Generac 02010-2, 04164-2 owner manual Electrical Connections, Mufflers and Spark Arrestors

Page 33

Section 2 – Installation

PRIMEPACT 50 Recreational Vehicle Generator

2.6.1 MUFFLERS AND SPARK ARRESTORS

This muffler meets code and standard requirements of the U.S. Forest Service. Use only mufflers and parts approved by Generac. Any person(s) installing an unapproved muffler, or an unapproved exhaust system part, or modifying an exhaust system in any way that might cause a hazard, is liable for any dam- age, injury or warranty expense that might be caused by such unapproved installation or modification.

Failure to provide and maintain a spark arrestor may be in violation of the law. If this generator is used on any forest covered, brush covered or grass covered unimproved land, you must provide a spark arrestor. The vehicle owner or operator must maintain this device in good condition. In the state of California, the preceding is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.

2.6.2 TYPE OF EXHAUST SYSTEM

Two types of exhaust systems for PRIMEPACT series generators are available from Generac. They include the following:

“Out-the-bottom” exhaust system dimensions are 15/16” O.D., model 9742.

“Out-the-side” exhaust system dimensions are 1- 1/4” O.D., 18 gauge, model 4172.

NOTE:

No matter what type of exhaust kit best fits your recreational vehicle, the mounting base has open- ings for either “bottom-out” or “side-out” exhaust systems. Use the cover plate provided with the generator to cover the opening you do NOT use.

2.6.3 EXHAUST SYSTEM SAFETY

Maintain a clearance of at least 3 inches (76 mm) between exhaust system parts and any com- bustible material (such as wood, felt, cotton, organic fibers or other like material). If you cannot maintain the 3-inch (76 mm) clearance, locate, insulate or shield the exhaust part(s) so that the temperature of any combustible material is not raised more than 117° F (65° C) above the ambient air temperature.

Extend the exhaust system at least 1 inch (25 mm) past the outer edge of the vehicle. Do not terminate the exhaust system under the vehicle.

Terminate the exhaust tailpipe such that exhaust gases will not be drawn back into the generator compartment and recirculated.

If there is any possibility of the tailpipe or muffler being damaged, protect these damage-prone areas by means of a protective device (such as a skid bar).

Install the generator exhaust system according to safe automotive practices.

Use enough exhaust system hangers to prevent any part of the system from being dislocated.

Use exhaust system parts recommended by Generac. Using unapproved exhaust mufflers and exhaust system parts is the responsibility of the person(s) installing such unauthorized parts.

Do not terminate the exhaust system under any opening, window or vent that can be opened or is not permanently sealed from the vehicle interior.

Exhaust piping must be large enough to prevent excessive back pressure on the generator engine.

Never tee the generator engine exhaust pipe into the vehicle engine exhaust piping. This causes excessive back pressure on the generator engine. Also, water from one engine can damage the other engine.

Plan exhaust system installation carefully. Comply with all applicable codes, standards and regula- tions.

2.7ELECTRICAL CONNECTIONS

Be sure to read Section 1.6 on Page 20.

The following general rules apply to electrical con- nections in a recreational vehicle:

Qualified electricians who are familiar with applic- able codes, standards and regulations should install electrical wiring.

The wiring should comply with codes, standards and regulations. The National Electrical Code (NFPA 70), and state and local codes apply.

Switches and circuit breakers should be of a type approved for use in recreational vehicles and must be mounted and installed to prevent damage from road shock.

Wiring must be of adequate size, have approved insulative qualities and be properly supported.

Conduit and wire openings into the generator com- partment (if used) must be vapor-sealed to prevent entry of flammable, explosive or poisonous gases into the vehicle.

2.7.1 ELECTRICAL JUNCTION BOX

Install an approved, square electrical junction box with a blank cover on the interior or exterior wall of the area you plan to install the generator (NOT on the generator). Route the generator's AC output leads into this junction box through approved flexible con- duit. This is the point of first termination for genera- tor AC output leads.

Generac® Power Systems, Inc. 31

Image 33
Contents Power SYSTEMS, INC Introduction Authorized Service Dealer LocationTable of Contents Part II Installation InstructionsGeneral Hazards Electrical Hazards Generator Identification Model 02010-2 PrimepactModel 04164-2 Primepact 50LP Specifications SafetyGenerator Applicability Generator AC Connection SystemFuel Consumption Optional Propane Fuel SystemEngine OIL Requirements GeneratorGenerator Control Panel START/STOP SwitchOptional Remote START/STOP Panel Fuel PrimerBefore Starting the Engine Automatic Choke Gasoline onlyStopping the Generator Starting the GeneratorApplying Loads to Generator SUMMER/WINTER Heat Riser SystemHigh Temperature Switch LOW OIL Pressure SwitchProtection Systems Do not Overload the GeneratorAdditional Information Changing the Engine OIL AND/OR OIL Filter Checking the Engine OIL LevelClean AIR Intake Maintaining the Engine AIR CleanerCleaning the Foam Precleaner Checking the Engine Spark PlugBattery Maintenance Cleaning the GeneratorSpark Arrestor Muffler WeeklyExercising the Generator Drive BeltOUT of Service Procedure Removal from ServiceReturn to Service Part General Hazards Fire Hazards Standards Booklets Purpose and Scope ManualEquipment Description Generator Engine Operating SpeedMajor Features and Dimensions Generator Location Location and SupportGenerator Support Suspended MountingGenerator Restraint Generator CompartmentsCompartment Construction Compartment SizeSound Insulating Materials AcousticsTypical Noise Abatement 2.2.5 Compartment Floor Cutouts Cooling and Ventilating AIR Generator AirflowCooling AIR Inlet Openings Testing the Installation Gasoline Fuel SystemCompensating for Restrictions Fuel Tank Flexible Fuel Line LP GAS Fuel SystemGenerator Fuel Supply Line Rigid Fuel LinesSome Important Considerations Primary RegulatorVapor Withdrawal Gaseous CarburetionFuel Supply Lines Exhaust SystemExcess Flow Valve Leakage TestsElectrical Connections Exhaust System SafetyMufflers and Spark Arrestors Type of Exhaust SystemIsolating Different Power Sources WiringGenerator AC Connections ConduitGround Fault Circuit Interrupters Power Supply CordRecommended Battery Optional AccessoriesBattery Cables Battery Cable ConnectionsTesting Under Load Post Installation TestsBefore Initial START-UP Remote Panel ModelsInstallation Checklist Problem Cause Correction Troubleshooting GuideElectrical Data Electrical Data Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists REGULATOR, GAS Fuel Exploded Views and Parts Lists Lower Bearing Carrier Exploded Views and Parts Lists ¼/ M6-LOCK Washer To Starter SCROLL, Flywheel Exploded Views and Parts Lists Piston Ring SET Exploded Views and Parts Lists MANIFOLD, Intake Exploded Views and Parts Lists CARBURETOR, GN 410 L/P Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule CONSUMER/PERSONAL Applications