2 − Check for the correct voltage at the furnace (furnace operating).

3 − Check amp-draw on the blower motor.

Motor Nameplate__________Actual__________

NOTE − Do not secure the electrical conduit directly to the air ducts or structure.

Blower Speeds

NOTE − CFM readings are taken external to unit with a dry evaporator coil and without accessories.

1 − Turn off electrical power to furnace.

2 − Remove blower access panel.

3 − Disconnect existing speed tap at control board speed terminal.

NOTE − Termination of any unused motor leads must be insulated.

4 − Refer to blower speed selection chart on unit wiring dia- gram for desired heating or cooling speed. See blower performance data beginning on Page 48.

5 − Connect selected speed tap at control board speed terminal.

6 − Resecure blower access panel.

7 − Turn on electrical power to furnace. Electronic Ignition

The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re- set device for ignition control lockout caused by ignition fail- ure. This type of lockout is usually due to low gas line pres-

sure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat de- mand to the furnace and automatically reset the control to begin the ignition sequence.

Exhaust and Air Intake Pipe

1 − Check exhaust and air intake connections for tightness and to make sure there is no blockage.

2 − Are pressure switches closed? Obstructed exhaust pipe will cause unit to shut off at pressure switches. Check termination for blockages.

3 − Reset manual flame rollout switches on burner box cover.

Failure To Operate

If the unit fails to operate, check the following:

1 − Is the thermostat calling for heat?

2 − Are access panels securely in place?

3 − Is the main disconnect switch closed?

4 − Is there a blown fuse?

5 − Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off.

6 − Is gas turned on at the meter?

7 − Is the manual main shut-off valve open?

8 − Is the internal manual shut-off valve open?

9 − Is the unit ignition system in lock out? If the unit locks out again, inspect the unit for blockages.

Page 47