Emerson CATALOG 5150 installation manual Device Configurator Screen for Asco 940/962 ATSs

Page 19

Connectivity Module

ASCO 940/962 ATSs 4-1

Device Configurator Screen for ASCO 940/962 ATSs

The Device Configurator Screen for ASCO 940/962 ATSs shows the Group 7A controller configuration settings (right side) and the Connectivity Module (server) configuration settings (left) for the selected ATS.

Group 7A Controller Configuration (right side)

Enter or change the ATS Name (18 char. max.) and ATS Nominal Voltage (must be entered to get correct reading). Press the Update button when finished to save the Group 7A controller configuration changes.

Connectivity Module (server) Configuration (left side)

Several configuration settings must be set appropriately as described below. Press the Update Server button when finished to save configuration changes.

Consult with your network administrator for these 4 settings:

IP Address

Subnet Mask

Gateway Address

TCP Port Number

(Range of ports allowed is:

10024-65535, but do not use

ports 1400-14009 or 30718)

Serial Port Speed 9600

Flow Control No flow control

Interface Mode RS485-4 or 2 Wire

Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)

ATS Name

Nom. Voltage

xxx

Press Update button when finished to save the configuration

Press Update Server button when finished to save the configuration changes.

Consult with your network administrator for these 4 settings:

IP Address

Subnet Mask

Gateway Address

TCP Port Number

(Range of ports allowed is:

10024-65535, but do not use

ports 1400-14009 or 30718)

Serial Port Speed 9600 Flow Control No flow control Interface Mode RS422/485-4Wire

Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)

Device Configurator Screen without Power Manager

ATS Name

Nom. Voltage

xxx

Press Update button when finished to save the configuration

Press Update Server button when finished to save the configuration changes.

Device Configurator Screen with Power Manager

Image 19
Contents 381333-367 B Connectivity ModuleImportant information Who Should Use this Installation ManualIi Welcome Connectivity Module PrerequisitesDIP Switch on bottom of unit SpecificationsInstallation Overview Check the DIP Switch Settings for RS485Iv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Status LEDs LED Description LED Function / Mode of OperationConnectivity Module Status LEDs How to Install the Connectivity Module on Asco 940/962 ATSs InstallationHow to Test Communication to the Connectivity Module Connectivity Module InstallationInstallation Connectivity Module Http//169.254.1.1/config.htmDevice Configurator Screen for 7000 & 4000 Series ATSs Device Configurator Screen for 7000 & 4000 Series ATSsGroup 5 Controller Configuration right side Connectivity Module server Configuration left sideInput Name & Output Names Power Manager only Power Manager or Power Meter Configuration7000 & 4000 Series ATSs Connectivity Module Detail Screen for 7000 & 4000 Series ATSs Series 300 ATSs Connectivity Module Device Configurator Screen for Series 300 ATSsGroup 1 Controller Configuration right side Device Configurator Screen for Series 300 ATSsConnectity Module Series 300 ATSs Detail Screen for Series 300 ATSs Detail Screen for Series 300 ATSs with a Power ManagerDevice Configurator Screen with Power Manager Device Configurator Screen for Asco 940/962 ATSsGroup 7A Controller Configuration right side Device Configurator Screen without Power ManagerDetail Screen for Asco 940/962 ATSs Detail Screen for Asco 940/962 ATSs with a Power ManagerAsco 940/962 ATSs Connectivity Module Power Manager or Power Meter Configuration Detail Screen for Digital Power Meters connected to a Load Detail Screen for Power Managers connected to a LoadDetail Screen for Power Detail Screen for Power Managers connected to a GeneratorDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Problem Cause Connectivity Module Troubleshooting A-3Read Requests Third Party Modbus Device ConfigurationSnmp Trap messages Connectivity Module Snmp Internet-standard Protocol A-5Snmp Internet-standard Protocol Connectivity Module Problem Cause SolutionSerial No Row IP Address Subnet Mask GatewayCatalog No Address set ATS Controller PM or DPM Index