Lennox International Inc G61MP Series Units Troubleshooting Cooling Sequence of Operation, Page

Models: G61MP Series Units Gas Units

1 64
Download 64 pages 11.85 Kb
Page 61
Image 61
Troubleshooting: Cooling Sequence of Operation

Troubleshooting: Cooling Sequence of Operation

COOLING SEQUENCE OF OPERATION

POWER ON

 

 

 

YES

SIGNAL POLARITY REVERSED.

 

CONTROL WILL CONTINUE TO CALL FOR COOLING

IS POLARITY REVERSED?

 

 

IN THIS CONDITION.

 

 

 

 

STATUS ERROR CODE 5 + 4.

NO

 

 

 

NO

SIGNAL IMPROPER GROUND AT LED.

IS THERE

CONTROL WILL CONTINUE TO CALL FOR COOLING

 

PROPER GROUND?

 

IN THIS CONDITION.

 

 

STATUS ERROR CODE 5 + 3.

YES

 

 

THERMOSTAT CALLS FOR FIRST−STAGE COOL.

 

COMPRESSOR AND CONDENSER FAN

 

 

ENERGIZED.

 

 

INDOOR BLOWER ENERGIZED ON FIRST STAGE

 

COOL SPEED AFTER 2 SECOND DELAY.

 

 

YES

COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.

FIRST−STAGE DEMAND FOR COOL SATISFIED?

INDOOR BLOWER DE−ENEGIZED.

 

 

NO

 

 

THERMOSTAT CALLS FOR SECOND−STAGE COOL.

 

INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.

 

SECOND−STAGE DEMAND FOR COOL SATISFIED?

 

YES

 

 

UNIT RETURNS TO FIRST STAGE COOL

 

 

Page 61

Page 61
Image 61
Lennox International Inc G61MP Series Units Troubleshooting Cooling Sequence of Operation, Cooling Sequence Of Operation