INSTALLATION (continued)

observe these lights

Figure 1–5. St andard controls and indicators.

2 – Voltage Checks

First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.

Verify that the feeders have been connected to the proper lugs.

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–5.

Black circle means light is on.

White circle means light is off.

*If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switch will respond only to the rated voltage specified on the Transfer Switch nameplate.

Close the normal source circuit

Source Accepted

breaker. The Normal Transfer

1 Switch Position and the Normal

Normal

Source Accepted lights should

Emergency

come on.

 

Use an accurate voltmeter to check phase to phase and

2phase to neutral voltages pres- ent at the transfer switch normal source terminals.

Close the emergency source

Source Accepted

circuit breaker. (Start generator,

3 if necessary.) The Emergency

Normal

Source Accepted light should

Emergency

come on.

 

Use an accurate voltmeter to check phase to phase and

4phase to neutral voltages pres- ent at the transfer switch emer- gency source terminals.*

 

Use a phase rotation meter to

A B C

 

 

5

check phase rotation of emer-

 

gency source; it must be the

 

 

same as the normal source.

 

 

Shut down the engine–genera-

 

 

tor, if applicable. The Emergen-

Source Accepted

 

cy Source Accepted light should

6 go off. Then put the starting

Normal

 

control selector switch (on the

 

Emergency

 

generator set) in the automatic

 

 

position. Close enclosure door.

 

Now continue to 3 – Electrical Operation on next page.

1---4

Image 8
Contents Operator’s Manual Nameplate Catalog Number Identification 600 800 1000 1200Rating Label Controller Membrane controlsPage Installation SectionInstallation Engine Starting ContactsAuxiliary Circuits Connections to ControllerManual Operation Test Installation Functional TestATS Position Handle Indicators Voltage Checks Electrical Operation Close the enclosure door firstSequence of Operation Transfer To EmergencyDisconnecting the Controller Testing & ServicePreventive Maintenance Testing & Service TROUBLE-SHOOTINGProceed with care Automatic transfer switch is energized Manual Load TransferAdjustments Time Delay AdjustmentSensor Adjustments Time Delay SettingsClose the enclosure door AdjustmentsHow to Change a Setting Control Features Engine Exercisers DIP Switch SettingsHow to Set Built-In Timer BUILT-IN Engine ExerciserControl Features Programmable Engine Exerciser ModuleDaylight Savings Time Adjust Display Fast / Slow Adjust DisplayFill in your settings for future reference Navigating the MenuLoad Disconnect Feature Remote Control FeaturesInphase Monitor For Motor Load Transfer Control Features Optional Strip Heater Accessory Strip Heater AccessoryAvailable Kits from Asco ControlsIndex