Emerson OpenComms-485 manual Liebert PowerSure Interactive, Data Point Status Coil # of Reg

Page 15

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Liebert PowerSure Interactive

Supported Modbus Points

Data Point

Status

Coil

# of Reg.

Scale

 

Notes /Units

 

Audible Alarm Enabled

10002

2

1

 

1

 

 

Automatic Battery Test

10003

3

1

 

1

 

 

Enabled

 

 

 

Battery Charge

 

 

 

 

 

 

 

Compensation

10046

 

1

 

1

 

 

Inverter Ready

10047

 

1

 

1

 

 

Load Circuit 1 State

10057

 

1

 

1

 

 

Load Circuit 2 State

10058

 

1

 

1

 

 

Load Circuit 3 State

10059

 

1

 

1

 

 

Load Circuit 4 State

10060

 

1

 

1

 

 

Load Circuit 5 State

10061

 

1

 

1

 

 

Load Circuit 6 State

10062

 

1

 

1

 

 

Load Circuit 7 State

10063

 

1

 

1

 

 

Load Circuit 8 State

10064

 

1

 

1

 

 

Load Circuit 9 State

10065

 

1

 

1

 

 

Load Circuit 10 State

10066

 

1

 

1

 

 

Load Circuit 11 State

10067

 

1

 

1

 

 

Load Circuit 12 State

10068

 

1

 

1

 

 

Load Circuit 13 State

10069

 

1

 

1

 

 

Load Circuit 14 State

10070

 

1

 

1

 

 

Load Circuit 15 State

10071

 

1

 

1

 

 

Load Circuit 16 State

10072

 

1

 

1

 

 

Load On Inverter

10073

 

1

 

1

 

 

Boost Mode On

10075

 

1

 

1

 

 

Buck Mode On

10076

 

1

 

1

 

 

Battery Under Test

10082

 

1

 

1

 

 

Shutdown Reason - Over

 

 

 

 

 

 

 

Temperature

10086

 

1

 

1

 

 

Shutdown Reason -

 

 

 

 

 

 

 

Overload

10087

 

1

 

1

 

 

Shutdown - Output Short

10089

 

1

 

1

 

 

Shutdown Reason -

 

 

 

 

 

 

 

Remote Shutdown

10093

 

1

 

1

 

 

Load On Battery

10128

 

1

 

1

 

 

Output Off Pending

10151

 

1

 

1

 

 

Low Battery - Shutdown

10152

 

1

 

1

 

 

Imminent

 

 

 

 

Output Overload

10154

 

1

 

1

 

 

Over Temperature Warning

10171

 

1

 

1

 

 

Battery Over Temperature

 

 

 

 

 

 

 

CB Trip

10172

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

Image 15
Contents Monitoring Revision Level Updates Table of Contents Modbus Communications Connectivity to OpenComms-485 using ModbusModbus Packet Format RTU Framing Status Coil Scale Reg Liebert NfinityInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Data Point Status Coil # of Reg Scale Liebert NxREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Data Point Status Coil # of Reg Liebert PowerSure InteractiveInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Status Coil # of Reg Scale Liebert GXT2REV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Liebert HiNet Input Holding Register# of Reg Scale Data Point Liebert UPS SeriesInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Data points Mapped to Input Status and Coils Liebert DSMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service