Generac 40kW LP, 37kW NG owner manual Checking Fluid Levels

Page 18

Section 4 — Maintenance

QUIETSOURCE™ 40kW Liquid-cooled Generators

4.4CHECKING FLUID LEVELS

‹4.4.1 CHECK ENGINE OIL

Check engine crankcase oil level (Figure 4.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint-free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See Section 1.14 for recom- mended oils.

Figure 4.1 - Oil Dipstick and Oil Fill Cap

Oil Dipstick

Oil Fill

 

Oil Filter

‹4.4.2 BATTERY FLUID

Check battery electrolyte fluid at least once weekly. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

4.5MAINTENANCE OWNER/ OPERATOR CAN PERFORM

‹4.5.1 CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels” in Section 4.4.

‹4.5.2 CHECK BATTERY

Check battery fluid level each week as outlined under “Check Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹4.5.3 EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See Section 3.6, “Weekly Exercise Cycle”.

‹4.5.4 INSPECT COOLING SYSTEM

Inspect engine cooling system at least once each month.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹4.5.5 CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels” in Section 4.4.

‹4.5.6 PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹4.4.3 ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications, Section 1.10.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an authorized Generac Service Dealer. Inspect cooling system and coolant recovery system for leaks.

‹4.5.7 INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹4.5.8 CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹ 4.5.9 INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

16 Generac® Power Systems, Inc.

Image 18
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service Authorized Service Dealer Location‹ Operation and Maintenance IntroductionTable of Contents General Hazards Electrical Hazards Automatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Generator Fuel SystemUnpacking Lifting the Generator‹ 1.10.1 Generator Specifications SpecificationsReconfiguring the Fuel System ‹ 1.10.2 Engine SpecificationsEngine OIL Recommendations Torque SpecificationsBefore Installation Coolant RecommendationsBasic Standby Electric System Generator LocationGenerator Mounting Support ‹ 2.1.1 Nfpa StandardsTotal Circuit Isolation Method Transfer Switch Signal ConnectionsEmergency Circuit Isolation Method Generator AC Neutral ConnectionsBattery Installation ‹ 2.9.2 GTS-TYPE Engineered Transfer Switch‹ 2.10.1 Vented Batteries Using AN Engineered GTS Transfer Switch Preparation Before START-UP‹ 3.2.5 SET Exercise Time Switch ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.2 Fault Indicator LED Control Console ComponentsAutomatic Operation Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Weekly Exercise CycleCooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.5.12 Spark Plugs ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.5.10 Changing Engine OIL ‹ 4.5.13 Coolant Change‹ 4.6.2 Battery Miscellaneous Maintenance‹ 4.6.1 Cleaning the Generator ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionInstallation Diagram Electrical Data Electrical Data Electrical Data Electrical Data Carrier Rear Bearing Boot Battery Cable Assy WireHold Down Battery Battery Post Covwer BlackSee Latch Detail Duct Intake MID AL Assy GRD Wire 99HSBASSEMBLY,BASE-DOOR Ground Wire Duct Discharge RH ALGenerac Power Systems, Inc Cover Front Panel HSB Assy 2A 12V UL BatteryControl BOX HSB Cover TOP Panel HSB ShockGenerac Power Systems, Inc Flexplate 3.9L HSB Cover Flywheel AccessAssembly Resistor SunkPump VENTURI,3.9L Cryslr HSB 22FAN Tank Coolant RecoveryRadiator Copper Brass Radiator Support L/H SideTo Engine Plate AIR Cleaner TOP Base AIR Cleaner PlateHold Down AIR Cleaner Flange Fuel InletLeads STR-390--40AD HSB 433MM LONG3.9L Chrysler Rotor 390 30KW 1P Direct HSBRotor 390 40KW 1P Direct HSB Rear Bearing Carrier 390/DRCTNUT TOP Lock FL M12-1.75 OUTWYE, Pipe 3.9L Chrysler Pipe L/H Exhaust ManifoldQuietsource 40kW Liquid-cooled Generators Quietsource 40kW Liquid-cooled Generators Quietsource 40kW Liquid-cooled Generators This Warranty Shall not Apply to the Following