Lennox International Inc G61MP Series Units, Gas Units installation instructions

Models: G61MP Series Units Gas Units

1 64
Download 64 pages 11.85 Kb
Page 17
Image 17
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter- nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi- als. Use transition solvent cement when bonding ABS to ei- ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni- formly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fit- ting and male end of pipe to depth of fitting socket.

Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap- pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex- haust) system. When bonding the vent system to the fur- nace, use ULC S636 approved One−Step Transition Ce- ment to bond the pipe to the flue collar, or to bond the 90° elbow or reducing 90° elbow to the flue collar. In addi- tion, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.

Table 5 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when siz- ing vent pipe. All Lennox vent terminations are PVC.

TABLE 5

OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES

 

 

 

 

Vent Pipe Length Equivalency (feet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ex-

Outdoor Ex-

 

 

 

 

 

 

 

VENT

haust Accel-

haust Accel-

1−1/2"

2" Con-

3" Con-

2" Wall Plate

3" Wall Plate

2" Wall

 

erator

erator

Concentric

UNIT

PIPE

centric Kit

centric Kit

Kit

Kit

Ring Kit

MODEL

DIA.

(Dia. X

(Dia. X

Kit

 

 

 

 

 

 

(in.)

Length)

Length)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1−1/2" X 12"

2" X 12"

71M80

69M29

60L46

22G44

44J40

15F74

 

 

or 44W92

or 44W92

or 44W93

or 30G28

or 81J20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

Not

12

Not

Not

4

4*

4

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2−1/2

5

Not

15

Not

Not

5

5*

5

 

Allowed

Allowed

Allowed

36B−045

 

 

 

 

 

 

3

7

Not

21

Not

Not

7

7*

7

 

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

4

14

Not

42

Not

Not

14

14*

14

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2

4

Not

12

Not

Not

4

4*

4

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2−1/2

5

Not

15

Not

Not

5

5*

5

36B−070

Allowed

Allowed

Allowed

 

 

 

 

 

 

36B−071

3

8

Not

24

Not

Not

8

8*

8

 

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

4

14

Not

42

Not

Not

14

14*

14

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2

Not

1

Not

3

3

Not

1

1**

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

48C−090

2−1/2

Not

2

Not

6

6

Not

2

2**

Allowed

Allowed

Allowed

 

 

 

 

 

 

60C−090

 

 

 

 

 

 

 

Not

 

Not

 

 

Not

 

 

60C−091

3

2

6

6

2

2**

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

4

Not

4

Not

12

12

Not

4

4**

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

2−1/2

Not

2

Not

6

6

Not

2

2

 

Allowed

Allowed

Allowed

48C−110

 

 

 

 

 

 

3

Not

2

Not

6

6

Not

2

2

60C−110

Allowed

Allowed

Allowed

60C−111

 

 

 

 

 

 

 

4

Not

4

Not

12

12

Not

4

4

 

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

3

Not

6

Not

Not

15

Not

6

Not

 

Allowed

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

60D−135

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Not

10

Not

Not

25

Not

10

Not

 

 

Allowed

 

Allowed

Allowed

Allowed

Allowed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator.

Termination kits 44W92 (includes 1−1/2" reducer), 44W93, 30G28 and 81J20 approved for use in Canadian installations.

Page 17

Page 17
Image 17
Lennox International Inc G61MP Series Units, Gas Units installation instructions