INSTALLATION (continued)

Engine Starting Contacts

Customer connections for engine control contact and TS auxiliary contacts connections are located on terminal block TB which is mounted on the front lower left of the transfer switch. Refer to wiring diagram provided with the Series 300 ATS and connect the engine start wires to the appropriate terminals. See Figure 1–1 and Table A.

left side of

transfer switch

Table A. Engine start

connections.

When normal

Terminals

on transfer

source fails

switch

 

contact closes

TB1 and TB2

contact opens

TB1 and TB3

Auxiliary Circuits

COMMON

FEATURE 7

closes to start

FEATURE 8

opens to start

COMMON

FEATURE 14B

closed on emergency

FEATURE 14A

closed on normal

Engine Starting

Signals

5 amps, 32 V DC

5 amps resistive 28 V DC

or 120 V AC max.

TS Auxiliary Contacts Feature 14A & 14B

10 amps, 32 V DC

10 amps 250 V AC

general purpose

Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this Series 300 Automatic Transfer Switch. Make the neces- sary auxiliary connections by refer- ring to Section 5, Control Features.

Optional

COMMON TS Auxiliary Contacts

Feature 14AA & 14BA

FEATURE 14BA

10 amps, 32 V DC

closed on emergency

10 amps 250 V AC

FEATURE 14AA

general purpose

closed on normal

 

terminal block for engine start and

auxiliary circuit connections

Connections to Controller

for other Control Features

Figure 1-1. Engine start and auxiliary circuit

(located on bottom of Controller)

terminal block TB located on the transfer switch.

Load Disconnect

Programmable

Feature

Engine Exerciser

Connections

connection,

(see Wiring Diagram

if provided

& refer to page 5–4

(refer to

for DIP switch settings) page 5–3)

Remote Control Features Connections

 

(refer to the Wiring Diagram &

 

page 5–4 for DIP switch settings)

 

Each control contact must be suitable

for factory

for a 5 V DC low energy circuit.

use only

Figure 1-2. Input / output label on the Controller showing possible connections to the lower terminal block.

1---2

Image 6
Contents Operator’s Manual Nameplate Catalog Number Identification 600 800 1000 1200Rating Label Controller Membrane controlsPage Installation SectionAuxiliary Circuits InstallationEngine Starting Contacts Connections to ControllerInstallation Functional Test ATS Position Handle IndicatorsManual Operation Test Voltage Checks Electrical Operation Close the enclosure door firstSequence of Operation Transfer To EmergencyTesting & Service Preventive MaintenanceDisconnecting the Controller Proceed with care Automatic transfer switch is energized Testing & ServiceTROUBLE-SHOOTING Manual Load TransferSensor Adjustments AdjustmentsTime Delay Adjustment Time Delay SettingsAdjustments How to Change a SettingClose the enclosure door How to Set Built-In Timer Control Features Engine ExercisersDIP Switch Settings BUILT-IN Engine ExerciserControl Features Programmable Engine Exerciser ModuleFill in your settings for future reference Daylight Savings Time Adjust DisplayFast / Slow Adjust Display Navigating the MenuRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Available Kits from Asco Control Features Optional Strip Heater AccessoryStrip Heater Accessory ControlsIndex