Emerson 480V user manual Relay Card pin configuration, Relay card jumper configuration

Page 93

Options

Relay Card

The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.

Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.

The relay card is rated for 24 VAC/DC at 1A and supported in any of the three Liebert IntelliSlot bays on the Liebert NX.

Table 22 Relay Card pin configuration

Pin

Function

Operation

 

 

 

1

UPS Fault

Closed if no UPS failure

 

 

 

2-3

Not Used

 

 

 

 

4

UPS Fault

Closed if UPS fails

 

 

 

5

Summary Alarm**

Closed if SUMMARY ALARM** occurs

 

 

 

6

Summary Alarm**

Closed if no alarm conditions are present

 

 

 

7

Any Mode Shutdown return

Not supported – use External EPO terminal

 

 

 

8

Not Used

 

 

 

 

9

Common - Low Battery

 

 

 

 

10

Low Battery

Closed if battery is OK

 

 

 

11

Low Battery

Closed if LOW BATTERY point occurs

 

 

 

12-13

Not Used

 

 

 

 

14

UPS Any Mode Shutdown

Not supported – use External EPO terminal

 

 

 

15

On UPS

Closed if ON UPS (inverter) power

 

 

 

16

On Battery

Closed if ON BATTERY power (Utility failure)

 

 

 

17

Common - UPS Fault, Summary Alarm,

 

On UPS, On Battery, On Bypass

 

 

 

18

On Battery

Closed if not ON Battery power (Utility OK)

 

 

 

19-23

Not Used

 

 

 

 

24

On Bypass

Closed if ON BYPASS

 

 

 

25

Not Used

 

 

 

 

**A Summary Alarm occurs when any of the following conditions exist:

1.Utility power is out of the acceptable range (voltage and/or frequency).

2.UPS is in BYPASS MODE (load not on Inverter power).

3.UPS Battery is LOW.

4.UPS fault has occurred.

Table 23 Relay card jumper configuration

Number

Connection

Description

JP01

Pin 9 to Pin 17

Allows all relay COMMONS to be tied together.

 

 

 

ANY JP02

Pin 7 to Pin 17

REMOVE - (Interconnects all relay COMMONS and the (not

 

 

supported) MODE SHUTDOWN Return

85

Image 93 Contents
Liebert NX UPS Page Table of Contents UPS Specifications OptionsOperator Control and Display Panel Pop-Up Windows Operating InstructionsAppendix a UPS Status Messages Specifications and Technical DataTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections InstallationInternal Inspections Preliminary ChecksUPS Location Considerations in Moving the Liebert NX Battery LocationMechanical Considerations Special Considerations for Parallel SystemsClearances Floor InstallationCable Entry System CompositionCabinet arrangement-Liebert NX units and battery cabinets UPS Power Cabling Cable RatingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput and output busbars Cable ConnectionsSafety Ground Protective DevicesUPS Rectifier and Bypass Input Supply Output System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsFrequency Converter Mode Monitor Board FeaturesControl Cables Dry Contacts Maintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceInput Dry Contacts Input dry contacts atBCB control interface BCB Control InterfaceMain input fault relay center Inverter mode relay centerOutput Dry Contacts Output dry contact relaysEPO Input-Optional EPO input contact relaysIndicates Pin Introduction SafetyBattery Cabinets External Battery Cabinet InstallationConnecting the Batteries Installation ConsiderationsInsulated Post Tray Handle For Cabling Connecting the Battery Cabinet to the UPS Non-Standard BatteriesBCB Shunt Trip Alber Monitoring System-Optional This power must be UPS protectedLoad Bus Synchronization LBS Cable and SettingsPerformance Requirements LBS CableConfiguring Parallel System Operation Features of Parallel SystemGeneral Installing Parallel System Operating Principles Redundancy ParallelingOperation Modes Summary Power Cables Cabinet InstallationConditions for Parallel System Preliminary ChecksInterconnecting Auxiliary Dry Contact CablesCables Q1Ext Q2Ext QBypTo Load Normally Closed EPO Normally Open EPOEnvironmental characteristics UPS Mechanical CharacteristicsUPS mechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsLiebert approved replacement batteries Rectifier input powerRated Power kVA 100 120 Battery Manufacturer Models SuppliedDC Intermediate Circuit Inverter OutputBypass Input Left Side GND Left Side View Front View Max. Door Swing U3819205 Batt Ext530628 Pg , Rev External Battery Cabinet Battery BreakerAuxiliary Contacts Top Top Front Right Side System Front RearRear FRONTOutput Run From Conductors Ph A, B, C UPS Inputs Ph A, B, C System InputPh A, B, C UPS Outputs AC OutputUtility UPS #1-UPS #4 Module AC Ph A, B, C UPS Inputs Ph A, B, C System OutputsGround UPS U3819301 Isometric ViewGeneral Description Single module block diagram dual input configurationBattery Mode Normal ModeBypass Mode Bypass SuppliesParallel Redundancy Mode System Expansion Maintenance ModeDisplay Panel Layout Operator Control PanelDetailed view of control panel Mimic indicators Control buttons Navigation keysMimic display status indicators Mimic Display IndicatorsControl buttons Control ButtonsLCD Overview Audible BuzzerUPS System Information Navigation KeysIcons for navigation keys Description of items in UPS system windowLCD Menus and Data Items Menu Type Item Type Explanation Descriptions of UPS menus and data window itemsMains InputStart/stop Battery Language SelectionTests Set date and time Current Date and TimeCurrent status and history log records UPS Status MessagesDefault Screen Types of LCD ScreensOpening Display Screen Saver Window UPS Help ScreenPop-Up Windows UPS operating modes Liebert NX Operating ModesCircuit breakers Circuit BreakersStartup Procedure Indicator StateUPS Startup Switch from Bypass Mode to Normal Mode Switch from Normal Mode to Bypass ModeMaintenance Bypass Procedure and Powering Down the UPS Emergency Shutdown With EPO Auto RestartMulti-Module System Procedures Battery ProtectionBattery Undervoltage Pre-Warning Battery End-of-Discharge EOD ProtectionTie breaker LED Function Status Inserting One Module into a Multi-Module SystemCommissioning a Parallel System Shutdown Procedure-Complete UPS and Load ShutdownParallel System Start Up Communication and Other User Terminals Power Output Analog Input Interface Liebert IntelliSlot CommunicationLiebert NX communication options See 10.1.5 ConfiguringComments Baud RatesConfiguring Baud Rates Liebert IntelliSlot Web card display Relay card jumper configuration Relay Card pin configurationRelay Card Pin Function OperationMultiPort 4 Card AssignmentPin Description Remote Alarm Monitor LBS Mode-Load Bus SynchronizationReplacing Dust Filters Battery torque rating Torque specificationsLug Size and Torque Requirements Cable Lengths Floor to Connection Point Inside UPSParallel system current table Distance to connection points on the Liebert NX UPSExternal cabinet dimensions, including side panels Cable size and tightening torquesLead/Lag ratings 250 10 N*m Estimated battery run time, minutes Battery Run TimesServices at 800-543-2378 for assistance UPS status messagesEvent Message Description / Suggested Action if any Bypass voltage is beyond the normal range High ambient air temperatureBypass voltage exceeds the limit Software according to the customer’s agreementAlarm if applicable Error can also leads to the alarmInverter STS Fail Condition is removedEPO Emergency Power OffUPS status messages UPS Status Messages Page Iti Ne tTi n That