Page 5

SECTION 1

Series 300 Automatic Transfer Switches are factory wired and tested. Installation requires skid removal then securing the enclosure to the supporting foundation.

Remove the Shipping Skid

Open the front door and remove the four lag screws (2 in front, 2 in rear) securing enclosure to the wood skid.

Supporting Foundation

The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the Series 300 for all mounting details including door opening space.

If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.

Mounting

Refer to the applicable enclosure outline drawing fur- nished with this switch and mount the Series 300 according to details and instructions shown on diagram.

INSTALLATION

Testing Power Conductors

Do not connect the power conductors to the ASCO Series 300 transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-sus- pended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.

Protect the automatic transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the ATS.

Connecting Power Conductors

After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with this Series

300.Make sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the Series 300. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.

Line Connections

Refer to the Wiring Diagram provided with your Series 300 ATS. All wiring must be made in accordance with the National Electrical Code and local codes.

It is unnecessary to remove pole covers from the transfer switch. If you do remove them, reinstall them carefully.

De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.

Controller Ground

A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).

1---1

Image 5
Contents Operator’s Manual 600 800 1000 1200 Nameplate Catalog Number IdentificationController Membrane controls Rating LabelPage Section InstallationEngine Starting Contacts InstallationAuxiliary Circuits Connections to ControllerManual Operation Test Installation Functional TestATS Position Handle Indicators Voltage Checks Close the enclosure door first Electrical OperationTransfer To Emergency Sequence of OperationDisconnecting the Controller Testing & ServicePreventive Maintenance TROUBLE-SHOOTING Testing & ServiceProceed with care Automatic transfer switch is energized Manual Load TransferTime Delay Adjustment AdjustmentsSensor Adjustments Time Delay SettingsClose the enclosure door AdjustmentsHow to Change a Setting DIP Switch Settings Control Features Engine ExercisersHow to Set Built-In Timer BUILT-IN Engine ExerciserProgrammable Engine Exerciser Module Control FeaturesFast / Slow Adjust Display Daylight Savings Time Adjust DisplayFill in your settings for future reference Navigating the MenuLoad Disconnect Feature Remote Control FeaturesInphase Monitor For Motor Load Transfer Strip Heater Accessory Control Features Optional Strip Heater AccessoryAvailable Kits from Asco ControlsIndex