Briggs & Stratton 205051GS system manual Important Owner’s Considerations, Automatic Operation

Page 13

Operation

Important Owner’s Considerations

Engine Oil

notice

Any attempt to crank or start the engine before it has been properly serviced with the recommended coolant or oil will result in equipment failure.

Refer to Maintenance in the Operator’s Manual and engine manual for coolant and oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

This engine is shipped from the factory pre-run and filled with non-synthetic oil (API SL 10W-30W). This allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual.

NOTE: The use of multi-grade oil does not alter the required oil change intervals described in the engine operator’s manual.

Coolant System

This engine is shipped from the factory filled with a

50-50 mix of automotive (Dex-Cool™ orange) anti-freeze and water. This will provide optimum year round protection against freezing, boiling and corrosion. The coolant system incorporates a water heater that operates when ambient temperature is below 80ºF AND utility power is present at the transfer switch. Before starting the engine, check coolant level as described in the engine operator’s manual.

Battery

The installer must supply a sealed, rechargeable 12 Volt DC, 650 Cold Cranking Amps (CCA) 55 amp hour starting battery. The battery may not be at full charge when installed. If battery voltage is below 12 Volts, charge the battery. See Battery in the Maintenance section for details.

15 Amp Fuse

The generator’s 15 Amp fuse is critical to correct system operation. Your installer will ensure the fuse is properly installed upon completion of the installation.

Automatic Operation

To select automatic operation, do the following:

1.Confirm 15 Amp fuse is installed in control panel.

2.Set the main distribution panel circuit breaker that sends utility voltage to the transfer switch to ON.

3.Set the generator’s main circuit breaker to its ON position.

4.Set the control panel System switch to AUTO.

caution

With the system switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility source voltage drops below a preset level or during the normal exercise cycle.

To prevent possible injury that may be caused by such sudden starts, always set the system switch to OFF if performing maintenance on the system.

Remove the 15 Amp fuse before working on or around the generator or transfer switch.

Checking Automatic Operation

To check the system for proper automatic operation, proceed as follows:

1.Turn OFF main distribution panel circuit breaker sending power to automatic transfer switch.

The engine will crank and start when utility voltage is lost and the sensor has timed out. Let the system go through its entire automatic operation sequence.

2.With generator output supplying its loads, turn ON main distribution panel circuit breaker that supplies utility power to Automatic Transfer Switch.

3.The automatic transfer switch will transfer loads back to utility power after 5 minute minimum run time and utility is restored.

4.The generator will run for an additional one minute for engine cool down, then shut down.

NOTE: If utility is restored and generator does not shut down after 10 minutes, set system switch to OFF and contact your installer or local service center.

This completes the test procedures for automatic operation. The home generator will now start automatically and will supply power to the transfer switch when utility power is lost.

13

Image 13
Contents Liquid-Cooled Home Generator System Where to Find Us Table of Contents Hazard Symbols and Meanings Safety RulesPage See Essential Circuits For the Installing Dealer/Contractor InstallationFor the Home Owner Owner OrientationEssential Circuits Generator LocationDelivery Inspection To be supplied by InstallerEssential Circuit Selection Home generator system is supplied withControl Panel Door opening Provides access to control panel Features and ControlsHome Generator System Control Panel To Open an Access Door Access DoorsTo Close an Access Door Important Owner’s Considerations OperationAutomatic Operation Setting Exercise Timer MaintenanceFault Detection System Servicing the SystemLow Battery Voltage FC1 No LED Discharged BatteryLow Oil Pressure FC2 Low Voltage Generator, FC3Engine Maintenance Generator MaintenanceEngine Oil Charging the Battery BatteryServicing the Battery To Clean the GeneratorStorage When Calling the FactoryProblem Cause Correction TroubleshootingDown when loads are connected AvailableLimited Warranty Page 30 kW 45 kW Product SpecificationsManual del Operario Dónde encontrarnos Instrucciones importantes de seguridad Instalación Problemas Garantía Especificaciones del productoControles y características Operación MantenimientoSímbolos de Peligro y Significados Conserve estas instruccionesAdvertencia Precaución Para el Propietario Doméstico InstalaciónOrientación para el propietario Factores Relacionados con el CombustibleCircuitos Fundamentales Ubicación del GeneradorDistancias Desde el Generador Selección de los Circuitos Fundamentales Dispositivo Vatiaje deEl Generador Doméstico incluye lo siguiente Inspección al Momento de la EntregaGenerador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Abertura de la Puerta de llenado de RefrigerantePanel de control del sistema Para abrir una puerta de acceso Puertas de AccesoPara cerrar una puerta de acceso Funcionamiento Automático OperaciónVerificación de la Operación Automática Mantenimiento Configuración del Temporizador de PrácticaParo del Sistema Sistema de Detección de FallasBaja Tensión de la Batería FC1 No se Enciende el LED Batería DescargadaBaja Presión de Aceite FC2 Baja Tensión FC3Mantenimiento del Motor Mantenimiento del GeneradorAceite del Motor Batería Sistema refrigerante del motorCargar la Batería Almacenamiento Si Llama a la FábricaServicio la Batería Para Limpiar el GeneradorProblemas Causa Corrección ProblemasGarantía Limitada BRIGGSandSTRATTON.COM Page Especificaciones del producto Sistema generador domésticoGroupe électrogène Refroidissement par liquide Où nous trouver Fonctions et commandes Fonctionnement Directives de sécurité importantes InstallationEntreiten Dépannage Garantie Caractéristiques du produitVeuillez conserver ces instructions Symboles de Danger et MoyensDirectives de sécurité importantes SécuritéAvertissement Avis Conseils au propriétaire Au Propriétaire RésidentielFacteurs Relatifs au Combustible Circuits Essentiels Emplacement de la GénératriceDégagement Autour de la Génératrice Sélection des Circuits Essentiels Le Groupe électrogène est livré avec les éléments suivants Vérification de la LivraisonArticles non fournis Outils/équipements spécialisés nécessairesEntretien Dépannage Garantie Fonctions et commandesCommandes Fonctionnement Entretien Dépannage Garantie Tableau de commande de systèmeSécurité Instalación Pour ouvrir une porte d’accès Portes d’AccèsPour fermer une porte d’accès Fonctionnement automatique FonctionnementVérification du Fonctionnement Automatique Réglage de la Minuterie du Cycle d’Exercice EntreitenArrêt du Système Système de Détection des PannesFaible Tension de la Batterie FC1 Aucun DEL Batterie déchargéeFaible Pression d’Huile FC2 Basse Tension FC3Entretien du moteur Entretien du Générateur’Huile Moteur Batterie Système de refroidissement du moteurPour Nettoyer le Générateur Rechargez la BatterieDépannage Problème Cause SolutionCommunications avec le Fabricant RemisageFonctionnement Entretien Dépannage Garantie Sécurité Instalación CommandesPage Caractéristiques du produit Groupe électrogène