Emerson 480V user manual Safety Ground, Protective Devices, UPS Rectifier and Bypass Input Supply

Page 21

Electrical Connections

2.1.5Safety Ground

The safety ground busbar is located below the Maintenance Bypass circuit breaker as shown in Figure 4. The safety ground cable must be connected to the ground busbar and bonded to each cabi- net in the system.

All cabinets and cable conduit should be grounded in accordance with local regulations.

! WARNING

Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.

NOTE

Proper grounding significantly reduces electromagnetic interference problems in systems.

NOTE

The ground busbar is easily accessible when the lower protective cover plate is removed.

2.1.6Protective Devices

For safety, it is necessary to install circuit breakers in the input AC supply and external battery bat- tery cabinets, external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating prac- tices, regulatory standards and the equipment to be installed.

UPS Rectifier and Bypass Input Supply

Protection from excessive overcurrents and short circuits in power supply input

External overcurrent protection for the AC output circuit is to be provided. See 5.4 - UPS Elec- trical Characteristics and Table 9 for overload capacity.

When an external battery supply not made by Liebert is used, the customer must provide overcur- rent protection for the battery circuit.

Dual Input

When wiring the UPS with dual inputs, the Rectifier input and the Bypass input must be pro- tected separately. Size the breakers according to the input currents shown in Table 8. In dual input configuration, the neutral wire of each source should be connected together to guarantee dual source has the same voltage potential to earth.

13

Image 21 Contents
Liebert NX UPS Page Table of Contents UPS Specifications OptionsOperator Control and Display Panel Pop-Up Windows Operating InstructionsAppendix a UPS Status Messages Specifications and Technical DataTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections InstallationInternal Inspections Preliminary ChecksUPS Location Considerations in Moving the Liebert NX Battery LocationMechanical Considerations Special Considerations for Parallel SystemsClearances Floor InstallationCable Entry System CompositionCabinet arrangement-Liebert NX units and battery cabinets UPS Power Cabling Cable RatingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput and output busbars Cable ConnectionsSafety Ground Protective DevicesUPS Rectifier and Bypass Input Supply Output System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsFrequency Converter Mode Monitor Board FeaturesControl Cables Dry Contacts Maintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceInput Dry Contacts Input dry contacts atBCB control interface BCB Control InterfaceMain input fault relay center Inverter mode relay centerOutput Dry Contacts Output dry contact relaysEPO Input-Optional EPO input contact relaysIndicates Pin Introduction SafetyBattery Cabinets External Battery Cabinet InstallationConnecting the Batteries Installation ConsiderationsInsulated Post Tray Handle For Cabling Connecting the Battery Cabinet to the UPS Non-Standard BatteriesBCB Shunt Trip Alber Monitoring System-Optional This power must be UPS protectedLoad Bus Synchronization LBS Cable and SettingsPerformance Requirements LBS CableConfiguring Parallel System Operation Features of Parallel SystemGeneral Installing Parallel System Operating Principles Redundancy ParallelingOperation Modes Summary Power Cables Cabinet InstallationConditions for Parallel System Preliminary ChecksInterconnecting Auxiliary Dry Contact CablesCables Q1Ext Q2Ext QBypTo Load Normally Closed EPO Normally Open EPOEnvironmental characteristics UPS Mechanical CharacteristicsUPS mechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsLiebert approved replacement batteries Rectifier input powerRated Power kVA 100 120 Battery Manufacturer Models SuppliedDC Intermediate Circuit Inverter OutputBypass Input Left Side GND Left Side View Front View Max. Door Swing U3819205 Batt Ext530628 Pg , Rev External Battery Cabinet Battery BreakerAuxiliary Contacts Top Top Front Right Side System Front RearRear FRONTOutput Run From Conductors Ph A, B, C UPS Inputs Ph A, B, C System InputPh A, B, C UPS Outputs AC OutputUtility UPS #1-UPS #4 Module AC Ph A, B, C UPS Inputs Ph A, B, C System OutputsGround UPS U3819301 Isometric ViewGeneral Description Single module block diagram dual input configurationBattery Mode Normal ModeBypass Mode Bypass SuppliesParallel Redundancy Mode System Expansion Maintenance ModeDisplay Panel Layout Operator Control PanelDetailed view of control panel Mimic indicators Control buttons Navigation keysMimic display status indicators Mimic Display IndicatorsControl buttons Control ButtonsLCD Overview Audible BuzzerUPS System Information Navigation KeysIcons for navigation keys Description of items in UPS system windowLCD Menus and Data Items Menu Type Item Type Explanation Descriptions of UPS menus and data window itemsMains InputStart/stop Battery Language SelectionTests Set date and time Current Date and TimeCurrent status and history log records UPS Status MessagesDefault Screen Types of LCD ScreensOpening Display Screen Saver Window UPS Help ScreenPop-Up Windows UPS operating modes Liebert NX Operating ModesCircuit breakers Circuit BreakersStartup Procedure Indicator StateUPS Startup Switch from Bypass Mode to Normal Mode Switch from Normal Mode to Bypass ModeMaintenance Bypass Procedure and Powering Down the UPS Emergency Shutdown With EPO Auto RestartMulti-Module System Procedures Battery ProtectionBattery Undervoltage Pre-Warning Battery End-of-Discharge EOD ProtectionTie breaker LED Function Status Inserting One Module into a Multi-Module SystemCommissioning a Parallel System Shutdown Procedure-Complete UPS and Load ShutdownParallel System Start Up Communication and Other User Terminals Power OutputAnalog Input Interface Liebert IntelliSlot CommunicationLiebert NX communication options See 10.1.5 ConfiguringComments Baud RatesConfiguring Baud Rates Liebert IntelliSlot Web card display Relay card jumper configuration Relay Card pin configurationRelay Card Pin Function OperationMultiPort 4 Card AssignmentPin Description Remote Alarm Monitor LBS Mode-Load Bus SynchronizationReplacing Dust Filters Battery torque rating Torque specificationsLug Size and Torque Requirements Cable Lengths Floor to Connection Point Inside UPSParallel system current table Distance to connection points on the Liebert NX UPSExternal cabinet dimensions, including side panels Cable size and tightening torquesLead/Lag ratings 250 10 N*m Estimated battery run time, minutes Battery Run TimesServices at 800-543-2378 for assistance UPS status messagesEvent Message Description / Suggested Action if any Bypass voltage is beyond the normal range High ambient air temperatureBypass voltage exceeds the limit Software according to the customer’s agreementAlarm if applicable Error can also leads to the alarmInverter STS Fail Condition is removedEPO Emergency Power OffUPS status messages UPS Status Messages Page Iti Ne tTi n That
Related manuals
Manual 112 pages 61.01 Kb