Generac 02010-0, 04164-0 owner manual Gasoline Fuel System, Testing the Installation

Page 29

Section 2 – Installation

PRIMEPACT 50 Recreational Vehicle Generator

Figure 2.12 – Air Inlet Using Ductwork

2.3.4 TESTING THE INSTALLATION

 

Generac recommends testing the installation to be

 

sure adequate cooling airflow is available to the unit

 

before placing the unit into service. If the unit shows

 

signs of overheating, you will need to enlarge the air

 

openings. Never place a unit into service until

 

absolutely certain that cooling and ventilation is ade-

 

quate.

 

NOTE:

 

You must test the installation, especially if you

 

bring in air from below the generator set.

Figure 2.13 – Air Inlet in Vehicle Skirt

VEHICLE FLOOR

VEHICLE

 

 

SKIRT

 

AIR

 

INLET

MINIMUM

 

CLEARANCE

 

1-1/2"

 

2.3.3 COMPENSATING FOR RESTRICTIONS

Such materials as screening, louvers or expanded metal can restrict the free flow of air. Compensate for this restriction by making the actual air opening pro- portionately larger.

Some materials may offer only a 60 percent “free air inlet area.” Other more efficient materials may pro- vide up to a 90 percent free air inlet area. The per- centage of free air inlet opening is usually available from the material supplier or manufacturer.

To determine the actual air inlet opening size required, divide 100 square inches by the per- centage of free air inlet area for the material you will use.

For example: If you plan to use screening with an 80 percent free air inlet area, divide 100 by 0.8, which results in 125 square inches. Minimum actual size of air inlet opening in this case is 125 square inches.

2.4GASOLINE FUEL SYSTEM

The installation of a gasoline fuel system (Figure 2.14) for a recreational vehicle generator set must comply with applicable codes, standards and regula- tions. The entire fuel system must be completely free of leaks. There must be no possibility of gasoline vapors entering the vehicle interior.

Figure 2.14 – Generator Fuel System

DANGER

Gasoline is highly flammable, and its vapors are explosive. Comply with all codes, standards and regulations pertaining to gasoline fuel systems used in recreational vehicle generators.

Properly install and maintain the fuel system and keep it entirely free of leaks. Gasoline vapors must not enter the vehicle interior.

Factory installed generator fuel system components include (a) fuel filter, (b) 12-volt DC electric pump, (c) engine carburetor, and (d) interconnecting lines and fittings. Connect a fuel supply line to the fuel filter inlet. Use a flexible length of approved fuel hose between the fuel filter inlet connection and rigid fuel lines.

Generac® Power Systems, Inc. 27

Image 29
Contents Power SYSTEMS, INC Introduction Authorized Service Dealer LocationTable of Contents Part II Installation InstructionsGeneral Hazards Electrical Hazards Model Generator IdentificationPrimepact Primepact 50LPSpecifications SafetyGenerator Applicability Generator AC Connection SystemFuel Consumption Optional Propane Fuel SystemEngine OIL Requirements EngineGenerator Control Panel START/STOP SwitchOptional Remote START/STOP Panel Fuel PrimerStarting the Generator Automatic Choke Gasoline onlyBefore Starting the Engine Letting the Engine Stabilize Stopping the GeneratorSUMMER/WINTER Heat Riser System High Temperature Switch LOW OIL Pressure SwitchProtection Systems Do not Overload the GeneratorAdditional Information Changing the Engine OIL AND/OR OIL Filter Checking the Engine OIL LevelClean AIR Intake Maintaining the Engine AIR CleanerCleaning the Foam Precleaner Checking the Engine Spark PlugBattery Maintenance Cleaning the GeneratorSpark Arrestor Muffler WeeklyExercising the Generator Drive BeltReturn to Service OUT of Service ProcedureRemoval from Service Part General Hazards Electrical Hazards Standards Booklets Purpose and Scope ManualEquipment Description Generator Engine Operating SpeedMajor Features and Dimensions Generator Location Location and SupportGenerator Support Suspended MountingGenerator Restraint Generator CompartmentsCompartment Construction Compartment SizeSound Insulating Materials AcousticsTypical Noise Abatement 2.2.5 Compartment Floor Cutouts Cooling AIR Inlet Openings Cooling and Ventilating AIRGenerator Airflow Compensating for Restrictions Testing the InstallationGasoline Fuel System Fuel Tank LP GAS Fuel SystemGenerator Fuel Supply Line Rigid Fuel LinesSome Important Considerations Primary RegulatorVapor Withdrawal Gaseous CarburetionFuel Supply Lines Exhaust SystemExcess Flow Valve Leakage TestsElectrical Connections Exhaust System SafetyMufflers and Spark Arrestors Type of Exhaust SystemIsolating Different Power Sources WiringGenerator AC Connections ConduitGround Fault Circuit Interrupters Power Supply CordRecommended Battery Optional AccessoriesBattery Cables Battery Cable ConnectionsRemote Panel Cables Remote Panel ModelsTesting Under Load Post Installation TestsBefore Initial START-UP Initial StartInstallation Checklist Appendix 1 Notes Problem Cause Correction Troubleshooting GuideAppendix 3 Electrical Data Appendix 3 Electrical Data Appendix 4 Exploded Views and Parts Lists QTY. Description Appendix 4 Exploded Views and Parts Lists REGULATOR, GAS Fuel Appendix 4 Exploded Views and Parts Lists Lower Bearing Carrier Appendix 4 Exploded Views and Parts Lists Item Part no QTY. Description Appendix 4 Exploded Views and Parts Lists Piston Ring SET Appendix 4 Exploded Views and Parts Lists MANIFOLD, Intake Appendix 4 Exploded Views and Parts Lists BOLT, SHOULDER, M6 X 15 LG PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power SYSTEMS, INC