The Device Configurator Screen for Series 300 ATSs shows the Group 1 controller configuration settings (right side) and the Connectivity Module (server) configuration settings (left side) for the selected ATS.

Group 1 Controller Configuration (right side)

Enter or change the ATS Name (8 char. max.) and the ATS Location (20 char. max.). Press the Update button when finished to save the Group 1 controller configuration changes.

Connectivity Module (server) Configuration (left side)

Several configuration settings must be set appropriately as described below. Press the Update Server button when finished to save configuration changes.

Consult with your network administrator for these 4 settings:

IP Address

Subnet Mask

Gateway Address

TCP Port Number

(Range of ports allowed is:

1024-65535, but do not use

ports 14000-14009 or 30718)

Serial Port Speed 9600 Flow Control No flow control Interface Mode RS485-4 or 2 Wire

Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)

ATS Name

ATS Location

Press Update button when finished to save the configuration changes. Do this before you press Update Server button.

After Controller or has been updated, press Update Server button to save the configuration changes.

SNMP refer to Appendix A-5

Device Configurator Screen for Series 300 ATSs

When a Power Manager or Digital Power Meter is connected, additional buttons appear at the bottom of the Connectivity Module Device Configuration screen.

Press to configure the Power Manager or Digital Power Meter.

Press to configure the Group 1 Controller.

After Controller, PM, or DPM has been updated, press Update Server button to save the configuration changes.

Additional Buttons on Device Configurator Screen for

Series 300 ATSs with Power Manager or Digital Power Meter

Image 16
Contents Connectivity Module 381333-367 BWho Should Use this Installation Manual Ii Welcome Connectivity ModulePrerequisites Important informationSpecifications Installation OverviewCheck the DIP Switch Settings for RS485 DIP Switch on bottom of unitIv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Status LEDs LED Description LED Function / Mode of OperationConnectivity Module Status LEDs Installation How to Install the Connectivity Module on Asco 940/962 ATSsConnectivity Module Installation How to Test Communication to the Connectivity ModuleHttp//169.254.1.1/config.htm Installation Connectivity ModuleDevice Configurator Screen for 7000 & 4000 Series ATSs Group 5 Controller Configuration right sideConnectivity Module server Configuration left side Device Configurator Screen for 7000 & 4000 Series ATSsInput Name & Output Names Power Manager only Power Manager or Power Meter Configuration7000 & 4000 Series ATSs Connectivity Module Detail Screen for 7000 & 4000 Series ATSs Device Configurator Screen for Series 300 ATSs Group 1 Controller Configuration right sideDevice Configurator Screen for Series 300 ATSs Series 300 ATSs Connectivity ModuleConnectity Module Series 300 ATSs Detail Screen for Series 300 ATSs with a Power Manager Detail Screen for Series 300 ATSsDevice Configurator Screen for Asco 940/962 ATSs Group 7A Controller Configuration right sideDevice Configurator Screen without Power Manager Device Configurator Screen with Power ManagerDetail Screen for Asco 940/962 ATSs Detail Screen for Asco 940/962 ATSs with a Power ManagerAsco 940/962 ATSs Connectivity Module Power Manager or Power Meter Configuration Detail Screen for Power Managers connected to a Load Detail Screen for Digital Power Meters connected to a LoadDetail Screen for Power Managers connected to a Generator Detail Screen for PowerDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Connectivity Module Troubleshooting A-3 Problem CauseThird Party Modbus Device Configuration Read RequestsConnectivity Module Snmp Internet-standard Protocol A-5 Snmp Trap messagesProblem Cause Solution Snmp Internet-standard Protocol Connectivity ModuleSerial No Row IP Address Subnet Mask GatewayCatalog No Address set ATS Controller PM or DPM Index