Emerson GXT2-PP20KRT208 user manual Parallel Communication Port, Optional Power Distribution

Page 12

Major Components

3.5Parallel Communication Port

The Liebert GXT2-PP20KRT208 parallel POD has three 15-pin parallel communication ports on the upper right of the parallel POD. Several signals are provided on this port to communicate with each UPS. Use the parallel communication cables for the connection between the parallel POD and each UPS. When the UPS is powered on, it enters parallel mode automatically. Refer to 5.0 - Installation for the cable connection procedures

NOTICE

Do not disconnect the parallel communication cable while the parallel system is operating and powering the connected load. This may cause load-drop and damage the UPS or connected equipment.

If the parallel communication cable is disconnected or the connection is dropped during parallel operation, the UPS will shut down immediately.

If the parallel communication cable is not connected to the UPS, the UPS will not enter parallel mode, even if the parallel power cable is connected. Operating without the parallel communication cable may result in damage to the UPS.

3.6Optional Power Distribution

Additional power distribution options are available to provide the benefit of output receptacle conve- nience. See 5.4 - Add an Output Power Distribution Module—Optionalfor installation steps.

Figure 5 Optional output distribution modules

 

OUTPUT BREAKER 20A 250V~/T

OUTPUT BREAKER 20A 250V~/T

OUTPUT L1

 

T20A 125V~

 

 

PUSH TO

 

 

RESTART

 

 

 

OUTPUT BREAKER 20A 250V~/T

 

 

 

OUTPUT BREAKER 20A 250V~/T

T20A 125V~

 

 

PUSH TO

 

 

RESTART

 

 

OUTPUT L2

 

PD-201

 

 

PD-202

PD-201

 

Power Distribution Option

PD-202

(with internal connector shown)

Power Distribution Option

NOTE

The Liebert GXT2-PP20KRT208 distribution POD options are different than the distribution PODs used with individual Liebert GXT2-10000RT208 UPSs. Each POD type has different connectors and are not interchangeable.

If a Liebert GXT2-10000RT208 UPS that is to be connected to the parallel POD has a distribution POD option, then the distribution POD must be removed from the UPS to connect the parallel power cable assembly to the UPS.

8

Image 12
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Specifications CommunicationImportant Safety Instructions Glossary of Symbols Introduction Maintenance Bypass CompatibilityRedundancy Design System DescriptionLiebert MultiLink Shutdown EthernetSystem Description Input and Output Slots for UPS Main Input / Output Terminal BlocksMajor Components Optional Power Distribution Parallel Communication PortWHAT’S Included Items shipped with Liebert GXT2-PP20KRT208What You Need Installation Mount the Liebert GXT2-PP20KRT208 in a Rack or on a WallMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Main Input and Output Terminal Block Connections Electrical requirementsAdd an Output Power Distribution Module-Optional Parallel POD Main Electrical Connection-Must Be Installed O/P O/P I/P O/PInitial Startup and Electrical Checks Configuration Paralleling for CapacityParalleling for Capacity and Redundancy Operating Modes OperationBypass Mode Fault Condition Battery TestParallel Communication Cable Disconnection Add a Single UPS to the Online Paralleling System Remove a Single UPS from the Paralleling SystemReplacing a Faulty Power Module or UPS Internal Battery Overload ConditionBattery Low Voltage-Battery Mode Communication Interface UPS Status InformationCommunication Calculating total load per UPS UPS Configuration Settings Specifications Parallel POD specificationsOptional output distribution specifications-PD-201 Page Net