Connectivity Module

Installation 1-2

How to Install the Connectivity Module for a stand-alone Power Manager or Digital Power Meter

The Connectivity Module (CM) mounts on a DIN rail near the Power Manager (PM) or Digital Power Meter (DPM). A long serial cable connects the Connectivity Module to the PM or DPM. Refer to installation drawings provided and follow the steps below to install the Connectivity Module.

Connectivity Module Kit K889958

for a stand-alone Power Manager or Digital Power Meter (not connected to an ATS)

Connectivity

Module 5150

DIN Rail and

Hardware

4 ft. Serial Cable

for PM or DPM

!DANGER

To avoid possible shock, burns, or death, deenergize all electrical sources to the ATS before installing the Connectivity Module.

1.De-energize the power source that feeds the PM (or DPM). Open enclosure door and check with a non-contact AC voltage detector.

2.Mount the DIN rail (supplied in the kit) onto two studs (on the door) below or adjacent to the PM or DPM.

3.Install Connectivity Module onto DIN rail by hooking the bottom of module on bottom of DIN rail and rocking it upward unit it snaps in place.

4.Install the 4-foot serial cable between the Power Manager J5 receptacle (or Digital Power Meter J2 receptacle) and the Connectivity Module J2 receptacle.

Now test communications (go to next column).

How to Test Communication to the Connectivity Module

You need the following settings from your network administrator for each Connectivity Module (CM) connected to an Automatic Transfer Switch (ATS), Power Manager (PM), or Digital Power Meter (DPM). Fill in the form provided in the Appendix:

IP Address: ______________ (unique for each module)

Subnet mask __________ (usually same for all modules)

Gateway: ________________________ (usually blank)

Required items:

Portable laptop computer with network card, running Windows Xp and Windows Internet Explorer 6.0 + installed.

Ethernet crossover network cable (part no. 629590-006).

Connectivity Module connected to the ATS, PM, or DPM.

1.Directly connect the specified Ethernet crossover cable between your laptop’s Ethernet jack and the deenergized Connectivity Module jack J3.

2.For safety, close the ATS, PM, or DPM enclosure door as far as possible (with the crossover cable running to the laptop computer outside the enclosure). Then energize ATS, PM, or DPM and the Connectivity Module.

3.Refer to the Appendix and select the appropriate TCP/IP Installation & Configuration instructions for your laptop computer’s operating system. This procedure sets up your laptop computer (if necessary) for network connections and tests communications to the Connectivity Module.

4.After you have confirmed communication with the Connectivity Module, continue to the next page to view and change the configuration of the Connectivity Module and ATS, PM, or DPM.

Now view and change the configuration

(go to page 1-3)

Image 11
Contents 381333-367 B Connectivity ModuleImportant information Who Should Use this Installation ManualIi Welcome Connectivity Module PrerequisitesDIP Switch on bottom of unit SpecificationsInstallation Overview Check the DIP Switch Settings for RS485Iv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Connectivity Module Status LEDs LED Description LED Function / Mode of OperationStatus LEDs How to Install the Connectivity Module on Asco 940/962 ATSs InstallationHow to Test Communication to the Connectivity Module Connectivity Module InstallationInstallation Connectivity Module Http//169.254.1.1/config.htmDevice Configurator Screen for 7000 & 4000 Series ATSs Device Configurator Screen for 7000 & 4000 Series ATSsGroup 5 Controller Configuration right side Connectivity Module server Configuration left side7000 & 4000 Series ATSs Connectivity Module Power Manager or Power Meter ConfigurationInput Name & Output Names Power Manager only Detail Screen for 7000 & 4000 Series ATSs Series 300 ATSs Connectivity Module Device Configurator Screen for Series 300 ATSsGroup 1 Controller Configuration right side Device Configurator Screen for Series 300 ATSsConnectity Module Series 300 ATSs Detail Screen for Series 300 ATSs Detail Screen for Series 300 ATSs with a Power ManagerDevice Configurator Screen with Power Manager Device Configurator Screen for Asco 940/962 ATSsGroup 7A Controller Configuration right side Device Configurator Screen without Power ManagerAsco 940/962 ATSs Connectivity Module Detail Screen for Asco 940/962 ATSs with a Power ManagerDetail Screen for Asco 940/962 ATSs Power Manager or Power Meter Configuration Detail Screen for Digital Power Meters connected to a Load Detail Screen for Power Managers connected to a LoadDetail Screen for Power Detail Screen for Power Managers connected to a GeneratorDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Problem Cause Connectivity Module Troubleshooting A-3Read Requests Third Party Modbus Device ConfigurationSnmp Trap messages Connectivity Module Snmp Internet-standard Protocol A-5Snmp Internet-standard Protocol Connectivity Module Problem Cause SolutionCatalog No Address set ATS Controller PM or DPM Row IP Address Subnet Mask GatewaySerial No Index