUTION

Electrostatic discharge can affect electronic com- ponents. Take precautions during furnace installa- tion and service to protect the furnace’s electronic controls. Precautions will help to avoid control ex- posure to electrostatic discharge by putting the fur- nace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an un- painted unit surface, such as the gas valve or blower deck, before performing any service procedure.

INTERIOR MAKE−UP BOX INSTALLATION

MAKE−UP

BOX

Right Side

FIGURE 49

INTERIOR MAKE−UP BOX INSTALLATION

Left side

MAKE−UP

BOX

FIGURE 50

The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to fa- cilitate installation. If the make−up box is moved to the right side, the excess wire must be pulled into the blower compartment. Secure the excess wire to the existing har- ness to protect it from damage.

Refer to figure 51 and table 10 for field wiring and figure 54 for schematic wiring diagram and troubleshooting.

1 − Select circuit protection and wire size according to the unit nameplate. The power supply wiring must meet Class I restrictions.

2 − Holes are on both sides of the furnace cabinet to facili- tate wiring.

3 − Install a separate disconnect switch (protected by ei- ther fuse or circuit breaker) near the furnace so that power can be turned off for servicing.

4 − Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire.

5 − Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wir- ing diagram shown in figure 51 and table 10. Use 18−gauge wire or larger that is suitable for Class II rat- ing for thermostat connections.

NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the G61MP integrated control.

6 − Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.

NOTE − The G61MP furnace contains electronic com- ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

7 − One line voltage ade terminal is provided

on the furnace control board. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 52 for control board configuration. This terminal is energized in the heating mode when the combustion air inducer is oper- ating.

8 − One line voltage 1/4" spade terminal is provided on the furnace control board. Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. See figure 52 for control board configuration. This terminal is energized when the indoor blower is operating.

Page 35

Page 35
Image 35
Lennox International Inc G61MP Series Units, Gas Units installation instructions Electrical