Use the following steps to correctly size vent pipe diameter. Refer to Vent Pipe Size Determination Worksheet on page 53.

1 − Determine the vent termination and its corresponding equivalent feet value according to table 5.

2 − Determine the number of 90° elbows required for both indoor and outdoor (e.g. snow riser) use. Calculate the corresponding equivalent feet of vent pipe.

3 − Determine the number of 45° elbows required for both indoor and outdoor use. Calculate the corresponding equivalent feet of vent pipe.

4 − Determine the length of straight pipe required.

5 − Add the total equivalent feet calculated in steps 1 through 4 and compare that length to the maximum values given in table 6 for the proposed vent pipe di- ameter. If the total equivalent length required exceeds the maximum equivalent length listed in the appropri- ate table, evaluate the next larger size pipe.

TABLE 6

MINIMUM VENT PIPE LENGTHS

G61MP

MIN. EQUIV.

EXAMPLE

MODEL

VENT LENGTH

 

 

 

 

045, 070,

 

5 ft. plus 2 elbows of 2", 2−1/2", 3"

071, 090,

 

 

or 4" diameter pipe

091

 

 

 

 

 

 

110, 111**

15 ft.*

5 ft. plus 2 elbows of 2−1/2" 3" or 4"

 

diameter pipe

 

 

135***

 

5 ft. plus 2 elbows of 3" or 4"

 

diameter pipe

 

 

 

 

 

*Any approved termination may be added to the minimum equivalent length listed.

**G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111 must have 90° street ell (supplied or field replacment Canadian kit) installed directly into unit flue collar.

***G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replac- ment Canadian ki) installed directly into unit flue collar.

TABLE 7

MAXIMUM VENT PIPE LENGTHS

 

 

MAXIMUM EQUIVALENT VENT

ALTITUDE

G61MP

 

LENGTH FEET

 

 

 

 

 

MODEL

2"

2−1/2"

3"

4"

 

 

 

PIPE

PIPE

PIPE

PIPE

 

 

 

 

 

 

 

045

59

65

77

234

 

070

59

65

78

214

 

071†

59

65

78

214

0 − 4500

090

26

42

72

204

(0 − 1371 m)

091†

26

42

72

204

 

110*

n/a

32

72

179

 

111*†

n/a

32

72

179

 

135**‡

n/a

n/a

61

160

 

045

59

65

77

234

 

070

59

65

78

214

 

071†

59

65

78

214

4501−7500

090

26

42

72

204

(1372−2286 m)

091†

26

42

72

204

 

110*

n/a

32

72

179

 

111*†

n/a

32

72

179

 

135**‡

n/a

n/a

46

160

 

045

59

65

77

234

 

070

59

65

78

214

 

071†

59

65

78

214

7501 − 10000

090

26

42

72

204

(2287 − 3048 m)

091†

26

42

72

204

 

110*

n/a

32

72

179

 

111*†

n/a

32

72

179

 

135**‡

n/a

n/a

46

160

n/a −− Not allowed.

*G61MP−48C−110, G61MP−60C−110 and G61MP−60C−111must have 90° street ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.

**G61MP−60D−135 must have 3" to 2" reducing ell (supplied or field replacment Canadian ki) installed directly into unit flue collar.

***90° elbows used in configuration of G61MP−60D−135 vent, must be lim- ited to 3" sweep elbows.

†On G61MP−071, −091 and −111 units, sweep elbows must be used for all 90° elbows in the venting system when 2", 2−1/2" or 3" vent pipe is used. Sweep elbows are recommended for use in vent systems of other G61MP units.