Emerson OpenComms-485 manual REV 7/6/2007 Liebert Monitoring Group -Development

Page 31

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Input Voltage L1

30153

 

1

1

V

 

 

 

 

 

 

Input Current

30154

 

1

1

A

Bypass Voltage L1

30159

 

1

1

V

Bypass Current L1

30160

 

1

1

A

Output Voltage L1

30163

 

1

1

V

Output Current L1

30164

 

1

1

A

Input Voltage L2

30203

 

1

1

V

Input Current L2

30204

 

1

1

A

Bypass Voltage L2

30209

 

1

1

V

Bypass Current L2

30210

 

1

1

A

Output Voltage L2

30213

 

1

1

V

Output Current L2

30214

 

1

1

A

Input Voltage L3

30253

 

1

1

V

Input Current L3

30254

 

1

1

A

Bypass Voltage L3

30259

 

1

1

V

Bypass Current L3

30260

 

1

1

A

Output Voltage L3

30263

 

1

1

V

Output Current L3

30264

 

1

1

A

Black Out Count

30301

 

1

1

 

Brown Out Count

30302

 

1

1

 

Transient Count

30301

 

1

1

 

Silent Audible Alarm

 

40101

 

 

any value

Battery Start

 

40102

1

1

1=Start, 0=Abort

Open UPS Output

 

40104

 

 

Delay time in Second, last digit

Switch

 

 

 

 

will be ignored

Reboot UPS Output

 

40105

1

1

Delay time in Second, last digit

Switch

 

 

 

 

will be ignored

Close UPS Output

 

40106

 

 

Delay time in Second, last digit

Switch

 

 

 

 

will be ignored

Transfer Load to

 

40107

1

1

any value

Bypass

 

 

 

 

 

Transfer Load to

 

40108

 

 

any value

Inverter

 

 

 

 

 

Reset UPS Statistic

 

40111

1

1

any value

data

 

 

 

 

 

Turn UPS Outlets On

 

40112

1

1

Bitmap mask for Outlet 1-16. all

 

 

 

 

 

bits set to 1 will be turn On

Turn UPS Outlets Off

 

40113

1

1

Bitmap mask for Outlet 1-16. all

 

 

 

 

 

bits set to 1 will be turn Off

28

Image 31
Contents Monitoring Revision Level Updates Table of Contents Modbus Communications Connectivity to OpenComms-485 using ModbusModbus Packet Format RTU Framing Status Coil Scale Reg Liebert NfinityInput Holding Register Scale REV 7/6/2007 Liebert Monitoring Group -Development Data Point Status Coil # of Reg Scale Liebert NxREV 7/6/2007 Liebert Monitoring Group -Development Data Point Input Register Holding Register # of Reg Scale Data Point Register Coil # of Reg Scale 100 VAR Data Point Status Coil # of Reg Liebert PowerSure InteractiveInput Holding Data Point Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Supported Modbus Points Data Point Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Status Coil # of Reg Scale Liebert GXT2REV 7/6/2007 Liebert Monitoring Group -Development Input Register Holding Register # of Reg Scale REV 7/6/2007 Liebert Monitoring Group -Development Input Holding Register Liebert HiNet# of Reg Scale Data Point Liebert UPS SeriesInput Holding Scale Register REV 7/6/2007 Liebert Monitoring Group -Development Liebert UPS Series Battery Charger Fail 10234 REV 7/6/2007 Liebert Monitoring Group -Development Data points Mapped to Input Status and Coils Liebert DSMain FAN Overload Sensor a Failure Data Points Mapped to Input and Holding Registers HourMinute Sleep Interval 30042 40042 MSBHr Events/Alarm Bit0 =. Reset state Technical Support/Service