Emerson GXT2-PP20KRT208 user manual Important Safety Instructions

Page 5

IMPORTANT SAFETY INSTRUCTIONS

! WARNING

Risk of electric shock. Can cause equipment damage, injury or death. Extreme caution is required when performing maintenance.

Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations and manufacturers’ specifications.

Be constantly aware that the UPS system contains high DC voltages as well as high AC voltages.

Opening or removing the cover may expose personnel to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the elec- trical source.

Observe all warnings and cautions in this manual. Failure to do so may result in serious injury or death.

Never work alone.

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions pertaining to the Liebert GXT2-PP20KRT208, a parallel power output device that will connect up to three Liebert GXT2-10000RT208 UPSs. Read all safety, installation and operating instructions before operating the Liebert GXT2-PP20KRT208 par- allel power output distribution (parallel POD). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Individuals must fully understand this equipment to install and operate it.

It is not intended for use with life support or other designated critical devices. Maximum load must not exceed that shown on the Liebert GXT2-PP20KRT208 rating label. This parallel POD is designed for use on a properly grounded (earthed), 100/200, 110/220, 115/230, 120/208, 120/240 or

127/220 VAC, 50Hz or 60Hz supply. Installation instructions and warning notices are found in this manual.

This Liebert parallel POD is only for use with a four-wire input: L1, L2, N, G.

This Liebert parallel POD must NOT be used with a three-wire, single-phase utility source: L1, N, G.

ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT2-PP20KRT208 complies with the limits for a Class A digital device pursuant to Part 15 of FCC rules. Operation is subject to these con- ditions:

This device may not be permitted to cause harmful interference.

This device must accept any interference received, including interference that may cause unde- sired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.

Operate the parallel POD only in an indoor environment in an ambient temperature range of 32°F to 104°F (0°C to 40°C). Install it in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases and corrosive substances.

This parallel POD contains no user serviceable parts. Refer all faults to your local dealer, Liebert rep- resentative or the Emerson Network Power Liebert Worldwide Support Group.

Never block or insert any object into the ventilation holes or other openings of a UPS or this parallel POD.

Do NOT connect equipment that could overload the parallel POD or demand half-wave rectification from the parallel POD, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any other appliance using half-wave rectification.

Storing magnetic media on top of the UPS or parallel POD may result in data loss or corruption.

Turn the parallel POD and connected UPSs Off and isolate the paralleling system before cleaning; use only a soft cloth, never liquid or aerosol cleaners.

1

Image 5
Contents Liebert GXT2-PP20KRT208 Page Table of Contents Communication SpecificationsImportant Safety Instructions Glossary of Symbols Introduction Compatibility Maintenance BypassRedundancy Design System DescriptionEthernet Liebert MultiLink ShutdownSystem Description Major Components Input and Output Slots for UPSMain Input / Output Terminal Blocks Parallel Communication Port Optional Power DistributionItems shipped with Liebert GXT2-PP20KRT208 WHAT’S IncludedWhat You Need Mount the Liebert GXT2-PP20KRT208 in a Rack or on a Wall InstallationMount the Liebert GXT2-PP20KRT208 on a Wall Paralleling System Connections Installation Electrical requirements Main Input and Output Terminal Block ConnectionsAdd an Output Power Distribution Module-Optional O/P O/P I/P O/P Parallel POD Main Electrical Connection-Must Be InstalledInitial Startup and Electrical Checks Paralleling for Capacity and Redundancy ConfigurationParalleling for Capacity Operation Operating ModesBypass Mode Parallel Communication Cable Disconnection Fault ConditionBattery Test Remove a Single UPS from the Paralleling System Add a Single UPS to the Online Paralleling SystemOverload Condition Replacing a Faulty Power Module or UPS Internal BatteryBattery Low Voltage-Battery Mode Communication Communication InterfaceUPS Status Information Calculating total load per UPS UPS Configuration Settings Parallel POD specifications SpecificationsOptional output distribution specifications-PD-201 Page Net