Emerson 480V user manual Battery Run Times, Estimated battery run time, minutes

Page 100

Specifications and Technical Data

11.4Battery Run Times

Table 35 Estimated battery run time, minutes

UPS Rating/Model

 

Number of Cabinets

 

 

 

 

 

1

 

2

3

4

 

 

 

 

 

 

 

 

40kVA UPS

 

 

 

 

 

 

 

 

 

 

 

UPS12-100MR

5

 

18

32

47

 

 

 

 

 

 

UPS12-150MR

13

 

33

53

75

 

 

 

 

 

 

UPS12-210MR

21

 

51

81

123

 

 

 

 

 

 

60kVA UPS

 

 

 

 

 

 

 

 

 

 

 

UPS12-100MR

-

 

9

18

27

 

 

 

 

 

 

UPS12-150MR

7

 

19

33

47

 

 

 

 

 

 

UPS12-210MR

11

 

31

51

73

 

 

 

 

 

 

80kVA UPS

 

 

 

 

 

 

 

 

 

 

 

UPS12-100MR

-

 

5

11

18

 

 

 

 

 

 

UPS12-150MR

-

 

13

22

33

 

 

 

 

 

 

UPS12-210MR

6

 

21

36

51

 

 

 

 

 

 

100kVA UPS

 

 

 

 

 

 

 

 

 

 

 

UPS12-100MR

-

 

-

8

12

 

 

 

 

 

 

UPS12-150MR

-

 

9

17

25

 

 

 

 

 

 

UPS12-210MR

-

 

15

27

38

 

 

 

 

 

 

120kVA UPS

 

 

 

 

 

 

 

 

 

 

 

UPS12-100MR

-

 

-

5

9

 

 

 

 

 

 

UPS12-150MR

-

 

7

13

19

 

 

 

 

 

 

UPS12-210MR

-

 

11

21

31

 

 

 

 

 

 

92

Image 100 Contents
Liebert NX UPS Page Table of Contents Options UPS SpecificationsOperator Control and Display Panel Operating Instructions Pop-Up WindowsSpecifications and Technical Data Appendix a UPS Status MessagesTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Installation External InspectionsPreliminary Checks Internal InspectionsUPS Location Battery Location Considerations in Moving the Liebert NXMechanical Considerations Special Considerations for Parallel SystemsFloor Installation ClearancesCable Entry System CompositionCabinet arrangement-Liebert NX units and battery cabinets UPS Cable Rating Power CablingLug Size and Torque Requirements UPS Input Configuration Cabling GuidelinesCable Connections Input and output busbarsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply Cabling Procedure Output System Connections-Ensure Correct Phase RotationCommon Input Connections Dual Input ConnectionsMonitor Board Features Frequency Converter ModeControl Cables Dry Contacts Maintenance Bypass Cabinet Interface Maintenance bypass cabinet interfaceInput Dry Contacts Input dry contacts atBCB Control Interface BCB control interfaceInverter mode relay center Main input fault relay centerOutput Dry Contacts Output dry contact relaysEPO input contact relays EPO Input-OptionalIndicates Pin Safety IntroductionExternal Battery Cabinet Installation Battery CabinetsInstallation Considerations Connecting the BatteriesInsulated Post Tray Handle For Cabling Non-Standard Batteries Connecting the Battery Cabinet to the UPSBCB Shunt Trip This power must be UPS protected Alber Monitoring System-OptionalLBS Cable and Settings Load Bus SynchronizationPerformance Requirements LBS CableFeatures of Parallel System Configuring Parallel System OperationGeneral Operating Principles Redundancy Paralleling Installing Parallel SystemOperation Modes Summary Cabinet Installation Power CablesConditions for Parallel System Preliminary ChecksAuxiliary Dry Contact Cables InterconnectingCables QByp Q1Ext Q2ExtTo Load Normally Open EPO Normally Closed EPOUPS Mechanical Characteristics Environmental characteristicsUPS mechanical characteristics Conformity and StandardsUPS Electrical Characteristics UPS terminalRectifier input power Liebert approved replacement batteriesRated Power kVA 100 120 Battery Manufacturer Models SuppliedInverter Output DC Intermediate CircuitBypass Input Left Side GND Left Side View Front View Max. Door Swing U3819205 Ext Batt530628 Pg , Rev Battery Breaker External Battery CabinetAuxiliary Contacts Top Top Front Right Side Front Rear SystemRear FRONTOutput Run From Conductors Ph A, B, C System Input Ph A, B, C UPS InputsPh A, B, C UPS Outputs AC OutputPh A, B, C System Outputs Utility UPS #1-UPS #4 Module AC Ph A, B, C UPS InputsGround UPS Isometric View U3819301Single module block diagram dual input configuration General DescriptionNormal Mode Battery ModeBypass Mode Bypass SuppliesMaintenance Mode Parallel Redundancy Mode System ExpansionOperator Control Panel Display Panel LayoutMimic indicators Control buttons Navigation keys Detailed view of control panelMimic Display Indicators Mimic display status indicatorsControl Buttons Control buttonsAudible Buzzer LCD OverviewNavigation Keys UPS System InformationIcons for navigation keys Description of items in UPS system windowLCD Menus and Data Items Descriptions of UPS menus and data window items Menu Type Item Type ExplanationMains InputLanguage Selection Start/stop BatteryTests Current Date and Time Set date and timeUPS Status Messages Current status and history log recordsTypes of LCD Screens Default ScreenOpening Display UPS Help Screen Screen Saver WindowPop-Up Windows Liebert NX Operating Modes UPS operating modesCircuit Breakers Circuit breakersIndicator State Startup ProcedureUPS Startup Switch from Normal Mode to Bypass Mode Switch from Bypass Mode to Normal ModeMaintenance Bypass Procedure and Powering Down the UPS Auto Restart Emergency Shutdown With EPOBattery Protection Multi-Module System ProceduresBattery Undervoltage Pre-Warning Battery End-of-Discharge EOD ProtectionTie breaker Inserting One Module into a Multi-Module System LED Function StatusShutdown Procedure-Complete UPS and Load Shutdown Commissioning a Parallel SystemParallel System Start Up Power Output Communication and Other User TerminalsAnalog Input Interface Liebert IntelliSlot CommunicationSee 10.1.5 Configuring Liebert NX communication optionsComments Baud RatesConfiguring Baud Rates Liebert IntelliSlot Web card display Relay Card pin configuration Relay card jumper configurationRelay Card Pin Function OperationAssignment MultiPort 4 CardPin Description LBS Mode-Load Bus Synchronization Remote Alarm MonitorReplacing Dust Filters Torque specifications Battery torque rating Lug Size and Torque Requirements Cable Lengths Floor to Connection Point Inside UPSDistance to connection points on the Liebert NX UPS Parallel system current tableCable size and tightening torques External cabinet dimensions, including side panelsLead/Lag ratings 250 10 N*m Battery Run Times Estimated battery run time, minutesUPS status messages Services at 800-543-2378 for assistanceEvent Message Description / Suggested Action if any High ambient air temperature Bypass voltage is beyond the normal rangeBypass voltage exceeds the limit Software according to the customer’s agreementError can also leads to the alarm Alarm if applicableInverter STS Fail Condition is removedEmergency Power Off EPOUPS status messages UPS Status Messages Page Ne t ItiTi n That