Emerson Series 300 manual Rating Label, Controller Membrane controls

Page 3

ASCO Series 300 Automatic Transfer Switches (ATSs) are Listed under Underwriters Laboratories UL 1008 Standard for Safety for Automatic Transfer Switches. All control features are UL Component Recognized, which assures that ASCO automatic transfer switches meet OSHA Safety Requirements and will be acceptable to electrical inspectors.

ASCO Series 300 Automatic Transfer Switches are suitable for emergency and standby system applications. They meet emergency system rating requirements as defined in National Electrical Code (NEC) Article 700 and UL 1008. Also, they are suitable for the requirements of NEC Article 517 – Health Care Facilities, NEC Article 701 – Legally Required Standby Systems, NEC Article 702 – Optional

neutral connections

power connections

Transfer

Switch

terminal block TB

for engine start

and switch

position contacts

power connections

neutral connections

Standby Systems, NFPA 99 Health Care Facilities, and NFPA 110 Emergency and Standby Power Systems.

Rating Label

Each automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.

Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.

Controller

membrane controls

800 and 1000 amp. size in typical enclosure with location of customer connections

Image 3
Contents Operator’s Manual 600 800 1000 1200 Nameplate Catalog Number IdentificationController Membrane controls Rating LabelPage Section InstallationConnections to Controller InstallationEngine Starting Contacts Auxiliary CircuitsInstallation Functional Test ATS Position Handle IndicatorsManual Operation Test Voltage Checks Close the enclosure door first Electrical OperationTransfer To Emergency Sequence of OperationTesting & Service Preventive MaintenanceDisconnecting the Controller Manual Load Transfer Testing & ServiceTROUBLE-SHOOTING Proceed with care Automatic transfer switch is energizedTime Delay Settings AdjustmentsTime Delay Adjustment Sensor AdjustmentsAdjustments How to Change a SettingClose the enclosure door BUILT-IN Engine Exerciser Control Features Engine ExercisersDIP Switch Settings How to Set Built-In TimerProgrammable Engine Exerciser Module Control FeaturesNavigating the Menu Daylight Savings Time Adjust DisplayFast / Slow Adjust Display Fill in your settings for future referenceRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Controls Control Features Optional Strip Heater AccessoryStrip Heater Accessory Available Kits from AscoIndex