Emerson GXT2-PP20KRT208 user manual Specifications, Parallel POD specifications

Page 33

Specifications

10.0SPECIFICATIONS

Table 5

Parallel POD specifications

 

 

 

 

Model Number

Liebert GXT2-PP20KRT208

 

 

 

 

Model Rating

20,000VA / 16,000W at 120/208 or 120/240 VAC

 

 

Dimensions, in (mm)

 

 

 

 

 

Unit, W x D x H in. (mm)

16.94 x 9.85 x 16.61 (430 x 250 x 422)

 

 

Shipping, W x D x H in. (mm)

23.05 x 16.74 x 19.38 (585 x 425 x 492)

 

 

Weight, lb (kg)

 

 

 

 

 

Unit

41.89 (19)

 

 

 

 

Shipping

48.94 (22.2)

 

 

Input AC Parameters

 

 

 

Nominal Operating Frequency

50 or 60 Hz

 

 

 

 

Nominal Operating Voltage

120/208 or 120/240 VAC

 

 

 

 

Input Power Connection

Hardwire Terminal Block 3W + G (L-L-N-G)

 

 

Output AC Parameters

 

 

 

 

 

Voltage

120/208 or 120/240 VAC

 

 

 

 

Output Connections

Hardwire Terminal Block 3W + G (L-L-N-G);

 

also see 3.6 - Optional Power Distribution

 

 

 

Frequency

50 Hz or 60 Hz, Nominal

 

 

Agency

 

 

 

 

 

Safety

UL / c-UL Listed as accessory for UPS

 

 

 

 

ESD

EN61000-4-2, Level 4, Criteria A

 

 

 

 

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

 

 

 

 

Conducted Immunity

EN61000-4-6 Level 3, Criteria A

 

 

 

 

EFT / Burst

EN61000-4-4, Level 4, Criteria A

 

 

 

 

Surge

EN61000-4-5, Level 3, Criteria A

 

ANSI C62.41 (IEEE 587) Category A (Level 3) & B (Level 1)

 

 

 

Transportation

ISTA 1A

 

 

 

Table 6

Paralleling cable kit dimensions and weight

 

 

 

 

Model Number

Liebert GXT2-20KPC-6 (1 required for each UPS)

 

 

Dimensions, in (mm)

 

Shipping, W x D x H in. (mm)

15.76 x 15.76 x 4.02 (400 x 400 x 120)

Weight, lb (kg)

Shipping

13.89 (6.3)

29

Image 33
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Communication SpecificationsImportant Safety Instructions Glossary of Symbols Introduction Compatibility Maintenance BypassRedundancy Design System DescriptionEthernet Liebert MultiLink ShutdownSystem Description Input and Output Slots for UPS Main Input / Output Terminal BlocksMajor Components Parallel Communication Port Optional Power DistributionItems shipped with Liebert GXT2-PP20KRT208 WHAT’S IncludedWhat You Need Mount the Liebert GXT2-PP20KRT208 in a Rack or on a Wall InstallationMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Electrical requirements Main Input and Output Terminal Block ConnectionsAdd an Output Power Distribution Module-Optional O/P O/P I/P O/P Parallel POD Main Electrical Connection-Must Be InstalledInitial Startup and Electrical Checks Configuration Paralleling for CapacityParalleling for Capacity and Redundancy Operation Operating ModesBypass Mode Fault Condition Battery TestParallel Communication Cable Disconnection Remove a Single UPS from the Paralleling System Add a Single UPS to the Online Paralleling SystemOverload Condition Replacing a Faulty Power Module or UPS Internal BatteryBattery Low Voltage-Battery Mode Communication Interface UPS Status InformationCommunication Calculating total load per UPS UPS Configuration Settings Parallel POD specifications SpecificationsOptional output distribution specifications-PD-201 Page Net