Emerson 480V user manual Internal Inspections, Preliminary Checks, UPS Location

Page 13

Installation

1.2Internal Inspections

1.Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately.

2.Check the nameplate inside the cabinet door to verify that the model number and rating correspond to the ones specified. Record the model number and serial number in the front of this installation manual. This information is necessary should service be required.

3.Check for loose connections or unsecured components in the cabinet.

4.Check for shipping damage to internal components.

1.2.1Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the Liebert NX from excessive moisture (see 5.2 - UPS Environmental).

! CAUTION

If the battery cabinet must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the battery cabinet must be connected to the Liebert NX UPS and the UPS must be connected to utility power and started up because the charger operates only while the Liebert NX UPS is operating.

! CAUTION

When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient operating temperature.

1.3Preliminary Checks

1.3.1Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

1.4UPS Location

1.4.1Positioning the UPS

Choose a location for the UPS that offers:

Easy connection to inputs, outputs and auxiliary equipment

Enough space to service the UPS

Air circulation sufficient to expel heat produced by UPS

Protection against moisture and excessive humidity

Protection against dust and other particulate matter

Compliance with fire prevention regulations and practices

Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

1.4.2Environmental Considerations

Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions stipulated in 5.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.

The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).

For optimal UPS and battery system performance and service life, maintain the operating tempera- ture within the range of 74-80°F, (23-27°C).

The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 8 in. (203mm).

See Table 7 for details on heat dissipation.

5

Image 13
Contents Liebert NX UPS Page Table of Contents Options UPS SpecificationsOperator Control and Display Panel Pop-Up Windows Operating InstructionsAppendix a UPS Status Messages Specifications and Technical DataTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections InstallationPreliminary Checks Internal InspectionsUPS Location Considerations in Moving the Liebert NX Battery LocationMechanical Considerations Special Considerations for Parallel SystemsClearances Floor InstallationCable Entry System CompositionCabinet arrangement-Liebert NX units and battery cabinets UPS Cable Rating Power CablingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput and output busbars Cable ConnectionsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply Output System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsMonitor Board Features Frequency Converter ModeControl Cables Dry Contacts Maintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceInput Dry Contacts Input dry contacts atBCB control interface BCB Control InterfaceMain input fault relay center Inverter mode relay centerOutput Dry Contacts Output dry contact relaysEPO input contact relays EPO Input-OptionalIndicates Pin Introduction SafetyBattery Cabinets External Battery Cabinet InstallationInstallation Considerations Connecting the BatteriesInsulated Post Tray Handle For Cabling Non-Standard Batteries Connecting the Battery Cabinet to the UPSBCB Shunt Trip Alber Monitoring System-Optional This power must be UPS protectedLoad Bus Synchronization LBS Cable and SettingsPerformance Requirements LBS CableFeatures of Parallel System Configuring Parallel System OperationGeneral Operating Principles Redundancy Paralleling Installing Parallel SystemOperation Modes Summary Power Cables Cabinet InstallationConditions for Parallel System Preliminary ChecksAuxiliary Dry Contact Cables InterconnectingCables QByp Q1Ext Q2ExtTo Load Normally Closed EPO Normally Open EPOEnvironmental characteristics UPS Mechanical CharacteristicsUPS mechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsLiebert approved replacement batteries Rectifier input powerRated Power kVA 100 120 Battery Manufacturer Models SuppliedInverter Output DC Intermediate CircuitBypass Input Left Side GND Left Side View Front View Max. Door Swing U3819205 Ext Batt530628 Pg , Rev Battery Breaker External Battery CabinetAuxiliary Contacts Top Top Front Right Side System Front RearRear FRONTOutput Run From Conductors Ph A, B, C UPS Inputs Ph A, B, C System InputPh A, B, C UPS Outputs AC OutputPh A, B, C System Outputs Utility UPS #1-UPS #4 Module AC Ph A, B, C UPS InputsGround UPS U3819301 Isometric ViewGeneral Description Single module block diagram dual input configurationBattery Mode Normal ModeBypass Mode Bypass SuppliesParallel Redundancy Mode System Expansion Maintenance ModeDisplay Panel Layout Operator Control PanelDetailed view of control panel Mimic indicators Control buttons Navigation keysMimic display status indicators Mimic Display IndicatorsControl buttons Control ButtonsLCD Overview Audible BuzzerUPS System Information Navigation KeysIcons for navigation keys Description of items in UPS system windowLCD Menus and Data Items Menu Type Item Type Explanation Descriptions of UPS menus and data window itemsMains InputLanguage Selection Start/stop BatteryTests Set date and time Current Date and TimeCurrent status and history log records UPS Status MessagesTypes of LCD Screens Default ScreenOpening Display Screen Saver Window UPS Help ScreenPop-Up Windows UPS operating modes Liebert NX Operating ModesCircuit breakers Circuit BreakersIndicator State Startup ProcedureUPS Startup Switch from Bypass Mode to Normal Mode Switch from Normal Mode to Bypass ModeMaintenance Bypass Procedure and Powering Down the UPS Emergency Shutdown With EPO Auto RestartMulti-Module System Procedures Battery ProtectionBattery Undervoltage Pre-Warning Battery End-of-Discharge EOD ProtectionTie breaker LED Function Status Inserting One Module into a Multi-Module SystemCommissioning a Parallel System Shutdown Procedure-Complete UPS and Load ShutdownParallel System Start Up Communication and Other User Terminals Power OutputAnalog Input Interface Liebert IntelliSlot CommunicationLiebert NX communication options See 10.1.5 ConfiguringComments Baud RatesConfiguring Baud Rates Liebert IntelliSlot Web card display Relay card jumper configuration Relay Card pin configurationRelay Card Pin Function OperationAssignment MultiPort 4 CardPin Description LBS Mode-Load Bus Synchronization Remote Alarm MonitorReplacing Dust Filters Battery torque rating Torque specificationsLug Size and Torque Requirements Cable Lengths Floor to Connection Point Inside UPSParallel system current table Distance to connection points on the Liebert NX UPSCable size and tightening torques External cabinet dimensions, including side panelsLead/Lag ratings 250 10 N*m Estimated battery run time, minutes Battery Run TimesUPS status messages Services at 800-543-2378 for assistanceEvent Message Description / Suggested Action if any Bypass voltage is beyond the normal range High ambient air temperatureBypass voltage exceeds the limit Software according to the customer’s agreementAlarm if applicable Error can also leads to the alarmInverter STS Fail Condition is removedEPO Emergency Power OffUPS status messages UPS Status Messages Page Iti Ne tTi n That
Related manuals
Manual 112 pages 61.01 Kb

480V specifications

The Emerson 480V power systems play a critical role in modern industrial applications, providing reliable and efficient power distribution. These systems are designed for facilities that require robust performance and operational efficiency while adhering to safety regulations. With voltage ratings at 480V, they cater primarily to industries such as manufacturing, data centers, and commercial buildings.

One of the main features of the Emerson 480V systems is their scalability. These systems can be easily adapted and expanded as operational demands grow, thereby reducing initial investment costs and providing a flexible solution for evolving business needs. This ability to scale is crucial in a fast-paced environment where demands can change rapidly.

The Emerson 480V systems also incorporate advanced technologies for improved performance and safety. One key technology is the use of smart grid solutions. This enables real-time monitoring, diagnostics, and control, allowing facility managers to optimize energy consumption and reduce operational costs. Furthermore, these systems often include integrated protection devices that enhance safety measures by minimizing the risk of electrical faults, overloads, or short circuits.

Energy efficiency is another characteristic that distinguishes Emerson 480V systems from traditional alternatives. With advanced power management features, these systems effectively reduce energy waste and lower electricity bills. Emerson’s commitment to sustainability is evident in its designs, which aim to minimize environmental impact through energy-efficient technologies.

The build quality of Emerson 480V systems is also noteworthy. They are designed to withstand harsh industrial environments and are constructed with high-grade materials that promote longevity and reliability. The modular design allows for easy maintenance and repair, which further extends the lifespan of the system.

Additionally, Emerson 480V systems are equipped with user-friendly interfaces that facilitate ease of operation. This ensures that operators can efficiently manage and control power distribution without extensive training. The combination of performance, scalability, safety features, and user-centric design makes Emerson 480V systems an ideal choice for businesses looking to enhance their electrical infrastructure.

In summary, Emerson 480V power systems are a leading solution for industrial power distribution, characterized by their scalability, smart technology integration, energy efficiency, robust build quality, and user-friendly operation. These attributes make them a valuable investment for any organization aiming to improve its electrical management and operational performance.