Emerson GXT2-PP20KRT208 user manual Optional output distribution specifications-PD-201

Page 34

Specifications

Table 7

Optional output distribution specifications—PD-201

 

 

 

 

Model Number

PD-201

 

 

Dimensions, in (mm)

 

 

 

Shipping W x D x H in. (mm)

10.44 x 8.87 x 7.88 (265 x 225 x 200)

 

 

Weight, lb (kg)

 

 

 

 

 

Unit

5.29 (2.4)

 

 

 

 

Shipping

6.39 (2.9)

 

 

Electrical Specifications

 

 

 

 

 

Amp Rating

120A (multiple connectors used)

 

 

 

 

Input Power Connections

Internal Anderson connectors

 

 

Output Power Connection

 

 

 

 

 

L1-L2-G

(4) L6-20R on a 12" cord

 

 

 

 

L1-N-G

(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker

 

 

 

 

L2-N-G

(2) 5-15/20R, T-type receptacles with (1) 20A circuit breaker

 

 

 

Table 8

Optional output distribution specifications—PD-202

 

 

 

 

Model Number

PD-202

 

 

Dimensions, in (mm)

 

 

 

Shipping, W x D x H in. (mm)

10.44 x 8.87 x 7.88 (265 x 225 x 200)

 

 

Weight, lb (kg)

 

 

 

 

 

Unit

5.95 (2.7)

 

 

 

 

Shipping

7.05 (3.2)

 

 

Electrical Specifications

 

 

 

 

 

Amp Rating

120 Amps (multiple connectors used)

 

 

 

 

Input Power Connections

Internal Anderson connectors

 

 

Output Power Connection

 

 

 

 

 

L1-L2-G

(4) L6-30R on a 12" cord

 

 

 

 

L1-N-G

(2) 5-15/20R, T-type, receptacles with (1) 20A circuit breaker

 

 

 

 

L2-N-G

(2) 5-15/20R, T-type, receptacles with (1) 20A circuit breaker

 

 

 

30

Image 34
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Specifications CommunicationImportant Safety Instructions Glossary of Symbols Introduction Redundancy Design Maintenance BypassCompatibility System DescriptionLiebert MultiLink Shutdown EthernetSystem Description Main Input / Output Terminal Blocks Input and Output Slots for UPSMajor Components Optional Power Distribution Parallel Communication PortWHAT’S Included Items shipped with Liebert GXT2-PP20KRT208What You Need Installation Mount the Liebert GXT2-PP20KRT208 in a Rack or on a WallMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Main Input and Output Terminal Block Connections Electrical requirementsAdd an Output Power Distribution Module-Optional Parallel POD Main Electrical Connection-Must Be Installed O/P O/P I/P O/PInitial Startup and Electrical Checks Paralleling for Capacity ConfigurationParalleling for Capacity and Redundancy Operating Modes OperationBypass Mode Battery Test Fault ConditionParallel Communication Cable Disconnection Add a Single UPS to the Online Paralleling System Remove a Single UPS from the Paralleling SystemReplacing a Faulty Power Module or UPS Internal Battery Overload ConditionBattery Low Voltage-Battery Mode UPS Status Information Communication InterfaceCommunication Calculating total load per UPS UPS Configuration Settings Specifications Parallel POD specificationsOptional output distribution specifications-PD-201 Page Net