Emerson OpenComms-485 manual Input Register Holding Register # of Reg Scale

Page 23

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Point

Input Register

Holding Register

# of Reg.

Scale

Notes / Units

Number Of Input

30004

40004

1

1

 

Bits 12 - 15

Lines

 

 

Number Of

30004

40004

1

1

 

Bits 4 - 7

Bypass Lines

 

Bits 8 - 11

Number Of Output

30004

40004

1

1

 

Lines

 

 

Number Of

 

 

 

 

 

 

SubModules

30009

40009

1

1

 

There are 16 possible Load

Load Circuit

 

 

 

 

 

Present

 

 

 

 

 

Circuits. So each bit represents 1

 

 

 

 

 

 

load circuit. Load Circuit 1 is bit 0,

 

 

 

 

 

 

Load Circuit 2 is bit 1 and so on. If

 

 

 

 

 

 

the bit is 1 then the Load Circuit is

 

30013

40013

1

 

 

supported.

Battery Cabinet

30018

40018

2

1

 

 

Type

 

 

Battery Cabinet

 

 

 

 

 

 

Number

30019

40019

1

1

 

 

Battery AmpHour

30020

40020

1

1

 

AH

Nominal Power

30021

40021

2

1

 

VA

Rating

 

V

Nominal Input

30027

40027

1

1

 

Voltage

 

 

Nominal Output

30028

40028

1

1

 

V

Voltage

 

V

Nominal Static

 

 

 

 

 

Bypass Switch

30029

40029

1

1

 

 

Voltage

 

 

Nominal Input

30030

40030

1

1

 

A

Current

 

Hz

Nominal Input

30031

40031

1

10

 

Frequency

 

 

Nominal Output

30032

40032

1

10

 

Hz

Frequency

 

 

Nominal Power

 

 

 

 

 

 

Factor

30033

40033

1

100

 

 

Nominal Battery

 

 

 

 

 

V

Voltage

30034

40034

1

1

 

 

Auto Restart Delay

30051

40051

1

1

 

seconds

Device Low

 

 

 

 

 

min

Battery Time

30053

40053

1

1

 

VA

Load (Apparent

30102

 

2

1

 

Power)

 

 

 

Load (Real Power)

30104

 

2

1

 

W

Load / Capacity

30106

 

1

1

%

Input Frequency

30107

 

1

10

 

Hz

Output Frequency

30108

 

1

10

 

Hz

Bypass Frequency

30109

 

1

10

 

Hz

 

 

 

 

 

 

 

20

Image 23
Contents Monitoring Revision Level Updates Table of Contents Modbus Communications Connectivity to OpenComms-485 using ModbusModbus Packet Format RTU Framing Status Coil Scale Reg Liebert NfinityInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Data Point Status Coil # of Reg Scale Liebert NxREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Data Point Status Coil # of Reg Liebert PowerSure InteractiveInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Status Coil # of Reg Scale Liebert GXT2REV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development # of Reg Scale Liebert HiNetInput Holding Register Data Point Liebert UPS SeriesInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Data points Mapped to Input Status and Coils Liebert DSMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service