Generac 004188-1 Transfer Switch Start Signal Connections, Battery Installation, Vented Batteries

Page 12

Section 2 — Installation

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

GENERATOR AC NEUTRAL CONNECTIONS

Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance. If the neutral wire is grounded and one of the phase loads becomes grounded, the excessive current opens the load circuit breaker or collapses the genera- tor field. The actual result depends on the electrical characteristics of the particular installed generator.

TRANSFER SWITCH START SIGNAL CONNECTIONS

If your generator is to be installed with an automatic transfer switch, such as a Generac GTS-type switch, it will be necessary to connect the two-wire start control system.

Connect the two-wire start signal from the automatic transfer switch to the automatic start connection, which is located in the right hand corner inside the control panel. Match wires 178 and 183 in the transfer switch to 178 and 183 on the terminal strip in the control panel. The conductors for the two-wire start circuit must be in their own conduit.

BATTERY INSTALLATION

Standby generators installed with automatic transfer switches will crank and start automatical- ly when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per- sonnel, do not connect battery cables until you are certain that normal source voltage at the transfer switch is correct and you are ready to place the system into operation.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If you spill the fluid, flush the affected area immediately with clear water.

Do not dispose of the battery in a fire. The bat- tery is capable of exploding.

Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically con- ductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten- tion, and

Spilled electrolyte is to be washed down with an acid- neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The following proce- dure are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touching batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

For recommended batteries, see “Specifications.” All batteries must be at 100 percent state-of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not neces- sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec- ified in Section 4, “Maintenance.” A negative ground sys- tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

Note:

Damage will result if the battery connections are made in reverse.

10 Generac® Power Systems, Inc.

Image 12
Contents Power SYSTEMS, INC Authorized Service Dealer Location Operation and MaintenanceHOW to Obtain Service IntroductionIntroduction IFC Safety Rules General Hazards Electrical Hazards Transfer Switch GeneratorAutomatic System Operation Generator AC Connection SystemsHigh Coolant Temperature Switch LOW OIL Pressure SwitchLOW Coolant Level Switch Engine Protective DevicesSpecifications UnpackingLifting the Generator Torque Specifications Before InstallationFuel Consumption Engine OIL RecommendationsStandby Generator Installation Generator LocationOther Published Standards Nfpa StandardsBasic Standby Electric System Total Circuit Isolation MethodGrounding the Generator Emergency Circuit Isolation MethodTransfer Switch Start Signal Connections Battery InstallationVented Batteries Using a Standard GTS Transfer Switch Preparation Before START-UPPrior to Initial START-UP Control Console Components Meter Reading Selector Switch SET Exercise Time SwitchManual Transfer and Start UP Retransfer and Shutdown Automatic OperationEngine Heater Cooling SystemOverload Protection for Engine DC Electrical System Checking Fluid LevelsMaintenance OWNER/OPERATOR can Perform Changing the Engine AIR Cleaner Coolant ChangeMiscellaneous Maintenance Cleaning the GeneratorBattery Battery ReplacementTroubleshooting Points Service Maintenance Interval Information Level Maintenance Level Electrical Data Electrical Data Electrical Data AC Outlet Outlet AC Circuit FED Ground Wire Assembly BRACE, SideBumper DOOR, EnclosureGenerac Power Systems, Inc Washer Nylon Hinge Slip Male LHHinge Slip Female LH Hinge Slip Male RHGenerac Power Systems, Inc CMA BOX Assembly Rocker Switch DpstSWITCH, Selector AMP/VOLT SWITCH, Toggle DpdtGenerac Power Systems, Inc Switch 6A AMP/V Selector Harness Wiring 1.5LDECAL, TRANS. Switch Conn Switch Dpst 5 125V SPD RckrGenerac Power Systems, Inc Tank Coolant Recovery Bracket Coolant Recovery TankSupport Radiator Radiator 1.5LGenerac Power Systems, Inc Venturi 1.5L Guard FANHose RES 5/8 RIA 250F NUT HEX M6 -1.0 G8 YEL CHRBASE, Mounting ISOLATOR-VIBRATIONISOLATOR, Vibration Flat WASHER-M8Dampener Vibration Washer Flat M8Earth Strap Washer Shakeproof EXT 5/16 STLMuffler W/RAIN Shld Mufflr Strap 6IN DIAElbow 90 DEG 2 NPT Nipple TOE 2 NPT X 4.5 BLK IronManifold Exhaust 1.5L Nipple TOE 1.5 NPT X 6.5 BL IronPipe Exhaust Flex Pipe ExhaustSilkscreen P Panel Cover BQ Circuit BreakerBracket Mounting Circuit Breaker Circuit Breaker 70 X 2 240V 39782 BrktHarness CMA Wire Assy Home Stdby LogicDECAL, CMA Label PP Logic ASM 50/60HZASSY,WIRE#16 RED Bolt Battery Hold DownBAR Battery Holddown Battery Post Cover RED+Housing Governor Connector Connector Interface AssemblyCover Connector Housing Assembly Carburator LinkageGenerac Power Systems, Inc Housing Blower Assy Rotor 10KWAssy Rotor 15KW Assy Rotor 20KWGenerac Power Systems, Inc Cover AIR Cleaner Weldment Mounting BaseFlange Fuel Inlet Solenoid GAS FuelGenerac Power Systems, Inc Switch OIL Pressure ARM Adjust AlternatorGround Wire Starter ENGINE-1.5LInstallation Air Outlet Air Intake Installation Air Intake Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following

004371-2, 004188-1, 004474-1, 004475-1, 004370-2 specifications

Generac Power Systems is renowned for its commitment to providing reliable power solutions, and their various models, including the Generac 004189-1, 004370-2, 004475-1, 004474-1, and 004188-1, showcase the company’s innovative engineering and technology. Each of these models is designed to meet diverse energy needs, ensuring homeowners and businesses can maintain power during outages or in remote locations.

The Generac 004189-1 is an essential model in the lineup known for its robust construction and user-friendly interface. It features a powerful engine, ensuring reliable power output and efficient fuel consumption. Additionally, its lightweight design makes it portable, allowing easy relocation to different sites. The model integrates advanced technology for automatic voltage regulation, safeguarding sensitive electronics while operating.

Moving on to the Generac 004370-2, this model emphasizes advanced start-up technology. It is equipped with a reliable electric start feature, minimizing the effort required to power up the generator. Its noise-dampening design significantly reduces sound levels, making it ideal for residential use without causing disturbances to neighbors. The unit also includes a durable metal enclosure that helps protect the generator from the elements and increases its lifespan.

The Generac 004475-1 model stands out for its enhanced fuel efficiency and low emissions. This eco-friendly design adheres to strict emissions regulations, making it a suitable choice for environmentally conscious users. Its intuitive control panel provides easy monitoring of power output, fuel levels, and maintenance needs, ensuring users can efficiently manage their energy requirements.

Similarly, the Generac 004474-1 exemplifies convenience and performance with its dual fuel capability, allowing it to operate on both gasoline and propane. This flexibility ensures users can easily switch fuels based on availability and cost-effectiveness. The model also boasts an extended runtime, capable of powering essential appliances and systems for prolonged periods during outages.

Finally, the Generac 004188-1 emphasizes ease of use, featuring a comprehensive user manual and a straightforward assembly process. The model provides ample power capacity, making it excellent for both emergency back-up and recreational activities. Its compact design allows storage in confined spaces, while its efficient cooling system prevents overheating during extended use.

Overall, these Generac models reflect the company's dedication to innovation, quality, and user satisfaction. With features aimed at enhancing convenience, performance, and environmental responsibility, they cater to the varying power demands of modern users.