Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap- pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex- haust) system. When bonding the vent system to the fur- nace, use ULC S636 approved One−Step Transition Ce- ment to bond the pipe to the flue collar, or to bond the 90° elbow or reducing 90° elbow to the flue collar. In addi- tion, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits, as well as vent pipe equivalencies which must be used when siz- ing vent pipe. All Lennox vent terminations are PVC.
TABLE 5
OUTDOOR TERMINATION KITS AND CORRESPONDING EQUIVALENCIES
|
|
|
| Vent Pipe Length Equivalency (feet) |
|
| ||||
|
|
|
|
|
|
|
|
|
| |
|
| Outdoor Ex- | Outdoor Ex- |
|
|
|
|
|
| |
| VENT | haust Accel- | haust Accel- | 1−1/2" | 2" Con- | 3" Con- | 2" Wall Plate | 3" Wall Plate | 2" Wall | |
| erator | erator | Concentric | |||||||
UNIT | PIPE | |||||||||
centric Kit | centric Kit | Kit | Kit | Ring Kit | ||||||
MODEL | DIA. | (Dia. X | (Dia. X | Kit | ||||||
|
|
|
|
| ||||||
| (in.) | Length) | Length) |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
| 1−1/2" X 12" | 2" X 12" | 71M80 | 69M29 | 60L46 | 22G44 | 44J40 | 15F74 | |
|
| or 44W92 | or 44W92 | or 44W93 | or 30G28 | or 81J20 | ||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |
| 2 | 4 | Not | 12 | Not | Not | 4 | 4* | 4 | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 2−1/2 | 5 | Not | 15 | Not | Not | 5 | 5* | 5 | |
| Allowed | Allowed | Allowed | |||||||
36B−045 |
|
|
|
|
|
| ||||
3 | 7 | Not | 21 | Not | Not | 7 | 7* | 7 | ||
| ||||||||||
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 4 | 14 | Not | 42 | Not | Not | 14 | 14* | 14 | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 2 | 4 | Not | 12 | Not | Not | 4 | 4* | 4 | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 2−1/2 | 5 | Not | 15 | Not | Not | 5 | 5* | 5 | |
36B−070 | Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
| |||||
36B−071 | 3 | 8 | Not | 24 | Not | Not | 8 | 8* | 8 | |
| ||||||||||
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 4 | 14 | Not | 42 | Not | Not | 14 | 14* | 14 | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 2 | Not | 1 | Not | 3 | 3 | Not | 1 | 1** | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
48C−090 | 2−1/2 | Not | 2 | Not | 6 | 6 | Not | 2 | 2** | |
Allowed | Allowed | Allowed | ||||||||
|
|
|
|
|
| |||||
60C−090 |
|
|
|
|
|
| ||||
| Not |
| Not |
|
| Not |
|
| ||
60C−091 | 3 | 2 | 6 | 6 | 2 | 2** | ||||
Allowed | Allowed | Allowed | ||||||||
|
|
|
|
|
|
| ||||
| 4 | Not | 4 | Not | 12 | 12 | Not | 4 | 4** | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 2−1/2 | Not | 2 | Not | 6 | 6 | Not | 2 | 2 | |
| Allowed | Allowed | Allowed | |||||||
48C−110 |
|
|
|
|
|
| ||||
3 | Not | 2 | Not | 6 | 6 | Not | 2 | 2 | ||
60C−110 | ||||||||||
Allowed | Allowed | Allowed | ||||||||
60C−111 |
|
|
|
|
|
| ||||
| 4 | Not | 4 | Not | 12 | 12 | Not | 4 | 4 | |
| Allowed | Allowed | Allowed | |||||||
|
|
|
|
|
|
| ||||
| 3 | Not | 6 | Not | Not | 15 | Not | 6 | Not | |
| Allowed | |||||||||
| Allowed | Allowed | Allowed | Allowed | ||||||
|
|
|
|
| ||||||
60D−135 |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| ||
4 | Not | 10 | Not | Not | 25 | Not | 10 | Not | ||
| ||||||||||
| Allowed | |||||||||
| Allowed | Allowed | Allowed | Allowed | ||||||
|
|
|
|
| ||||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
*Requires field−provided and installed 1−1/2" exhaust accelerator. **Requires field−provided and installed 2" exhaust accelerator.
Termination kits 44W92 (includes 1−1/2" reducer), 44W93, 30G28 and 81J20 approved for use in Canadian installations.
Page 17