Troubleshooting: Heating Sequence of Operation (Continued)

HEATING SEQUENCE OF OPERATION

CONTINUED

THERMOSTAT CALLS FOR HEAT

STATUS LED − HEARTBEAT.

(Refer to box A on previous page)

FIRST−STAGE (LOW FIRE) PRESSURE

NO

 

GAS VALVE OFF. COMBUSTION AIR INDUCER

 

SWITCH CLOSED WITHIN 2.5 MINUTES?

 

 

OFF. INDOOR BLOWER OFF. UNIT WILL RETRY

YES

 

 

 

AFTER 5−MINUTE WAIT PERIOD.

 

 

 

STATUS ERROR CODE 2 + 3.

 

 

 

 

 

 

 

 

 

15−SECOND COMBUSTION AIR INDUCER

 

 

 

PRE−PURGE INITIATED BY CLOSED FIRST−STAGE

 

 

 

PRESSURE SWITCH (or 15 SECOND

 

 

 

INTER−PURGE PERIOD.)

 

 

 

STATUS LED −− HEARTBEAT.

 

 

 

IGNITOR WARM−UP (20 SECONDS)

STATUS LED −− HEARTBEAT.

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

COMBUSTION AIR INDUCER OFF, IGNITOR OFF.

 

 

IS IGNITOR INTACT AND CONNECTED?

 

 

 

 

 

 

 

 

 

SIGNAL HOLDS UNTIL IGNITOR IS REPLACED OR

 

 

 

 

 

 

 

 

 

 

 

 

 

RECONNECTED.

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

STATUS ERROR CODE 4 + 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AT END OF IGNITOR 20 SECOND WARM UP

 

 

 

 

 

 

 

 

 

 

 

 

 

PERIOD, 4−SECOND TRIAL FOR IGNITION.

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS VALVE OPENS, IGNITOR ENERGIZED DURING

 

 

 

 

 

 

 

 

 

 

 

 

 

4−SECOND TRIAL UNTIL FLAME SENSED.

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

IS VOLTAGE ABOVE 90 VOLTS?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4−SECOND FLAME STABILIZATION PERIOD.

 

 

 

 

 

 

COMBUSTION AIR INDUCER OFF, IGNITER OFF.

 

 

 

 

 

NO

 

 

 

SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLTS. STATUS ERROR CODE 4 + 8.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME RECTIFICATION CURRENT CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

CAN FLAME BE PROVEN WITHIN 4

 

 

 

 

 

GAS VALVE OFF. COMBUSTION AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECONDS AFTER GAS VALVE OPENS?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDUCER ON. INDOOR BLOWER OFF.

 

 

 

 

 

 

(u0.20 microamps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS LED −− HEARTBEAT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HAS CONTROL FAILED TO SENSE

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

FLAME FOR FIVE CONSECUTIVE TRIES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DURING A SINGLE HEAT DEMAND?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATCHGUARD MODE. GAS VALVE OFF,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION AIR INDUCER OFF.

 

YES

 

 

 

 

 

 

 

 

 

 

INDOOR BLOWER OFF.

 

 

 

 

 

 

 

 

 

 

 

STATUS ERROR CODE 4 + 1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IS 60−MINUTE RESET PERIOD COMPLETE?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

FLAME PRESENT?

 

 

 

 

 

 

HAS CONTROL RESET IGNITION SEQUENCE

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOUR (4) TIMES?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

WATCHGUARD MODE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS ERROR CODE 4 + 3.

 

 

 

 

 

 

CONTINUED ON NEXT PAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 