Section 3 – Post-installation Start-up Adjustments

PRIMEPACT 50 Recreational Vehicle Generator

3.1POST INSTALLATION TESTS

The air-cooled generator set was factory tested and adjusted. You should not be required to adjust the unit any further except under special circumstances.

Do not make any unnecessary adjustments.

!Factory settings are correct for most applica- tions. When making adjustments, however, be careful to avoid overspeeding the engine.

3.2BEFORE INITIAL START-UP

Before starting, complete the following:

1.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick “FULL” mark (cross- hatched area) with the recommended oil. Do not fill above the FULL mark.

2.Check the fuel supply. Gas fuel lines must have been properly purged and leak tested in accor- dance with applicable fuel codes. All fuel shutoff valves in the fuel supply lines must be open.

DANGER

If a liquid propane (LP) gas fuel system has

!been installed, it must be properly tested for leaks before operating the system in compli- ance with ANSI A119.2/NFPA 501C. No leakage is permitted. You must be sure no gasoline fuel vapors enter the vehicle interior.

3.3INITIAL START

When you are absolutely certain that the unit has been properly installed and prepared for use, start the engine as follows:

1.Turn off all electrical loads. Do this by setting the generator’s main circuit breakers to their “OFF” (or open) position.

2.Refer to Part I, Section 2.5, “Starting the Generator” (Page 8), for cranking and starting instructions. The engine may require more cranking for initial starting since the fuel lines have to be primed (use of the primer switch will shorten this time).

3.Let the engine warm up for about five minutes to allow internal temperatures to stabilize.

4.Carefully inspect the engine/generator for fuel, oil and exhaust system leaks. Before proceeding to the next step, correct any leakage immediately.

5.When all tests and adjustments at no-load are completed, apply electrical loads and check for proper operation under load. See Section 3.4. Run the unit at least 30 minutes with loads applied.

6.Turn off all electrical loads by setting the genera- tor’s main circuit breakers to their “OFF” (or open) position.

7.Let the unit run at no-load for a few minutes to stabilize internal engine/-generator temperatures. Then, shut down the engine.

NOTE:

The generator set was thoroughly tested and adjusted at the factory before shipping. No addi- tional adjustment should be necessary. Only qual- ified service technicians who have been trained should perform adjustments outlined in this man- ual.

3.4TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 per- cent of the unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling air- flow is available. You must not allow the unit to over- heat during prolonged operation.

NOTE:

The generator engine is equipped with a high tem- perature switch. The switch has normally closed (N.C.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.

GENERAC RECOMMENDS THAT YOU TEST THE GENERATOR FOR ADEQUATE COOLING.

36 Generac® Power Systems, Inc.

Image 38
Contents Power SYSTEMS, INC Authorized Service Dealer Location IntroductionPart II Installation Instructions Table of ContentsGeneral Hazards Electrical Hazards Primepact Generator IdentificationModel Primepact 50LPGenerator Applicability SafetySpecifications Generator AC Connection SystemEngine OIL Requirements Optional Propane Fuel SystemFuel Consumption EngineOptional Remote START/STOP Panel START/STOP SwitchGenerator Control Panel Fuel PrimerStarting the Generator Automatic Choke Gasoline onlyBefore Starting the Engine Letting the Engine Stabilize Stopping the GeneratorSUMMER/WINTER Heat Riser System Protection Systems LOW OIL Pressure SwitchHigh Temperature Switch Do not Overload the GeneratorAdditional Information Checking the Engine OIL Level Changing the Engine OIL AND/OR OIL FilterCleaning the Foam Precleaner Maintaining the Engine AIR CleanerClean AIR Intake Checking the Engine Spark PlugSpark Arrestor Muffler Cleaning the GeneratorBattery Maintenance WeeklyDrive Belt Exercising the GeneratorReturn to Service OUT of Service ProcedureRemoval from Service Part General Hazards Electrical Hazards Equipment Description Purpose and Scope ManualStandards Booklets Generator Engine Operating SpeedMajor Features and Dimensions Generator Support Location and SupportGenerator Location Suspended MountingCompartment Construction Generator CompartmentsGenerator Restraint Compartment SizeAcoustics Sound Insulating MaterialsTypical Noise Abatement 2.2.5 Compartment Floor Cutouts Cooling AIR Inlet Openings Cooling and Ventilating AIRGenerator Airflow Compensating for Restrictions Testing the InstallationGasoline Fuel System Generator Fuel Supply Line LP GAS Fuel SystemFuel Tank Rigid Fuel LinesVapor Withdrawal Primary RegulatorSome Important Considerations Gaseous CarburetionExcess Flow Valve Exhaust SystemFuel Supply Lines Leakage TestsMufflers and Spark Arrestors Exhaust System SafetyElectrical Connections Type of Exhaust SystemGenerator AC Connections WiringIsolating Different Power Sources ConduitPower Supply Cord Ground Fault Circuit InterruptersBattery Cables Optional AccessoriesRecommended Battery Battery Cable ConnectionsRemote Panel Models Remote Panel CablesBefore Initial START-UP Post Installation TestsTesting Under Load Initial StartInstallation Checklist Appendix 1 Notes Troubleshooting Guide Problem Cause CorrectionAppendix 3 Electrical Data Appendix 3 Electrical Data Appendix 4 Exploded Views and Parts Lists QTY. Description Appendix 4 Exploded Views and Parts Lists REGULATOR, GAS Fuel Appendix 4 Exploded Views and Parts Lists Lower Bearing Carrier Appendix 4 Exploded Views and Parts Lists Item Part no QTY. Description Appendix 4 Exploded Views and Parts Lists Piston Ring SET Appendix 4 Exploded Views and Parts Lists MANIFOLD, Intake Appendix 4 Exploded Views and Parts Lists BOLT, SHOULDER, M6 X 15 LG PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power SYSTEMS, INC