SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS

These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without load transfer, or they can be completely disabled. The engine-generator should be exercised under load once a week for a minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.

BUILT–IN ENGINE EXERCISER

The engine exerciser included in ASCO Series 300 Automatic Transfer Switches provides a once a week 20–minute exercise period. It occurs immediately when the Set Engine Exerciser push button is pressed (and held for at least 5 seconds), and then at the same time weekly thereafter. A 9 volt alkaline battery (DuracellR MN1604, EverreadyR 522, or PanasonicR 6AM6) is furnished and installed in the controller to maintain the setting. The battery jumper block must be shifted to the ON position. See Figure 4–2 on page 4–2.

Fill in day and time set. Week Day ______ Time _______.

DIP Switch Settings

FUNCTION

S1 DIP

 

 

 

S2 DIP

 

 

SWITCH

 

 

 

SWITCH

 

 

 

 

 

 

 

 

Std. Timer

Actuator

 

 

 

 

 

 

 

7

 

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Enabled

7 on

 

 

 

 

 

 

 

 

5 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std. Timer

Actuator

 

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

 

 

 

 

7

 

 

5

 

Disabled

7 off

 

 

 

 

 

 

5 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

without

 

 

 

8

 

 

 

 

 

 

 

8 off

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exercise

Actuator

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with Load

8 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

Press to cancel an active exercise

status light

 

Press and hold for 5 sec. or until status light

period (stops generator).

 

blinks rapidly to set exercise period immediately

If Exercise with Load is set, retransfers load to

and every week hereafter (generator starts).

 

If Exerciser with Load is set,

Normal, then stops generator after min. cooldown.

 

Figure 5-1. Operator panel pushbuttons and light.

transfers load to Emergency.

 

Select below either Exercise without Load or Exercise with Load according to the setting of DIP switch S1, actuator 8. The load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.

Exercise without Load, DIP Switch S1, Actuator 8 off

8

How to Set Built–In Timer

Step

 

 

 

Function

Explanation

 

Push Button

 

Status Light

 

 

 

 

 

 

 

Set Engine

 

blinks rapidly

 

Exercise the generator now and

1

Exerciser

 

set exercise period

 

●❍●❍●❍

every week at this time hereafter.

 

hold 5 sec.

 

 

 

 

 

 

 

2

release

 

blinks slowly

exercise period now active

Generator starts and runs.

 

●❍❍●❍❍

 

 

 

 

 

3

press Bypass

 

stays on

cancel active exercise period

Generator stops.

Time Delay

 

 

 

 

 

 

4

 

stays on

generator off

Exerciser enabled; repeats every 7 days.

Exercise with Load, DIP Switch S1, Actuator 8 on

8

How to Set Built–In Timer

Step

 

 

 

Function

Explanation

 

Push Button

 

Status Light

 

 

 

 

 

 

 

Set Engine

 

blinks rapidly

 

Exercise the generator now and

1

Exerciser

 

set exercise period

 

●❍●❍●❍

every week at this time hereafter.

 

hold 5 sec.

 

 

 

 

 

 

 

2

release

 

blinks slowly

exercise period now active

Generator starts and runs;

 

●❍❍●❍❍

the load transfers to Emergency.

 

 

 

 

 

press Bypass

 

blinks slowly

 

The load retransfers to Normal; then

3

 

cancel active exercise period

generator runs for 5 minute cooldown

Time Delay

 

●❍❍●❍❍

 

 

 

( light blinks slowly during cooldown ).

 

 

 

 

 

4

 

stays on

generator off

Exerciser enabled; repeats every 7 days.

NOTE: Every time SET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.

5---1

Image 15
Contents Operator’s Manual 600 800 1000 1200 Nameplate Catalog Number IdentificationController Membrane controls Rating LabelPage Section InstallationConnections to Controller InstallationEngine Starting Contacts Auxiliary CircuitsInstallation Functional Test ATS Position Handle IndicatorsManual Operation Test Voltage Checks Close the enclosure door first Electrical OperationTransfer To Emergency Sequence of OperationTesting & Service Preventive MaintenanceDisconnecting the Controller Manual Load Transfer Testing & ServiceTROUBLE-SHOOTING Proceed with care Automatic transfer switch is energizedTime Delay Settings AdjustmentsTime Delay Adjustment Sensor AdjustmentsAdjustments How to Change a SettingClose the enclosure door BUILT-IN Engine Exerciser Control Features Engine ExercisersDIP Switch Settings How to Set Built-In TimerProgrammable Engine Exerciser Module Control FeaturesNavigating the Menu Daylight Savings Time Adjust DisplayFast / Slow Adjust Display Fill in your settings for future referenceRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Controls Control Features Optional Strip Heater AccessoryStrip Heater Accessory Available Kits from AscoIndex