Emerson OpenComms-485 manual Battery Charger Fail 10234

Page 30

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Battery Charger Fail

10234

 

1

1

 

Data Point

Input

Holding

# of

Scale

Notes / Units

 

Register

Register

Reg.

 

 

Number Of Input Lines

30004

40004

1

1

Bits 12 - 15

Number Of Bypass

30004

40004

1

1

Bits 4 - 7

Lines

 

 

 

 

 

Number Of Output

30004

40004

1

1

Bits 8 - 11

Lines

 

 

 

 

 

Number Of

30009

40009

1

1

 

SubModules

 

 

 

 

 

Load Circuit Present

30013

40013

1

 

There are 16 possible Load

 

 

 

 

 

Circuits. So each bit represents 1

 

 

 

 

 

load circuit. Load Circuit 1 is bit

 

 

 

 

 

0, Load Circuit 2 is bit 1 and so

 

 

 

 

 

on. If the bit is 1 then the Load

 

 

 

 

 

Circuit is supported.

Nominal Power Rating

30021

40021

2

1

VA

Nominal Input Voltage

30027

40027

1

1

V

Nominal Output

30028

40028

1

1

V

Voltage

 

 

 

 

 

Nominal Static Bypass

30029

40029

1

1

V

Switch Voltage

 

 

 

 

 

Nominal Input Current

30030

40030

1

1

A

Nominal Input

30031

40031

1

10

Hz

Frequency

 

 

 

 

 

Nominal Output

30032

40032

1

10

Hz

Frequency

 

 

 

 

 

Nominal Power Factor

30033

40033

1

100

 

Nominal Battery

30034

40034

1

1

V

Voltage

 

 

 

 

 

Device Low Battery

30053

40053

1

1

min

Time

 

 

 

 

 

Load (Apparent

30102

 

2

1

VA

Power)

 

 

 

 

 

Load (Real Power)

30104

 

2

1

W

Load / Capacity

30106

 

1

1

%

Input Frequency

30107

 

1

10

Hz

Output Frequency

30108

 

1

10

Hz

Bypass Frequency

30109

 

1

10

Hz

Battery Charge Status

30112

 

1

1

1 - 100% Charged

 

 

 

 

 

2 - Less than 100% Charged

Battery Voltage

30113

 

1

1

V

 

 

 

 

 

 

Battery Current

30114

 

1

1

A

Battery Time

30115

 

1

1

min

Remaining

 

 

 

 

 

Battery Charge

30116

 

1

1

%

Percentage

 

 

 

 

 

Battery Test Result

30130

 

1

1

1 - Unknown

 

 

 

 

 

2 - Passed

 

 

 

 

 

3 - Failed

4 - In Progress

5 - System Failure

6 - Inhibited

27

Image 30
Contents Monitoring Revision Level Updates Table of Contents Connectivity to OpenComms-485 using Modbus Modbus CommunicationsModbus Packet Format RTU Framing Liebert Nfinity Status Coil Scale RegInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert Nx Data Point Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Liebert PowerSure Interactive Data Point Status Coil # of RegInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert GXT2 Status Coil # of Reg ScaleREV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert HiNet Input Holding Register# of Reg Scale Liebert UPS Series Data PointInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Liebert DS Data points Mapped to Input Status and CoilsMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service