TABLE 8

Details of Intake and Exhaust Piping Terminations for Direct Vent Installations

NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.

Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In at- tic or closet installations, vertical termination through the roof is preferred. Figures 31 through 39 show typical ter-

TABLE 8

EXHAUST PIPE TERMINATION SIZE REDUCTION

G61MP

Exhaust Pipe Size

Termination Pipe Size

MODEL

 

 

 

 

 

045, 070, −071

2", 2−1/2", 3" or 4"

1−1/2"

090, −091

2", 2−1/2", 3" or 4"

2"

110, −111

2−1/2", 3" or 4"

*2"

135

3" or 4"

*2"

*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.

minations.

1 − Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the

Inches(mm)

3(76) MAX.

SIZE TERMINATION PIPE PER TABLE 8.

UNCONDITIONED

side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.

2 − Intake and exhaust pipes should be placed as close together as possible at termination end (refer to il- lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina- tions.

3 − If necessary, install a field−provided reducer to adapt larger vent pipe size to termination pipe size.

4 − On roof terminations, the intake piping should termi- nate straight down using two 90° elbows (See figure

8" (203) MIN

12" (305) ABOVE AVERAGE SNOW ACCUMULATION

3" (76) OR 2" (51) PVC

PROVIDE SUPPORT

FOR INTAKE AND EXHAUST LINES

ATTIC SPACE

1/2" (13) FOAM INSULATION IN UNCONDITIONED SPACE

31).

5 − Exhaust piping must terminate straight out or up as shown. In rooftop applications, a reducer may be re- quired on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.

NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.

6 − On field supplied terminations for side wall exits, ex- haust piping should extend a minimum of 12 inches (305mm) beyond the outside wall. Intake piping should be as short as possible. See figure 32.

7 − On field supplied terminations, a minimum separation distance between the end of the exhaust pipe and the end of the intake pipe is 8 inches (203mm).

8 − If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstruc- tions, piping must be supported every 3 ft. (.9m) as shown in figure 22. Refer to figure 35 for proper piping method. In addition, WTK wall termination kit must be extended for use in this application. See figure 38. When exhaust and intake piping must be run up an outside wall, the exhaust piping is reduced to 1−1/2" (38mm) after the final elbow. The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.

9 − Based on the recommendation of the manufacturer, a multiple furnace installation may use a group of up to four termination kits WTK assembled together hori- zontally, as shown in figure 37.

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 31

 

12" (305) MAX.

 

 

1/2" (13) ARMAFLEX

(unless supported)

 

 

 

 

INSULATION IN

 

 

1/2" (13)

UNCONDITIONED SPACE

 

 

 

 

ARMAFLEX

 

 

INSULATION

FIELD−

 

 

SIZE

PROVIDED

 

 

 

 

TERMINA-

REDUCER MAY

6" (152)

TION PIPE

BE REQUIRED

MAXI-

PER TABLE

TO ADAPT

MUM

 

 

8.

LARGER VENT

 

 

 

 

 

PIPE SIZE TO

 

 

 

TERMINATION

 

 

 

OUTSIDE

8" (203)

 

Inches (mm)

WALL

 

 

 

MINIMUM

 

 

2" (51)

 

 

 

 

 

PVC

 

 

 

COUPLING

 

 

 

TOP VIEW WALL RING KIT WITH STRAIGHT INTAKE

 

(15F74)

 

 

1/2 (13) ARMAFLEX

12 (305) MAX.

 

 

INSULATION IN

 

 

 

 

 

UNCONDITIONED

 

 

1/2" (13)

SPACE

 

 

ARMAFLEX

 

 

 

INSULATION

FIELD−

 

 

 

PROVIDED

 

 

 

REDUCER MAY

 

 

 

BE REQUIRED

 

 

 

TO ADAPT

 

 

SIZE

LARGER VENT

6 (152)

TERMINATION PIPE

PIPE SIZE TO

MAXIMUM

 

PER TABLE 8.

TERMINATION

 

 

 

 

4 (102)

 

 

Inches (mm) OUTSIDE

MINIMUM

 

 

 

 

 

WALL

 

 

 

TOP VIEW WALL RING KIT WITH 90° ELBOW ON INTAKE

 

(15F74)

 

 

FIGURE 32

Page 28

Page 28
Image 28
Lennox International Inc Gas Units, G61MP Series Units Table Exhaust Pipe Termination Size Reduction