Installation
5.5Parallel POD Main Electrical Connection—Must Be Installed
Electrical connections are made through a removable conduit box that attaches to the top of the paral- lel POD.
A branch breaker is required for short circuit or overcurrent protection. The installer must provide a 120A (@ 208V to 240V) branch circuit breaker. If the paralleling system detects any UPS with short circuit or overcurrent, the input circuit breaker and the output circuit breaker on the rear
The manual bypass breaker passes utility power directly to the bypass switch from the input terminal block. The three UPS input circuit breakers on the POD do not disconnect power from the manual bypass breaker.
Figure 13 120A branch circuit breaker connection
UPS1
UPS2
UPS3
63A Input and | I/P O/P | I/P O/P I/P O/P | Optional |
|
|
| Output |
| |
Output Circuit |
|
| Distribution |
|
Breakers |
|
| Module |
|
Input |
|
|
|
|
Utility |
|
|
|
|
120 A External |
| Maintenance |
|
|
Branch Circuit |
| Breaker | Output |
|
Breaker | Main I/P |
|
| |
|
|
|
| |
| Terminal Block |
| Main O/P Terminal Block | Load |
|
|
| 100 A External | |
|
|
|
| |
|
|
| Circuit Breaker |
|
! WARNING
Risk of electrical shock and fire. May cause equipment damage, personal injury and death.
A disconnect switch for the AC input circuit must be
! WARNING
Risk of electrical shock and fire. May cause equipment damage, personal injury and death.
A disconnect switch for the AC output circuit must be
17