Page 19

Electrical Connections

2.1.2UPS Input Configuration

Figure 3 illustrates the Liebert NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally with properly sized protective devices. By default, the unit ships with internal links installed between the bypass input and main input (Single Input configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the input bus bars, then wire the Main input directly to CB1 (see Figure 4).

Figure 3 Single module block diagram—dual input configuration

2.1.3Cabling Guidelines

The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.

1.The ground conductor should be sized in accordance with the input overcurrent protection device data in Table 8. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit.

Output and input cables must be run in separate conduit.

2.Consider using paralleled smaller cables for heavy currents—this can ease installation.

3.When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in UPS terminal. For terminal connection sizing, see Table 8.

4.In most installations, especially parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.

NOTE

If more load is added to the distribution panel, the unit’s cabling must be resized.

5.When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference.

11

Image 19
Contents Liebert NX UPS Page Table of Contents Options UPS SpecificationsOperator Control and Display Panel Pop-Up Windows Operating InstructionsAppendix a UPS Status Messages Specifications and Technical DataTables Page Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections InstallationPreliminary Checks Internal InspectionsUPS Location Special Considerations for Parallel Systems Battery LocationConsiderations in Moving the Liebert NX Mechanical ConsiderationsSystem Composition Floor InstallationClearances Cable EntryCabinet arrangement-Liebert NX units and battery cabinets UPS Cable Rating Power CablingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationInput and output busbars Cable ConnectionsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply Dual Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Common Input ConnectionsMonitor Board Features Frequency Converter ModeControl Cables Dry Contacts Input dry contacts at Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface Input Dry ContactsBCB control interface BCB Control InterfaceOutput dry contact relays Inverter mode relay centerMain input fault relay center Output Dry ContactsEPO input contact relays EPO Input-OptionalIndicates Pin Introduction SafetyBattery Cabinets External Battery Cabinet InstallationInstallation Considerations Connecting the BatteriesInsulated Post Tray Handle For Cabling Non-Standard Batteries Connecting the Battery Cabinet to the UPSBCB Shunt Trip Alber Monitoring System-Optional This power must be UPS protectedLBS Cable LBS Cable and SettingsLoad Bus Synchronization Performance RequirementsFeatures of Parallel System Configuring Parallel System OperationGeneral Operating Principles Redundancy Paralleling Installing Parallel SystemOperation Modes Summary Preliminary Checks Cabinet InstallationPower Cables Conditions for Parallel SystemAuxiliary Dry Contact Cables InterconnectingCables QByp Q1Ext Q2ExtTo Load Normally Closed EPO Normally Open EPOConformity and Standards UPS Mechanical CharacteristicsEnvironmental characteristics UPS mechanical characteristicsUPS terminal UPS Electrical CharacteristicsBattery Manufacturer Models Supplied Rectifier input powerLiebert approved replacement batteries Rated Power kVA 100 120Inverter Output DC Intermediate CircuitBypass Input Left Side GND Left Side View Front View Max. Door Swing U3819205 Ext Batt530628 Pg , Rev Battery Breaker External Battery CabinetAuxiliary Contacts Top Top Front Right Side System Front RearRear FRONTOutput Run From Conductors AC Output Ph A, B, C System InputPh A, B, C UPS Inputs Ph A, B, C UPS OutputsPh A, B, C System Outputs Utility UPS #1-UPS #4 Module AC Ph A, B, C UPS InputsGround UPS U3819301 Isometric ViewGeneral Description Single module block diagram dual input configurationBypass Supplies Normal ModeBattery Mode Bypass ModeParallel Redundancy Mode System Expansion Maintenance ModeDisplay Panel Layout Operator Control PanelDetailed view of control panel Mimic indicators Control buttons Navigation keysMimic display status indicators Mimic Display IndicatorsControl buttons Control ButtonsLCD Overview Audible BuzzerDescription of items in UPS system window Navigation KeysUPS System Information Icons for navigation keysLCD Menus and Data Items Input Descriptions of UPS menus and data window itemsMenu Type Item Type Explanation MainsLanguage Selection Start/stop BatteryTests Set date and time Current Date and TimeCurrent status and history log records UPS Status MessagesTypes of LCD Screens Default ScreenOpening Display Screen Saver Window UPS Help ScreenPop-Up Windows UPS operating modes Liebert NX Operating ModesCircuit breakers Circuit BreakersIndicator State Startup ProcedureUPS Startup Switch from Bypass Mode to Normal Mode Switch from Normal Mode to Bypass ModeMaintenance Bypass Procedure and Powering Down the UPS Emergency Shutdown With EPO Auto RestartBattery End-of-Discharge EOD Protection Battery ProtectionMulti-Module System Procedures Battery Undervoltage Pre-WarningTie breaker LED Function Status Inserting One Module into a Multi-Module SystemCommissioning a Parallel System Shutdown Procedure-Complete UPS and Load ShutdownParallel System Start Up Liebert IntelliSlot Communication Power OutputCommunication and Other User Terminals Analog Input InterfaceBaud Rates See 10.1.5 ConfiguringLiebert NX communication options CommentsConfiguring Baud Rates Liebert IntelliSlot Web card display Pin Function Operation Relay Card pin configurationRelay card jumper configuration Relay CardAssignment MultiPort 4 CardPin Description LBS Mode-Load Bus Synchronization Remote Alarm MonitorReplacing Dust Filters Cable Lengths Floor to Connection Point Inside UPS Torque specificationsBattery torque rating Lug Size and Torque RequirementsParallel system current table Distance to connection points on the Liebert NX UPSCable size and tightening torques External cabinet dimensions, including side panelsLead/Lag ratings 250 10 N*m Estimated battery run time, minutes Battery Run TimesUPS status messages Services at 800-543-2378 for assistanceEvent Message Description / Suggested Action if any Software according to the customer’s agreement High ambient air temperatureBypass voltage is beyond the normal range Bypass voltage exceeds the limitCondition is removed Error can also leads to the alarmAlarm if applicable Inverter STS FailEPO Emergency Power OffUPS status messages UPS Status Messages Page That Ne tIti Ti n
Related manuals
Manual 112 pages 61.01 Kb

480V specifications

The Emerson 480V power systems play a critical role in modern industrial applications, providing reliable and efficient power distribution. These systems are designed for facilities that require robust performance and operational efficiency while adhering to safety regulations. With voltage ratings at 480V, they cater primarily to industries such as manufacturing, data centers, and commercial buildings.

One of the main features of the Emerson 480V systems is their scalability. These systems can be easily adapted and expanded as operational demands grow, thereby reducing initial investment costs and providing a flexible solution for evolving business needs. This ability to scale is crucial in a fast-paced environment where demands can change rapidly.

The Emerson 480V systems also incorporate advanced technologies for improved performance and safety. One key technology is the use of smart grid solutions. This enables real-time monitoring, diagnostics, and control, allowing facility managers to optimize energy consumption and reduce operational costs. Furthermore, these systems often include integrated protection devices that enhance safety measures by minimizing the risk of electrical faults, overloads, or short circuits.

Energy efficiency is another characteristic that distinguishes Emerson 480V systems from traditional alternatives. With advanced power management features, these systems effectively reduce energy waste and lower electricity bills. Emerson’s commitment to sustainability is evident in its designs, which aim to minimize environmental impact through energy-efficient technologies.

The build quality of Emerson 480V systems is also noteworthy. They are designed to withstand harsh industrial environments and are constructed with high-grade materials that promote longevity and reliability. The modular design allows for easy maintenance and repair, which further extends the lifespan of the system.

Additionally, Emerson 480V systems are equipped with user-friendly interfaces that facilitate ease of operation. This ensures that operators can efficiently manage and control power distribution without extensive training. The combination of performance, scalability, safety features, and user-centric design makes Emerson 480V systems an ideal choice for businesses looking to enhance their electrical infrastructure.

In summary, Emerson 480V power systems are a leading solution for industrial power distribution, characterized by their scalability, smart technology integration, energy efficiency, robust build quality, and user-friendly operation. These attributes make them a valuable investment for any organization aiming to improve its electrical management and operational performance.