Emerson GXT2-PP20KRT208 user manual Add a Single UPS to the Online Paralleling System

Page 27

Operation

8.5Add a Single UPS to the Online Paralleling System

1.Make sure that breakers on the UPS to be added and the corresponding breakers on the parallel POD are in the Off position.

2.Connect the parallel power cables between the UPS and the parallel POD.

3.Turn On the corresponding input breaker (do NOT turn On the corresponding output breaker) on the parallel POD and make sure the input phase of the UPS is correct.

4.Turn On the input and output breakers on the UPS.

5.Turn on the UPS by pressing the On button.

6.Make sure that the single UPS is working normally and its output voltage is the same as the paralleling system. If the output voltage of the UPS needs to be changed with the configuration program, it must be done now.

7.Shut off the UPS by pressing the Off button and open the input breaker.

8.Make sure that the single UPS has shut down.

9.Connect the parallel communication cable between the UPS and parallel POD.

10.Close the input and output breakers on the UPS and the corresponding breakers on the parallel POD. The UPS is now in Output Off Mode.

11.Press the On button on the UPS. The UPS will join the paralleling system.

8.6Remove a Single UPS from the Paralleling System

1.Press the UPS’ Off button twice within four seconds to turn it off. The UPS will transfer to Output Off Mode.

2.Open the input and output breakers on the UPS and the corresponding input and output breakers on the parallel POD.

3.Verify that the single UPS has shut down.

4.Disconnect the parallel communication cable and the parallel power cable between the UPS and parallel POD.

NOTE

To shut down an individual UPS in the paralleling system while others are in Line Mode, press the Off button on the UPS control panel twice within four seconds.

23

Image 27
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Communication SpecificationsImportant Safety Instructions Glossary of Symbols Introduction System Description Maintenance BypassCompatibility Redundancy DesignEthernet Liebert MultiLink ShutdownSystem Description Input and Output Slots for UPS Main Input / Output Terminal BlocksMajor Components Parallel Communication Port Optional Power DistributionItems shipped with Liebert GXT2-PP20KRT208 WHAT’S IncludedWhat You Need Mount the Liebert GXT2-PP20KRT208 in a Rack or on a Wall InstallationMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Electrical requirements Main Input and Output Terminal Block ConnectionsAdd an Output Power Distribution Module-Optional O/P O/P I/P O/P Parallel POD Main Electrical Connection-Must Be InstalledInitial Startup and Electrical Checks Configuration Paralleling for CapacityParalleling for Capacity and Redundancy Operation Operating ModesBypass Mode Fault Condition Battery TestParallel Communication Cable Disconnection Remove a Single UPS from the Paralleling System Add a Single UPS to the Online Paralleling SystemOverload Condition Replacing a Faulty Power Module or UPS Internal BatteryBattery Low Voltage-Battery Mode Communication Interface UPS Status InformationCommunication Calculating total load per UPS UPS Configuration Settings Parallel POD specifications SpecificationsOptional output distribution specifications-PD-201 Page Net