Installation on Combustible Flooring

Installation on Combustible Flooring

(Using an Additive Base)

1 − When unit is installed on a combustible floor, an addi-

tive base must be installed between the furnace and

the floor. The base must be ordered separately. See table 2 for opening size to cut in floor.

CAUTION

The furnace and additive base shall not be installed directly on carpeting, tile, or other combustible ma- terial other than wood flooring.

TABLE 2

ADDITIVE BASE FLOOR OPENING SIZE

Cabinet

Catalog

Front to Rear

Side to Side

 

 

 

 

Width

Number

in.

mm

in.

mm

 

 

 

 

 

 

 

 

B Cabinet

11M60

22

559

18 − 3/4

476

(17.5")

 

 

 

 

 

 

 

 

 

 

 

C Cabinet

11M61

22

559

22 − 3/4

578

(21")

 

 

 

 

 

 

 

 

 

 

 

D Cabinet

11M62

22

559

25 − 3/4

654

(24.5")

 

 

 

 

 

 

 

 

 

 

 

2 − After opening is cut, set additive base into opening.

3 − Check fiberglass strips on additive base to make sure they are properly glued and positioned.

4 − Lower supply air plenum into additive base until ple- num flanges seal against fiberglass strips.

NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.

5 − Set the furnace over the plenum.

6 − Ensure that the seal between the furnace and plenum is adequate.

Installation on Cooling Coil Cabinet

1 − Refer to reverse−flow coil installation instructions for correctly sized opening in floor and installation of cabi- net.

2 − When cooling cabinet is in place, set and secure the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.

3 − Seal the cabinet and check for air leaks.

Return Air Opening −− Downflow Units

Return air may be brought in only through the top opening of a furnace installed in the downflow position.The follow- ing steps should be taken when installing plenum:

1 − Bottom edge of plenum should be flanged with a hemmed edge (See figure 15 or 16).

2 − Sealing strips should be used to ensure an airtight seal between the cabinet and the plenum.

3 − In all cases, plenum should be secured to top of fur- nace using sheet metal screws.

4 − Make certain that an adequate seal is made.

PLENUM

(Field Provided) Manual background SECURE FROM OUTSIDE CABINET

SEALING STRIP

CABINET

SIDE PANEL

(Field Provided)

 

Side View

FIGURE 15

G61MP UNIT

PROPERLY

SIZED FLOOR

OPENING

SUPPLY AIR PLENUM

ADDITIVE BASE

PLENUM

(Field Provided)

SECURE FROM

 

INSIDE CABINET

Side View

SEALING STRIP (Field Provided)

CABINET

SIDE PANEL

FIGURE 16