Liebert Monitoring Group –Development

Battery Charge Percentage

30116

 

1

1

%

Battery Temperature

30117

 

1

1

deg C

Transformer Temperature

30121

 

1

1

deg C

Redundant Power Modules

30124

 

1

1

 

Active Power Module Count

30126

 

1

1

 

Battery Module Active

 

 

 

 

 

Count

30127

 

1

1

 

Battery Test Result

30130

 

1

1

 

Input Voltage L1

30153

 

1

1

V

Input Current L1

30154

 

1

1

A

Bypass Voltage L1

30159

 

1

1

V

Bypass Current L1

30160

 

1

1

A

Output Voltage L1

30163

 

1

1

V

Output Current L1

30164

 

1

1

A

Power Module Failure

 

 

 

 

 

Count

30304

 

1

1

 

Battery Module Failure

 

 

 

 

 

Count

30305

 

1

1

 

Power Module Warning

30306

 

1

1

 

Count

 

 

Battery Module Warning

30307

 

1

1

 

Count

 

 

6

Image 9
Contents Monitoring Revision Level Updates Table of Contents Modbus Communications Connectivity to OpenComms-485 using ModbusModbus Packet Format RTU Framing Status Coil Scale Reg Liebert NfinityInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Data Point Status Coil # of Reg Scale Liebert NxREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Data Point Status Coil # of Reg Liebert PowerSure InteractiveInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Status Coil # of Reg Scale Liebert GXT2REV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert HiNet Input Holding Register# of Reg Scale Data Point Liebert UPS SeriesInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Data points Mapped to Input Status and Coils Liebert DSMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service