Emerson user manual Mount the Liebert GXT2-PP20KRT208 on a Wall

Page 16

Installation

5.1.2Mount the Liebert GXT2-PP20KRT208 on a Wall

Mounting the parallel POD on a wall requires eight field-supplied wall inserts and eight field-sup- plied screws. The minimum size for the wall insert is 5x30 and for the screw, M5x30.

1.Secure the four fixed brackets to the rearmost screw holes on either side of the Liebert GXT2-PP20KRT208 (see Figure 10).

2.Use the electric drill to drill the holes with suitable depth (could be the length of the wall inserts) in the wall.

3.Put the field-supplied wall inserts into the holes.

4.Hold the parallel POD against the wall, aligned with the mounting holes and use field-supplied screws to attach the unit to the wall (see Figure 10).

Figure 10 Mount the Liebert GXT2-PP20KRT208 on a wall

12

Image 16
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Specifications CommunicationImportant Safety Instructions Glossary of Symbols Introduction Maintenance Bypass CompatibilityRedundancy Design System DescriptionLiebert MultiLink Shutdown EthernetSystem Description Main Input / Output Terminal Blocks Input and Output Slots for UPSMajor Components Optional Power Distribution Parallel Communication Port WHAT’S Included Items shipped with Liebert GXT2-PP20KRT208What You Need Installation Mount the Liebert GXT2-PP20KRT208 in a Rack or on a WallMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Main Input and Output Terminal Block Connections Electrical requirementsAdd an Output Power Distribution Module-Optional Parallel POD Main Electrical Connection-Must Be Installed O/P O/P I/P O/PInitial Startup and Electrical Checks Paralleling for Capacity ConfigurationParalleling for Capacity and Redundancy Operating Modes OperationBypass Mode Battery Test Fault ConditionParallel Communication Cable Disconnection Add a Single UPS to the Online Paralleling System Remove a Single UPS from the Paralleling SystemReplacing a Faulty Power Module or UPS Internal Battery Overload ConditionBattery Low Voltage-Battery Mode UPS Status Information Communication InterfaceCommunication Calculating total load per UPS UPS Configuration Settings Specifications Parallel POD specificationsOptional output distribution specifications-PD-201 Page Net