Emerson CATALOG 5150 installation manual Third Party Modbus Device Configuration, Read Requests

Page 28

A-4 Create Favorites folder, 3rd Party Modbus Configuration

Connectivity Module

How to create a Favorites folder for ASCO device pages and copy it to another computer

To create a favorites folder and copy it to another user’s computer, the administrator should follow these steps:

1.Open the first page and then pull down the Favorites manual and select Add to Favorites … This window will appear:

2.Click the New Folder button, type the new folder name as asco, then click the OK button.

3.Click folder asco and click OK.

4.Open the other pages one by one and click Add to Favorite, click folder asco, then click OK.

5.Once the administrator is done with saving all the pages, the following steps describe how to copy the asco folder from the administrator’s computer to another user’s computer.

a.For Windows XP, find the asco folder from directory ‘c:documentd and settings\’user name’\favorites’.

b.Copy the asco folder into the corresponding path above.

c.Open browser and select address or name from favorite asco folder to view the device pages.

Third Party Modbus Device Configuration

The Connectivity Module supports the Modbus devices with Modbus/TCP portocol. The transmit and receiving data format are as follows:

Read:

Requests:

Bytes 0, 1 Transaction ID.

Usually zero when making a request, the server will copy them into the response.

Bytes 2, 3 Protocol number. It must be zero. Byte 4 length (high byte) its always zero.

Byte 5 length (low byte) of the following total bytes Byte 6 device address

Byte 7 function code

Bytes 8, 9 Modbus address of the starting transfer. Bytes 10, 11 number of word to transfer

Response:

Bytes 0, 1 Transaction ID. Its faithfully copied from the request

Bytes 2, 3 Protocol number. It always is zero. Byte 4 length (high byte) its always zero

Byte 5 length (low byte) of the following total bytes Byte 6 device address

Byte 7 function code

Bytes 8 byte count of Modbus data. Bytes rest data values

Configure the Connectivity Module to properly communicate with the other devices. The following items should be ready before you start to configure it:

1.Ethernet crossover cable.

2.Laptop with proper Ethernet connect ability.

3.Start Internet browser and type ‘IP address\config.htm’ on the browser address field.

4.This page should appear:

From this page,

xxx

configure all the

 

parameters except

 

reply timeout which

 

needs to configured

 

from client device.

 

Image 28
Contents Connectivity Module 381333-367 BWho Should Use this Installation Manual Ii Welcome Connectivity ModulePrerequisites Important informationSpecifications Installation OverviewCheck the DIP Switch Settings for RS485 DIP Switch on bottom of unitIv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Status LEDs LED Description LED Function / Mode of OperationConnectivity Module Status LEDs Installation How to Install the Connectivity Module on Asco 940/962 ATSsConnectivity Module Installation How to Test Communication to the Connectivity ModuleHttp//169.254.1.1/config.htm Installation Connectivity ModuleDevice Configurator Screen for 7000 & 4000 Series ATSs Group 5 Controller Configuration right sideConnectivity Module server Configuration left side Device Configurator Screen for 7000 & 4000 Series ATSsInput Name & Output Names Power Manager only Power Manager or Power Meter Configuration7000 & 4000 Series ATSs Connectivity Module Detail Screen for 7000 & 4000 Series ATSs Device Configurator Screen for Series 300 ATSs Group 1 Controller Configuration right sideDevice Configurator Screen for Series 300 ATSs Series 300 ATSs Connectivity ModuleConnectity Module Series 300 ATSs Detail Screen for Series 300 ATSs with a Power Manager Detail Screen for Series 300 ATSsDevice Configurator Screen for Asco 940/962 ATSs Group 7A Controller Configuration right sideDevice Configurator Screen without Power Manager Device Configurator Screen with Power ManagerDetail Screen for Asco 940/962 ATSs Detail Screen for Asco 940/962 ATSs with a Power ManagerAsco 940/962 ATSs Connectivity Module Power Manager or Power Meter Configuration Detail Screen for Power Managers connected to a Load Detail Screen for Digital Power Meters connected to a LoadDetail Screen for Power Managers connected to a Generator Detail Screen for PowerDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Connectivity Module Troubleshooting A-3 Problem CauseThird Party Modbus Device Configuration Read RequestsConnectivity Module Snmp Internet-standard Protocol A-5 Snmp Trap messagesProblem Cause Solution Snmp Internet-standard Protocol Connectivity ModuleSerial No Row IP Address Subnet Mask GatewayCatalog No Address set ATS Controller PM or DPM Index