G61MP−60D−135 PERFORMANCE (Less Filter)
| Air Volume / Watts at Different Blower Speeds | Air Volume / Watts at Different Blower Speeds | |||||||||||||||
External | Bottom Return Air, Side Return Air with Optional RAB | Single Side Return Air − Air volumes in bold require field | |||||||||||||||
Return Air Base, Return Air from Both Sides or Return | fabricated transition to accommodate 20 x 25 x 1 in. air | ||||||||||||||||
Static | |||||||||||||||||
Air from Bottom and One Side. |
|
|
| filter in order to maintain proper air velocity. |
|
| |||||||||||
Pressure |
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Medium− | Medium− |
|
|
|
| Medium− | Medium− |
|
| ||||||
in. w.g. | High | Low | High | Low | |||||||||||||
High | Low | High | Low | ||||||||||||||
|
|
|
|
|
|
|
|
| |||||||||
| cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | |
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
0.00 | 2730 | 1465 | 2425 | 1125 | 2055 | 915 | 1560 | 680 | 2665 | 1440 | 2325 | 1100 | 1865 | 890 | 1410 | 690 | |
0.10 |
| 1440 |
| 1100 |
| 890 |
| 675 |
| 1405 |
| 1065 |
| 865 |
| 685 | |
2670 | 2400 | 2065 | 1590 | 2615 | 2310 | 1915 | 1465 | ||||||||||
0.20 |
| 1400 |
| 1070 |
| 865 |
| 665 |
| 1370 |
| 1055 |
| 850 |
| 675 | |
2600 | 2365 | 2045 | 1620 | 2530 | 2280 | 1925 | 1570 | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
0.30 | 2525 | 1360 | 2315 | 1045 | 2035 | 845 | 1615 | 655 | 2470 | 1330 | 2235 | 1015 | 1920 | 825 | 1590 | 670 | |
0.40 | 2445 | 1325 | 2260 | 1015 | 2020 | 820 | 1615 | 645 | 2380 | 1290 | 2175 | 985 | 1910 | 805 | 1590 | 655 | |
0.50 | 2360 | 1280 | 2195 | 985 | 1960 | 790 | 1610 | 635 | 2310 | 1265 | 2120 | 965 | 1890 | 790 | 1595 | 645 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
0.60 | 2290 | 1255 | 2130 | 965 | 1900 | 755 | 1600 | 615 | 2200 | 1230 | 2055 | 935 | 1835 | 765 | 1580 | 630 | |
0.70 | 2205 | 1220 | 2035 | 910 | 1825 | 730 | 1570 | 600 | 2120 | 1190 | 1970 | 900 | 1790 | 740 | 1545 | 605 | |
0.80 |
| 1195 |
| 880 |
| 710 |
| 580 |
| 1160 |
| 875 |
| 710 |
| 590 | |
2110 | 1945 | 1765 | 1540 | 2025 | 1890 | 1720 | 1515 | ||||||||||
0.90 |
| 1120 |
| 830 |
| 690 |
| 545 |
| 1110 |
| 835 |
| 685 |
| 570 | |
1970 | 1835 | 1680 | 1540 | 1930 | 1800 | 1655 | 1440 | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTES − All air data is measured external to unit without filter (not furnished − field provided).