HEATING SEQUENCE OF OPERATION

Troubleshooting: Heating Sequence of Operation (Continued)

HEATING SEQUENCE OF OPERATION

CONTINUED

THERMOSTAT CALLS FOR HEAT.

STATUS LED −− HEARTBEAT.

SEE BOX A.

FLAME SIGNAL ABOVE

(u1.40 microamps)

YES

YES

SINGLE−STAGE THERMOSTAT MODE (DIP SWITCH SET AT

YES Manual background

START SECOND−STAGE RECOGNITION ON DELAY (10 OR 15 MINUTES).

STATUS LED −− HEARTBEAT

ROLLOUT SWITCHES CLOSED?

YES Manual background

FIRST−STAGE (LOW FIRE)

PRESSURE SWITCH CLOSED?

NO

LOW FLAME SIGNAL

(Does not affect control operation) STATUS ERROR CODE 1 + 2.

TWO STAGE THERMOSTAT MODE (DIP SWITCH SET AT

YES

 

 

 

 

45−SECOND INDOOR BLOWER ON DELAY BEGINS.

 

 

 

 

 

STATUS LED −− HEARTBEAT.

 

 

 

 

 

YES

 

 

 

YES

 

 

 

NO

PRIMARY & SECONDARY LIMIT SWITCHES

 

 

 

 

 

CLOSED?

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR BLOWER ON.

 

 

 

 

 

 

 

YES

STATUS ERROR CODE 5 + 1. SEQUENCE HOLDS

 

 

UNTIL ROLLOUT SWITCH IS RESET AND MAIN

 

 

 

 

 

 

 

 

 

 

POWER IS INTERRUPTED OR THERMOSTAT

 

 

 

 

 

IS CYCLED OFF/ON FOR 3 SECOND MINIMUM.

 

YES

NO

NO

FIRST−STAGE HEAT DEMAND SATISFIED?

YES

GAS VALVE OFF, COMBUSTION AIR INDUCER

OFF FOLLOWING POST PURGE.

INDOOR BLOWER OFF WITH DELAY

STATUS LED −− PULSE

SECOND−STAGE HEAT DEMAND.

SECOND−STAGE HEAT DEMAND REQUIRED?

YES

SECOND STAGE PRESSURE SWITCH CLOSED?

ABNORMAL FLASH CODE.

NOTE − IF SECOND−STAGE PRESSURE SWITCH

WAS ORIGINALLY FOUND CLOSED,

ABNORMAL CODE WILL FLASH.

NO

YES

SECOND−STAGE 30−SECOND DELAY ON BEGINS.

STATUS LED −− HEARTBEAT.

YES Manual background

SECOND−STAGE COMBUSTION AIR INDUCER ON. SECOND−STAGE GAS VALVE ON. HIGH HEAT INDOOR BLOWER SPEED ON. STATUS LED −− HEARTBEAT.

YES Manual background

SECOND−STAGE PRESSURE SWITCH CLOSED

IN LESS THAN TEN (10) SECONDS?

STATUS LED −− HEARTBEAT

YES

CONTINUED ON NEXT PAGE

GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,

 

INDOOR BLOWER ON.

 

STATUS ERROR CODE 3 + 1.

 

 

 

YES

HAS PRIMARY OR SECONDARY LIMIT

SWITCH CLOSED WITHIN 3 MINUTES?

 

(Indoor blower on low speed during 3−minute period)

 

 

 

NO

 

 

 

 

 

LIMIT SWITCH WATCHGUARD MODE.

 

GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,

 

INDOOR BLOWER OFF WITH DELAY.

YES

STATUS ERROR CODE 4 + 5

 

IS 60−MINUTE RESET PERIOD COMPLETE?

 

GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF AFTER DELAY.

STATUS ERROR CODE 2 + 3. CONTROL RESTARTS YES IGNITION SEQUENCE IF PRESSURE SWITCH

CLOSES WITHIN 2−1/2 MINUTES.

 

SECOND−STAGE PRESSURE SWITCH CLOSED

NO

 

AT BEGINNING OF HEAT DEMAND?

 

 

 

STATUS ERROR CODE 2 + 6.

 

 

 

 

 

SECOND STAGE HEAT DEMAND

 

 

STATUS LED −− HEARTBEAT.

 

 

NO

 

 

RETURNS TO FIRST−STAGE HEAT MODE WHICH

 

 

CONTINUES UNTIL SECOND−STAGE PRESSURE

 

 

SWITCH CAN BE PROVEN or HEAT DEMAND IS

 

 

SATISFIED. FIVE (5) MINUTE WAIT PERIOD

 

NO

INITIATED BEFORE RETRY. WERE 5 ATTEMPTS

 

MADE FOR SECOND−STAGE HEAT?

 

 

YES

 

 

 

CONTINUES FIRST−STAGE HEATING DEMAND.

 

 

WILL NOT REATTEMPT SECOND−STAGE

 

 

HEATING DEMAND.

 

 

STATUS ERROR CODE 2 + 5.

 