Emerson Series 300 manual Time Delay Adjustment, Sensor Adjustments, Time Delay Settings

Page 13

SECTION 4 ADJUSTMENTS

Time Delay Adjustment

Standard time delays are set to customer specifications (if none specified, standard factory settings are used).

To change a setting, follow procedure on page 4-2. Use Table 4-1 as a guide to time delay values and their corre- sponding adjustment DIP switch or potentiometer.

 

 

Table 4-1. Time Delay Settings

 

 

 

 

 

 

 

 

DESCRIPTION

LABELS

FACTORY

ADJUSTMENT

S3 DIP

SETTING

RANGE

SWITCH

 

 

Override Momentary

TD ES

3 seconds

1 second

Actuator 1 on

 

 

 

Normal Source Outages

3 seconds

Actuator 1 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer to Emergency

TIMER

0 minutes

0 to 5

 

 

 

N/E

(full ccw)

minutes

 

 

 

 

 

 

Override Momentary

4 seconds

non-adjustable

 

 

 

Emergency S. Outages

 

 

 

 

 

 

 

 

Retransfer to Normal

TIMER

30 minutes

1 second to

 

 

 

E/N

(full cw)

30 minutes

 

 

 

 

 

 

Unloaded Running

5 minutes

non-adjustable

 

 

 

(Engine Cooldown)

 

 

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

 

 

 

 

POTENTIOMETER

 

 

1

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

P2

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

Sensor Adjustments

Voltage and frequency sensor pickup and dropout points are set to customer specifications (if none specified, standard factory settings are used). To change a setting, follow procedure on page 4–2. Use Tables 4-2 and 4–3 for settings and corresponding DIP switch actuators.

Any change in these settings may affect the normal operation of the automatic transfer switch. This change could allow the load circuits to remain connected to a low voltage source.

Table 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).

DESCRIPTION

LABELS

SETTING

% of nominal

S1 DIP

FACT. SET

ADJ RANGE

SWITCH

 

 

 

 

PU / N

Pickup

90 %

95 % *

Actuator 3 off

 

 

 

90 %

Actuator 3 on

 

 

 

 

 

 

 

 

 

 

 

 

90 % *

Actuator 1 off

 

 

 

 

 

 

 

 

 

 

 

Actuator 2 off

 

 

 

 

 

 

 

 

 

Normal Source Voltage

 

 

 

85 %

Actuator 1 on

 

 

 

 

 

 

 

 

 

 

Actuator 2 off

 

 

 

DO / N

Dropout

85 %

 

 

 

 

80 %

Actuator 1 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator 2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

70 %

Actuator 1 on

 

 

 

 

 

 

 

 

 

 

 

Actuator 2 on

 

 

 

 

 

 

 

 

 

Emergency Source

– –

Pickup

90 %

non-adjustable

– –

 

 

Voltage

– –

Dropout

75 %

non-adjustable

 

 

 

 

 

– –

Pickup

95 %

non-adjustable

– –

 

 

Emergency Source

– –

Dropout

85 %

non-adjustable

 

 

 

 

 

 

 

60 Hz

Actuator 4 off

 

 

Frequency

60 / 50

60 / 50 Hz

60 Hz

 

 

Hz

50 Hz

Actuator 4 on

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Phases

3, 1

3 / 1

3

3 phase

Actuator 6 off

 

1 phase

Actuator 6 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 3 1 2 1 2 1 2 1 2

4 4 6 6

* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.

Table 4-3. Transformer Voltage Adjust.

(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)

DESCRIPTION

LABELS

FACTORY SETTING

ADJUSTMENT

S3 DIP SWITCH

Voltage Adjust (4.2%)

LOW /

HI

LOW

Actuator 2 off

 

 

 

 

 

HI

HI

Actuator 2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

4---1

Image 13
Contents Operator’s Manual 600 800 1000 1200 Nameplate Catalog Number IdentificationController Membrane controls Rating LabelPage Section InstallationEngine Starting Contacts InstallationAuxiliary Circuits Connections to ControllerATS Position Handle Indicators Installation Functional TestManual Operation Test Voltage Checks Close the enclosure door first Electrical OperationTransfer To Emergency Sequence of OperationPreventive Maintenance Testing & ServiceDisconnecting the Controller TROUBLE-SHOOTING Testing & ServiceProceed with care Automatic transfer switch is energized Manual Load TransferTime Delay Adjustment AdjustmentsSensor Adjustments Time Delay SettingsHow to Change a Setting AdjustmentsClose the enclosure door DIP Switch Settings Control Features Engine ExercisersHow to Set Built-In Timer BUILT-IN Engine ExerciserProgrammable Engine Exerciser Module Control FeaturesFast / Slow Adjust Display Daylight Savings Time Adjust DisplayFill in your settings for future reference Navigating the MenuInphase Monitor For Motor Load Transfer Remote Control FeaturesLoad Disconnect Feature Strip Heater Accessory Control Features Optional Strip Heater AccessoryAvailable Kits from Asco ControlsIndex