Emerson 480V user manual Audible Buzzer, LCD Overview

Page 68

Operator Control and Display Panel

8.4Audible Buzzer

The buzzer produces three types of sounds:

Single beep - when any control button is pressed

Single beep repeating every two seconds - the system has a general alarm

Continuous - the system has a serious fault

If the buzzer makes no sound, the system may be operating properly, or an alarm may have been silenced manually.

Figure 43 Buzzer location

Buzzer

LED1

LED2 LED4 LED5

LED3

STATUS

Liebert NX

2007-01-06

09:20:37

 

 

80kVA-3X3

Single

 

Normal

 

 

 

Main

Bypass

Output

 

 

L-N current (A)

L 1-N/L2

L2-N/L3

L3-N/L1

 

 

71.4

70.8

71.3

 

 

Frequency (HZ)

59.9

59.9

59.9

EPO

 

L-L voltage (V)

480

480

480

 

 

 

PowerFactor

0.99

0.99

0.99

INVERTER OFF

FAULT CLEAR

 

 

 

 

 

Input disconnect closed

01-06 09:15

 

 

Output disconnect closed

01-06 09:15

SILENCE ON/OFF

Bypass abnormal

01-06 09:15

 

 

 

 

 

 

?

INVERTER ON

 

 

 

 

 

 

 

F1

F2

F3

F4

HELP

 

 

8.5LCD Overview

The LCD on the front panel has five main sections, as shown in Figure 44. Press the F1 key below the LCD to scroll through these sections.

UPS System Information - view UPS name and model, date and time, overall status (see Table 18).

LCD Menu - choose a category of data items to appear below the menus (see Table 19).

Data and Settings - view data items for the selected menu (see Table 19).

Current Status Messages - check any active UPS event and alarm messages (see Appendix A).

Navigation Key Icons - look at the icon above each navigation key to determine how the key operates when pressed (see 8.6 - Navigation Keys).

The LCD displays alarm information in real time. After appearing in the current status section of the LCD, status messages are stored in the history log—512 records can be stored and retrieved.

Figure 44 Sections of the LCD

LCD menu

Data and settings

Current status messages

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert NX

2007-01-06

 

09:20:37

 

 

 

 

 

 

80kVA-3X3

Single

 

 

Normal

 

 

 

 

 

 

 

Main

Bypass

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

L1-N/L2 L2-N/L3

L3-N/L1

 

 

 

 

 

 

L-N current(A)

71.4

70.8

71.3

 

 

 

 

 

 

Frequency(HZ)

59.9

59.9

59.9

 

 

 

 

 

 

L-L voltage(V)

480

480

480

 

 

 

 

 

 

PowerFactor

0.99

0.99

0.99

 

 

 

 

 

 

Input disconnect closed

01-06 09:15

 

 

 

 

 

 

Output disconnect closed 01-06 09:15

 

 

 

 

 

 

Bypass abnormal

01-06 09:15

 

 

 

 

 

 

 

 

 

 

 

?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1

F2

F3

 

F4

 

HELP

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS system information

Navigation key icons

60

Image 68
Contents Liebert NX UPS Page Table of Contents Operator Control and Display Panel UPS SpecificationsOptions Operating Instructions Pop-Up WindowsSpecifications and Technical Data Appendix a UPS Status MessagesTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Installation External InspectionsUPS Location Internal InspectionsPreliminary Checks Battery Location Considerations in Moving the Liebert NXMechanical Considerations Special Considerations for Parallel SystemsFloor Installation ClearancesCable Entry System CompositionCabinet arrangement-Liebert NX units and battery cabinets UPS Lug Size and Torque Requirements Power CablingCable Rating UPS Input Configuration Cabling GuidelinesCable Connections Input and output busbarsUPS Rectifier and Bypass Input Supply Safety GroundProtective Devices Cabling Procedure Output System Connections-Ensure Correct Phase RotationCommon Input Connections Dual Input ConnectionsControl Cables Frequency Converter ModeMonitor Board Features Dry Contacts Maintenance Bypass Cabinet Interface Maintenance bypass cabinet interfaceInput Dry Contacts Input dry contacts atBCB Control Interface BCB control interfaceInverter mode relay center Main input fault relay centerOutput Dry Contacts Output dry contact relaysIndicates Pin EPO Input-OptionalEPO input contact relays Safety IntroductionExternal Battery Cabinet Installation Battery CabinetsInsulated Post Tray Handle For Cabling Connecting the BatteriesInstallation Considerations BCB Shunt Trip Connecting the Battery Cabinet to the UPSNon-Standard Batteries This power must be UPS protected Alber Monitoring System-OptionalLBS Cable and Settings Load Bus SynchronizationPerformance Requirements LBS CableGeneral Configuring Parallel System OperationFeatures of Parallel System Operation Modes Summary Installing Parallel SystemOperating Principles Redundancy Paralleling Cabinet Installation Power CablesConditions for Parallel System Preliminary ChecksCables InterconnectingAuxiliary Dry Contact Cables To Load Q1Ext Q2ExtQByp Normally Open EPO Normally Closed EPOUPS Mechanical Characteristics Environmental characteristicsUPS mechanical characteristics Conformity and StandardsUPS Electrical Characteristics UPS terminalRectifier input power Liebert approved replacement batteriesRated Power kVA 100 120 Battery Manufacturer Models SuppliedBypass Input DC Intermediate CircuitInverter Output Left Side GND Left Side View Front View Max. Door Swing U3819205 530628 Pg , Rev BattExt Auxiliary Contacts External Battery CabinetBattery Breaker Top Top Front Right Side Front Rear SystemRear FRONTOutput Run From Conductors Ph A, B, C System Input Ph A, B, C UPS InputsPh A, B, C UPS Outputs AC OutputGround UPS Utility UPS #1-UPS #4 Module AC Ph A, B, C UPS InputsPh A, B, C System Outputs Isometric View U3819301Single module block diagram dual input configuration General DescriptionNormal Mode Battery ModeBypass Mode Bypass SuppliesMaintenance Mode Parallel Redundancy Mode System ExpansionOperator Control Panel Display Panel LayoutMimic indicators Control buttons Navigation keys Detailed view of control panelMimic Display Indicators Mimic display status indicatorsControl Buttons Control buttonsAudible Buzzer LCD OverviewNavigation Keys UPS System InformationIcons for navigation keys Description of items in UPS system windowLCD Menus and Data Items Descriptions of UPS menus and data window items Menu Type Item Type ExplanationMains InputTests Start/stop BatteryLanguage Selection Current Date and Time Set date and timeUPS Status Messages Current status and history log recordsOpening Display Default ScreenTypes of LCD Screens UPS Help Screen Screen Saver WindowPop-Up Windows Liebert NX Operating Modes UPS operating modesCircuit Breakers Circuit breakersUPS Startup Startup ProcedureIndicator State Switch from Normal Mode to Bypass Mode Switch from Bypass Mode to Normal ModeMaintenance Bypass Procedure and Powering Down the UPS Auto Restart Emergency Shutdown With EPOBattery Protection Multi-Module System ProceduresBattery Undervoltage Pre-Warning Battery End-of-Discharge EOD ProtectionTie breaker Inserting One Module into a Multi-Module System LED Function StatusShutdown Procedure-Complete UPS and Load Shutdown Commissioning a Parallel SystemParallel System Start Up Power Output Communication and Other User TerminalsAnalog Input Interface Liebert IntelliSlot CommunicationSee 10.1.5 Configuring Liebert NX communication optionsComments Baud RatesConfiguring Baud Rates Liebert IntelliSlot Web card display Relay Card pin configuration Relay card jumper configurationRelay Card Pin Function OperationPin Description MultiPort 4 CardAssignment Replacing Dust Filters Remote Alarm MonitorLBS Mode-Load Bus Synchronization Torque specifications Battery torque ratingLug Size and Torque Requirements Cable Lengths Floor to Connection Point Inside UPSDistance to connection points on the Liebert NX UPS Parallel system current tableLead/Lag ratings External cabinet dimensions, including side panelsCable size and tightening torques 250 10 N*m Battery Run Times Estimated battery run time, minutesEvent Message Description / Suggested Action if any Services at 800-543-2378 for assistanceUPS status messages High ambient air temperature Bypass voltage is beyond the normal rangeBypass voltage exceeds the limit Software according to the customer’s agreementError can also leads to the alarm Alarm if applicableInverter STS Fail Condition is removedEmergency Power Off EPOUPS status messages UPS Status Messages Page Ne t ItiTi n That
Related manuals
Manual 112 pages 61.01 Kb

480V specifications

The Emerson 480V power systems play a critical role in modern industrial applications, providing reliable and efficient power distribution. These systems are designed for facilities that require robust performance and operational efficiency while adhering to safety regulations. With voltage ratings at 480V, they cater primarily to industries such as manufacturing, data centers, and commercial buildings.

One of the main features of the Emerson 480V systems is their scalability. These systems can be easily adapted and expanded as operational demands grow, thereby reducing initial investment costs and providing a flexible solution for evolving business needs. This ability to scale is crucial in a fast-paced environment where demands can change rapidly.

The Emerson 480V systems also incorporate advanced technologies for improved performance and safety. One key technology is the use of smart grid solutions. This enables real-time monitoring, diagnostics, and control, allowing facility managers to optimize energy consumption and reduce operational costs. Furthermore, these systems often include integrated protection devices that enhance safety measures by minimizing the risk of electrical faults, overloads, or short circuits.

Energy efficiency is another characteristic that distinguishes Emerson 480V systems from traditional alternatives. With advanced power management features, these systems effectively reduce energy waste and lower electricity bills. Emerson’s commitment to sustainability is evident in its designs, which aim to minimize environmental impact through energy-efficient technologies.

The build quality of Emerson 480V systems is also noteworthy. They are designed to withstand harsh industrial environments and are constructed with high-grade materials that promote longevity and reliability. The modular design allows for easy maintenance and repair, which further extends the lifespan of the system.

Additionally, Emerson 480V systems are equipped with user-friendly interfaces that facilitate ease of operation. This ensures that operators can efficiently manage and control power distribution without extensive training. The combination of performance, scalability, safety features, and user-centric design makes Emerson 480V systems an ideal choice for businesses looking to enhance their electrical infrastructure.

In summary, Emerson 480V power systems are a leading solution for industrial power distribution, characterized by their scalability, smart technology integration, energy efficiency, robust build quality, and user-friendly operation. These attributes make them a valuable investment for any organization aiming to improve its electrical management and operational performance.